INSTALLATION INSTRUCTIONS

62-3050—3

T7047C,G

Electronic Thermostats

and Remote Space Sensors

APPLICATION

The T7047C,G Electronic Thermostats and Remote
Space Sensors are used in Series 70 Control Systems
to provide modulating space temperature control.

SPECIFICATIONS

Models:

T7047C: 2-wire remote sensor for use with control

systems such as the T7100, T7300, W927, W960,
and W973.

T7047G: 2-wire remote sensor without internal

adjustment means, requires remote setpoint device
such as T7100, T7300, S963B, 7067B or T7080B.

Dimensions:

See Fig. 1.

Temperature Sensor:

Thermistor-resistor element.

Sensor Resistance:

For the following negative temperature coefficient (NTC)

devices, resistance decreases as temperature
increases (Fig. 8 and 9):
T7047C: 1420 ohms nominal at 75°F (24°C);

resistance changes 15 ohms for each 1°F (0.6°C)
temperature change.

T7047G: 710 ohms nominal at 75°F (24°C);

resistance changes 7.5 ohms for each 1°F (0.6°C)
temperature change.

Mounting:

Mounts on wall or 2 x 4 in. vertical outlet box

with screws provided.

Accessories:

209649A Universal Cover Plate (taupe);

5-3/4 x 7-3/8 in. (146 x 187 mm).

209650A Universal Cover Plate (premier white);

5-3/4 x 7-3/8 in. (146 x 187 mm).

Fig. 1. T7047 dimensions in in. (mm).

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.

2.

Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.

3.

Installer must be a trained, experienced service
technician.

4.

After installation is complete, check out product
operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment
Damage Hazard.
Can shock individuals or short equipment
circuitry.

Disconnect power supply before installation.

3-1/4

(83)

3-13/16

(97)

4-5/8

(117)

1-13/16 (46)

3-5/8 (92)

7/8 (22)

1-1/16 (27)

2-7/8 (73)

3/8

(10)

M17720