Page 2 - Fire Alarm & Emergency Communication System Limitations
2 6700 Manual – LS10148-001SK-E:C 09/28/2017 Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! An automatic fire alarm system —typically made up of smoke detectors, heat detectors,...
Page 3 - Installation Precautions
6700 Manual – LS10148-001SK-E:C 09/28/2017 3 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before ser...
Page 4 - Documentation Feedback; Please give the following information:
4 6700 Manual – LS10148-001SK-E:C 09/28/2017 Documentation Feedback Your feedback helps us keep our documentation up-to-date and accurate. If you have a question or encounter a problem not covered in this manual, contact Honeywell Technical Support at 800-446-6444. Please give the following informat...
Page 5 - Contents
5 Contents Contents Section 1: Introduction ................................................................................................................................................... 10 1.1: Overview of Basic System...............................................................................
Page 10 - Section 1: Introduction; Overview of Basic System
10 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 1: Introduction The 6700 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 864. 1.1 Overview of Basic System 1.1.1 Hardware Features • The 6700 has one built in signaling line circuit (...
Page 11 - The following terminology is used with the 6700 system:; Compatible Products; The chart below lists the products available for use with the 6700.; Table 1.1 Manual Terminology
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 11 1.2.1 Terms Used in this Manual The following terminology is used with the 6700 system: 1.3 Compatible Products The chart below lists the products available for use with the 6700. Term Description SLC Signaling Line Circuit Module The term module is...
Page 14 - See manual for phone jack information.; Electrical Safety Advisory:; WARNING: FCC RULES PART 15
14 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 2: Agency Listings, Approvals, and Requirements Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of -line relays and resistors shall be placed within the electrical box located and the ...
Page 15 - Requirements for All Installations; Appendix; Requirements for Central Station Fire Alarm Systems; Use both phone lines. Enable phone line monitors for both lines.; Requirements for Local Protected Fire Alarm Systems; Do not exceed the current load restrictions shown in Section 3.7.; CAUTION: INSTALLATION AND TEST
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 15 2.2 Underwriters Laboratories (UL) 2.2.1 Requirements for All Installations General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The follow...
Page 18 - Section 3: Before You Begin Installing; Environmental Specifications; Table 3.4 : Terminal Descriptions and Electrical Specifications
18 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 3: Before You Begin Installing This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 6700 panel for the first time. 3.1...
Page 19 - Wiring Specifications
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 19 * Regulated NAC application. When programmed for releasing, NAC are Special Application. 3.5 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarm...
Page 21 - Current Draw Worksheet Requirements
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 21 3.6 Board Assembly Diagram Figure 3.2 shows the circuit boards, and annunciator. If you should need to remove the control board for repair, remove the three mount-ing screws which hold the control board in the cabinet. Then lift the control board ou...
Page 22 - SLC Devices; and; Table 3.5 Current Calculation Worksheet for SK Devices
22 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 3.7.2 Current Draw Worksheet for SK SLC Devices Use Table 3.5 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up to 50 SK detectors and 50 SK modules 1 . Device # of Devices...
Page 25 - Current Draw Worksheet for SD SLC Devices; Table 3.6 Current Calculation Worksheet for SD Devices
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 25 3.7.3 Current Draw Worksheet for SD SLC Devices Use Table 3.6 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can install up to 75 SD devices per panel. 1 Device # of Devices Current pe...
Page 27 - Maximum Battery Standby Load; Table 3.7 Maximum Battery Standby Load
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 27 Maximum Battery Standby Load The table below shows the maximum battery standby load for the 6700 based on 24 and 60 hours of standby. The standby load calcula-tions of line D in the Current Draw Calculation Worksheet (Table 3.7) must be less than th...
Page 28 - Section 4: Control Panel Installation; Mounting the Control Panel Cabinet; Removing the 6700 Assembly from the Housing; Installing the Dead Front; Set the dead front into the cabinet as shown in Figure 4.4.
28 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 4: Control Panel Installation 4.1 Mounting the Control Panel Cabinet Read the environmental specifications in Section 3.2 before mounting the 6700 panel. The 6700 cabinet base dimensions are: 12.531” W x 14.875” H. The 6700 panel should be l...
Page 29 - Reinsert the two annunciator screws.; Figure 4.4 Dead Front Installation and Removal; Dead Front Removal; Remove the dead front panel from the control panel cabinet.; WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 29 3. Reinsert the two annunciator screws. Figure 4.4 Dead Front Installation and Removal 4. Insert the two screws with the star washers into the bottom of the cabinet to secure the dead front into place. See Figure 4.4. Dead Front Removal Follow these...
