Honeywell T874/Q674 - Manual

Honeywell T874/Q674

Honeywell T874/Q674 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – LOCATION; IMPORTANT: An incorrectly leveled subbase will cause; WIRING THE SUBBASE
  • Page 6 – Settings; HEAT ANTICIPATOR SETTING; Fig. 10—Stage two adjustable heat anticipator.; TEMPERATURE SETTING; SUBBASE SETTING
  • Page 7 – Checkout; HEATING; Calibration; THERMOSTAT; They do not have provision for field calibration.; THERMOMETER
  • Page 8 – Automation and Control Solutions
Loading the manual

S. M. • Rev. 5-93 • • ©Honeywell Inc. 1993 • Form Number 60-1147—4

T874/Q674

Thermostat/Subbase Combinations

Installation Instructions for the Trained Service Technician.

Application

The T874/Q674 Thermostat/Subbase combinations provide 24 to 30 Vac control for heat pump systems. See Table 1.

TABLE 1—T874/Q674 THERMOSTAT/SUBBASE COMBINATIONS.

Thermostat/

Number

Changeover

Subbase

a

of Stages

Stage

Type of Switching

Model

Heating

Cooling

Heating

Cooling

System

Fan

See Fig.

T874N/Q674C

2

1

1

OFF-AUTO

AUTO-ON

5

T874N/Q674F

2

1

1

OFF-EM. HT.-

AUTO-ON

6

HEAT-AUTO-COOL

T874R/Q674L

2

1

2

b

EM. HT.-HEAT-

AUTO-ON

7

OFF-COOL

a

Q674 Subbase provides the wiring terminals, system switch and fan switch for system operation.

b

Provides manual changeover with the subbase system switch in COOL position.

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could cause a hazardous condition.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your applica-
tion.

3. Installer must be a trained, experienced service tech-

nician.

4. After installation is complete, check out product opera-

tion as provided in these instructions.

CAUTION

1. Disconnect power supply to prevent electrical

shock and equipment damage.

2. To prevent interference with the thermostat link-

age, keep wire length to a minimum and run
wires as close as possible to the subbase. Push
excess wire back into the hole and plug hole to
prevent drafts from affecting thermostat opera-
tion.

3. Do not overtighten thermostat captive mounting

screws because damage to subbase threads may
result.

4. Do not short across coil terminals on the relay.

This may burn out the thermostat heat
anticipator.

IMPORTANT: Thermostats are calibrated at the factory

using subbases mounted at true level. An inaccurately
leveled subbase will cause thermostat control devia-
tion.

Operation

On a two-heat thermostat, the two stages of heat make

sequentially as the temperature drops. Make refers to the
mercury switch initiating a call for heat or cool.

There are about 2

°

F [1

°

C] between stages so that the

second stage makes only when the first stage cannot handle
the load. This is the interstage differential.

One or two LEDs (light emitting diodes) are included on

your subbase. Refer to the list below for specific meaning.

The CHECK LED lights when something needs to be

checked or done to maintain efficient operation of the system.
See your heating system instructions for the specific mean-
ing.

The EM. HT. LED lights when the system switch is placed

in the EM. HT. position. Emergency heat is operating; in
most systems, the compressor has failed and the heat pump
is not operating.

The AUX. HT. LED lights when the auxiliary heat stage

is operating. The weather is cold enough that the first stage
cannot handle the load alone.

LEDs are not field replaceable or addable.

M3375

M3375

Recycling Notice

This control contains mercury in a sealed tube. Do not

place control in the trash at the end of its useful life.

If this control is replacing a control that contains mercury in

a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for in-

structions regarding recycling and the proper disposal of this
control, or of an old control containing mercury in a sealed
tube.

If you have questions, call Honeywell at 1-800-468-1502.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - LOCATION; IMPORTANT: An incorrectly leveled subbase will cause; WIRING THE SUBBASE

60-1147-4 2 Fig. 1—Installation of Q674 Subbase on outlet box. M925 VERTICAL OUTLETBOX ADAPTERRING SUBBASE COVER PLATE MOUNTINGSCREWS (2) MOUNTINGSCREWS (2) 1 SUBBASE MOUNTINGSCREWS (2) HORIZONTALOUTLETBOX 1 2 2 1 NOT INCLUDED WITH UNIT. 2 ACCESSORY PARTS AVAILABLE (193121A). Fig. 2—Installation of ...

Page 6 - Settings; HEAT ANTICIPATOR SETTING; Fig. 10—Stage two adjustable heat anticipator.; TEMPERATURE SETTING; SUBBASE SETTING

60-1147-4 6 Fig. 9—Mounting thermostat on subbase. THERMOSTATMOUNTING POST (2) M936 50 60 70 80 50 60 70 80 HEAT COOL THERMOSTATMOUNTING SLOTS (2) SUBBASE THERMOSTAT CAPTIVE MOUNTING SCREWS (2) Settings HEAT ANTICIPATOR SETTING Set the adjustable heat anticipator to match the current draw of the sec...

Page 7 - Checkout; HEATING; Calibration; THERMOSTAT; They do not have provision for field calibration.; THERMOMETER

60-1147-4 7 Checkout HEATING Move the system switch on the Q674 to HEAT or AUTO (if used) and the fan switch to AUTO. Move the heating setpoint lever on the T874 about 10 ° F [6 ° C] above room temperature. Heating equipment should start and the fanshould run. Move the heat lever about 10 ° F [6 ° C...

Other Honeywell Models