Application Note:

Fire-Lite IPDACT Setup for Installing Dealers


These pictorial instructions should be used in conjunction with the formal
PID (Product Installation Document) included with the IPBRKT or IPENC as
well as the instructions included with the IPDACT. Please Read all
documentation prior to performing any installation or programming.

Installation Instructions for use with HyperTerminal™ and serial port

Parts List

Part Numbers

Description

IPDACT

Internet Communicator-Contact ID only.
Requires compatible FL panel equipped
with on-board or optional DACT. Requires
300mA aux non-reset able power from
FACP. Includes cable from panel primary
telco port to IPDACT.

IPBRKT

Bracket for mounting IPDACT inside MS-
9200UDLS common enclosure or in
optional HPP-300ULX power supply

IPSPLT

Splitter for dual phone lines to IPDACT
input cable.

ALMSC119

RJ45-DB9F PC serial port programming
cable for IPDACT.

IPENC

Optional cabinet for mounting IPDACT next
to compatible Fire-Lite FACP. Use when
connecting to older non common enclosure
panels such as MS-9200UD or MS-9600.
Includes IPBRKT mounting bracket already
installed.

HP300ULX

Optional UL listed Fire Aux power supply for
mounting IPDACT next to compatible Fire
Panel when additional power is required for
IPDACT.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell Smoke Alarm

Summary

Page 2 - into the right slots of the common enclosure cabinet.

5/19/2008 2 of 15 Note: All of the above available at Fire-Lite Distribution The IDPACT requires 24VDC filtered regulated power and a phone pair from the DACT of the fire alarm control panel. While not required, it is highly recommended that any customer shared equipment used to connect the IPDACT t...

Page 4 - Plug one end of the IPDACT Programming Cable (PN ALSMSC120

5/19/2008 4 of 15 4. Loop the 8 PIN cable supplied with the IPDACT once through the large Ferrite Ring. Note that this cable is NOT used as an Ethernet Cable but to interconnect the dialer output of the panel to the input of the IPDACT. Plug the 8 PIN cable supplied with the IPDACT into the Primary ...

Page 7 - Programming Instructions Using HyperTerminal; P2 on the IPDACT using the supplied jumper.

5/19/2008 7 of 15 Installation using 411UD for monitoring Alarm, Trouble and Supervisory dry contacts from any FACP The 411UD can also be mounted next to the IPDACT inside the HP300ULX and used to monitor the Alarm, Trouble, and Supervisory dry contacts from any manufacturer’s fire alarm control pan...