Page 30 - Maximum battery charging current 3.1 Amps.
30 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 The AC is rated at 120 VAC, 60 Hz, 1.5A. Figure 4.5 120VAC Power Connection 4.3 Battery Power The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is...
Page 31 - Installing the RBB Accessory Cabinet and Batteries; then attach the RBB cabinet to the plywood.; Figure 4.7 RBB Cabinet Mounting Holes
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 31 4.3.1 Battery Accessory Cabinet The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH s...
Page 32 - Figure 4.9 Battery Connections in the RBB Cabinet; Calculating Wiring distance for SBUS modules; conduit; Cover Plate
32 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4.9. Figure 4.9 Battery Connections in the RBB Cabinet 4. Connect battery leads to the backup battery terminals. See Figure 4.9. Observe the proper p...
Page 33 - Wiring Distance calculation example:; Suppose a system is configured with the following SBUS modules:; Table 4.8 SBUS Device Current Draw; Table 4.9 Wire Distances Per Wire Gauge Using Copper Wire; Table 4.10 : Typical Wire Resistance Per 1000 ft. Using Copper Wire
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 33 To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated b...
Page 34 - Figure 4.11 SBUS Class B Wiring
34 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 2 - Module 5860 LCD Annunciator 1 - 5496 NAC Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface The total worst case current is calculated as follows: Using this value, and referring to the Wiring Distance table, it can be fou...
Page 35 - How to Power SBUS Devices From Auxiliary Power Supply; 855 Remote Annunciator Installation; Figure 4.13 Model 6855 Remote Annunciator, Front View; 855 installation involves the following steps:; SBUS Device
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 35 How to Power SBUS Devices From Auxiliary Power Supply Figure 4.12 illustrates how to power SBUS devices from an Auxiliary Power Supply such as the 5495 or 5499, when the maximum num-ber of SBUS devices exceeds the SBUS power requirements. Figure 4.1...
Page 36 - Flush Mounting; This section of the manual describes flush mounting.; Follow these steps to flush mount the 6855
36 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Flush Mounting This section of the manual describes flush mounting. Follow these steps to flush mount the 6855 1. The back box dimensions are 9-9/32” w x 8-3/8” h. The minimum depth 2". The back box can be mounted prior to the complete install...
Page 37 - Figure 4.16 Attaching Annunciator/Door Assembly to Backbox; Surface Mounting; Figure 4.17 Back Box Surface Mount Holes; Run wires to the control panel.; Back Box
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 37 4. Attach the annunciator and door assembly to back box as shown in Figure 4.16 using the supplied screws. Figure 4.16 Attaching Annunciator/Door Assembly to Backbox Surface Mounting The optional Model RA-100TG/TR trim ring kit is available for use ...
Page 38 - Place the trim ring over the back box as shown in Figure 4.18.; Figure 4.18 Installing Trim Ring; Attach the Door assembly to the back box using screws provided.; Figure 4.19 Model 6860 Connection to the Panel; 860 Remote Annunciator Installation
38 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 4. Place the trim ring over the back box as shown in Figure 4.18. Figure 4.18 Installing Trim Ring 5. Attach the Door assembly to the back box using screws provided. 6. After the annunciator wiring to the panel has been completed (described in Secti...
Page 39 - Figure 4.20 Model 5860 Remote Annunciator, Front View; 860 installation involves the following steps:; Figure 4.21 Annunciator Parts
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 39 Figure 4.20 Model 5860 Remote Annunciator, Front View 5860 installation involves the following steps: 1. Make sure power is off at the panel. 2. Mount the 5860 in the desired location (see Section 4.6.1). 3. Connect the 5860 to the panel (see Sectio...
Page 40 - Figure 4.22 Annunciator Back Box and Bezel Details; Flush Mounting with an Electrical Box; Figure 4.23 Placement of Electrical Box for Flush Mounting; Flush Mounting Steps; Remove knockout holes as needed for wires.
40 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4.22 for location of t...
Page 41 - Figure 4.24 Flush Mounting the Back Box; Drill holes in the surface to match the screw holes on the back box.; Figure 4.25 Model 5860 Connection to the Panel
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 41 4. After the annunciator wiring to the panel has been completed (described in Section 4), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. Figure 4.24 Flush Mounting the Back...
Page 42 - 860 Remote Annunciator Installation; Figure 4.26 6860 Remote Annunciator, Front View; 860 installation involves the following steps:; Figure 4.27 Back Box Mounting Holes
42 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 4.7 6860 Remote Annunciator Installation The optional Model 6860 Remote Annunciator, shown in Figure 4.26. The 6860 can be surface or flush mounted. Figure 4.26 6860 Remote Annunciator, Front View 6860 installation involves the following steps: 1. M...
Page 43 - Wire Knockouts
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 43 2. Remove knockout holes as needed for wires. See Figure 4.15 for backbox knockout locations. Figure 4.28 Back Box Knockout Locations 3. Wire the annunciator board to the main control panel. As described in Section 4.7.2. 4. Attach the annunciator a...
Page 44 - Figure 4.30 Back Box Surface Mount Holes; Figure 4.31 Installing Trim Ring; Attach the door assembly to the back box using screws provided.
44 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Place a level on top of the back box, with the back box level insert the rest of the mounting screws . Figure 4.30 Back Box Surface Mount Holes 3. Run wires to the control panel. 4. Place the trim ring over the back box as shown in Figure 4.18. Figu...
Page 45 - Figure 4.32 Model 6860 Connection to the Panel; 824 Serial/Parallel Printer Interface Module Installation; supervised
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 45 4.7.2 6860 Connection to the Panel Connect the 6860 to the panel as shown in Figure 4.32. Figure 4.32 Model 6860 Connection to the Panel 4.8 5824 Serial/Parallel Printer Interface Module Installation The 5824 serial/parallel printer interface module...
Page 46 - Select options for the printer and the output port. See below.; Printer and Output Port Options; From the Main Menu, select 7 for Program Menu.; Figure 4.34 Selecting Printer and Output Port Options
46 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 • Add the module to the system. JumpStart will add the module automatically (see Section 8.1). You can also add it manually (see Section 9.2.2). • Select a name, if desired. • Select options for the printer and the output port. See below. Printer ...
Page 51 - Figure 4.42 Inserting Zone Description Labels; Configuring Modules; Figure 4.43 Possible module addresses; Telephone Connection
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 51 Slide the labels under the plexiglass as shown in Figure 4.42. The LEDs will show through the label when illuminated. Figure 4.42 Inserting Zone Description Labels 4.11 Configuring Modules This section describes how to configure any system hardware ...
Page 52 - Figure 4.44 Connection of Telephone Lines; Notification Appliance/Auxiliary Power Circuits; Conventional Notification Appliance; Class B Notification Wiring; To install a Class B notification appliance circuit:; Figure 4.45 Class B Notification Appliance Circuit Wiring
52 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 A number of programmable options are available for customizing telephone lines. These options are described in Section 9.6. Figure 4.44 Connection of Telephone Lines 4.13 Notification Appliance/Auxiliary Power Circuits Two outputs are built-in to th...
Page 53 - Class A Notification Wiring
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 53 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as shown in Fig...
Page 54 - Door Holder Power; Figure 4.47 Example of an Auxiliary Power For Door Holder; Constant Power; Figure 4.48 Location of Conventional Relay Circuits
54 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Door Holder Power Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 27.4 volt power present at their terminals. Any alarm will cause power to discon...
Page 55 - To install one or two programmable relays, follow these steps.; Remote Station Applications; Program control panel Relay 2 for alarm.; Figure 4.49 Keltron 3158 Connection to Control Panel; Alarm Current:1Amp for 1 second; Example
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 55 4.14.2 Programmable Relays The control panel has two Form C programmable relays built into terminals labeled RELAY 1 or RELAY 2. Each relay provides a nor-mally open and a normally closed contact. To install one or two programmable relays, follow th...
Page 56 - Figure 4.50 City Box Connection; Standby Current:100mA
56 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Max Voltage: 27.4VDC The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box connection: 1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of ...
Page 57 - Figure 4.51 Polarity Reversal Connection Using the 5220 Module; To install the 7644-L8 for polarity reversal:; Figure 4.52 Polarity Reversal Connection Using the 7644-L8
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 57 5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board. Normal loop current is 2-to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm. Figure 4.51 Polarity Reversal Connection Using the...
Page 58 - Figure 4.53 Polarity Reversal Connection Using the MR-201/T Relay
58 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 4.15.4 Using a MR-201/T Control Relay From Air Products When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to rese...
Page 59 - Transmitter Activated by Dry Contacts
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 59 4.15.5 Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the 6700 FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-o...
Page 60 - Section 5: Common Communication Link; Hardware Features; SK-NIC Wiring Option
60 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 5: Common Communication Link 5.1 Hardware Features The 6700 panel can be connected to other 6700 and addressable panels to create a link where one panel is designated as the communica-tor for all the panels in the link. Up to 17 panels can b...
Page 61 - The following describe the two types of fiber optic modules.
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 61 5.3 SK-NIC Wiring Options Linking a group of 6700s requires the use of a network interface card with each panel. The SK-NIC connects to other linked units using unshielded, twisted-pair wiring or fiber-optic cable. Figure 5.55 SK-NIC Network Interfa...
Page 62 - Figure 5.57 SK-NIC with Fiber Loop Modules; Place the SK-NIC on the mounting bracket.
62 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Figure 5.57 SK-NIC with Fiber Loop Modules SK-NIC-KIT Mounting Kit SK-NIC can be mounted in an accessory cabinet. Accessory kits P/N SK-NIC-KIT are available that include a SK-NIC, small cabinet with door, cable & mounting hardware. The accessor...
Page 63 - Unshielded Twisted Pair Wiring between Multiple Panels; Figure 5.59 Twisted Pair Wiring Configuration
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 63 4. Unused optic ports on fiber loop modules must have their dust caps placed on the port. 5. Based on the type of data medium chosen, run the twisted pair wiring/fiber optic cable to the next SK-NIC using a class B or class A wiring method. A combin...
Page 64 - Fiber Optic Multi-Mode Wiring between Multiple Panels; Figure 5.60 Fiber Optic Wiring Example; Class A
64 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Fiber Optic Multi-Mode Wiring between Multiple Panels Fiber optic cable between multiple panels is shown in Figure 5.60. Class A is shown with a dotted line. Figure 5.60 Fiber Optic Wiring Example Class A wiring
Page 66 - Fiber Optic and Twisted Pair Wiring between Multiple Panels
66 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Fiber Optic and Twisted Pair Wiring between Multiple Panels A mixture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5.62. Class A cabling is shown with dotted line. Figure 5.62 Twisted Pair and Fiber Optic C...
Page 67 - Setting the Panel ID for each Panel; Figure 5.63 ID Settings
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 67 5.4 Setting the Panel ID for each Panel The panel ID for each panel is set using DIP switch positions 1 through 5. See Figure 5.63 below for possible DIP switch settings. Figure 5.63 ID Settings NOTE: It is important that much thought is given when ...
Page 68 - Section 6: Network Management; Network Diagnostics
68 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 6: Network Management 6.1 Network Diagnostics 6.1.1 Ping Panel The Ping Panel menu allows you to continually ping any panel programmed into the network. As the selected panel is being pinged, the Ping Panel screen will display the reply time...
Page 69 - To Edit the Network Panel ID:; User Profile Selectable Panel Functions
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 69 To Edit the Network Panel ID: 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 6 for Network Programming. 3. Press 3 to enter the Edit Panel ID menu. 4. If the Network Panel ID is changed and valid, the syst...
Page 70 - Profile Edit Menu; Edit Name
70 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 *Function Keys are only available on the 6860 LCD annunciator To change an access code: 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 6 for Network Programming Menu. 3. Select 5 for Access Codes. Display re...
Page 72 - Press * to add rows, Press ENTER to edit data; Figure 6.64 Communicator Reporting; Sync Network Options; Select 6 for Network Programming Menu.; Figure 6.65 SYNC Network Options
72 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 5. Press * to add rows, Press ENTER to edit data Figure 6.64 Communicator Reporting 6.3 Sync Network Options If after making changes to network programming, the distribution of network options fail, the system will report a trouble of network option...
Page 73 - Network Management Quick Reference; Menu
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 73 6.4 Network Management Quick Reference Menu Options/Defaults Comments Network Programing Learn Network Guest or member Add or remove panels into the network See Section 6.2.1 Edit Network Names Panel Names Network Panel ID Edit Panel Names See Secti...
Page 76 - SLC Device Installation; List of SK SLC Devices; Table 7.12 SK SLC Devices
76 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 7: SK, SD and SWIFT ™ SLC Device Installation 7.1 List of SK SLC Devices The following SK SLC devices can be used with the control panel. See the device installation instructions for more information (pack-aged with the device). ! CAUTION: T...
Page 77 - devices, system setup and operation see the SWIFT; Maximum Number of Devices; SK Devices–An 6700 system can support a total of 50 SK detectors; Wiring Requirements for SLC Devices
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 77 7.2 List of SD SLC Devices The following SD SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information. 7.3 SWIFT ® Wirele...
Page 78 - Wiring Requirements for SK Modules; Figure 7.66 Calculating wire run length for a simple out and back; mm
78 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 7.5.1 Wire Sizing for Internal SLC The SLC requires use of a specific wire type, depending on mode of operation, to ensure proper circuit functioning. Wire size should be no smaller than 18 AWG and no larger that 12 AWG wire. The wire size depends o...
Page 79 - Figure 7.67 Calculating Wire Run Length for a T-tap; Wiring SLC in Class A Configuration; Figure 7.68 Class A SLC Configuration
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 79 When using T-taps, the total length of all taps and the main bus must be met in addition to the maximum distance requirements for the various wire gauges. Figure 7.67 Calculating Wire Run Length for a T-tap 7.5.3 Wiring SLC in Class A Configuration ...
Page 80 - Addressing SK SLC Devices; ONES; Figure 7.69 SK SLC Device Addressing Using Rotary Dials; SD Detector Installation; Figure 7.70 Heat or Smoke Detector Connection to the FACP (Class B); Addressing SD SLC Devices; All dials labeled for ONES
80 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 7.6 Addressing SK SLC Devices All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in...
Page 82 - Figure 7.72 SLC Device Addressing Using DIP Switches; SWIFT
82 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Figure 7.72 SLC Device Addressing Using DIP Switches 7.9 Wiring the SK-WGI. For more information regarding Gateway wiring instructions, see SWIFT manual LS10036-000SK-E. 7.9.1 SLC Connections The SK-WGI Wireless Gateway acts as a bridge between a gr...
Page 84 - Section 8: Programming Overview; Autoprogramming
84 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 8: Programming Overview This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual care-fully, especially if you are programming the control panel for the first time. The...
Page 85 - Mapping Overview; Figure 8.73 Mapping Overview
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 85 4. When the message, “SLC FAMILY” message appears, select SK Series, or SD; depending on the type of SLC devices the panel is using, and press ENTER to accept. 5. A series of messages displays for the next several seconds. JumpStart ® scans the SLC ...
Page 86 - Figure 8.74 Input Point Assignment Example
86 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 8.2.1 Input Point Mapping Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned...
Page 87 - Table 8.15 Event Types
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 87 8.2.2 Output Circuit Mapping Figure 8.75 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 8.77. Figure 8.75 Assigning Output Circui...
Page 90 - Figure 8.78 Example of LED Points Mapped to Output Groups; Programming Using the HFSS Software Suite
90 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 8.2.4 Mapping LED Points Figure 8.78 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two out-put groups for each zone, one for alarms and one for troubles. (LED points are available when M...
Page 91 - To enter the Program Mode:; Enter the installer code if requested.; To Exit Program Mode:; Figure 8.79 Moving through Program Menu; Selecting Options and Entering Data
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 91 The following subsections describe programming basics, including a description of editing keys available for programming and how to move through programming menus. Section 9 contains specific information about individual programming options. 8.4.1 E...
Page 92 - Programming Menu Quick Reference
92 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 8.5 Programming Menu Quick Reference This section of the manual lists all Program Menu options in the order they appear on the sub-menus. Default settings are indicated in text or marked with an asterisk. The comments column provide quick informatio...
Page 100 - Section 9: Programming; UL 864 Programming Requirements; Editing Module ID
100 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 9: Programming This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed usin...
Page 101 - Figure 9.80 Edit module Name Programming Screen Example; Changing Module Options
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 101 Figure 9.80 Edit module Name Programming Screen Example Changing Module Options Each module has a unique set of options that specifically applies to the functionality of the module being edited. 8. Use the left and right arrow keys to move between ...
Page 102 - Figure 9.81 Edit Zone Properties; Alarm Delay Characteristics; Table 9.16 Alarm Delay Types
102 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 To edit a zone, follow these steps: 1. Enter the installer code. 2. Select 7 for Program Menu. 3. Press 2 to enter zone menu. 4. Press 1 to edit a zone. 5. Enter the zone number, then press ENTER. Edit Zone Name 6. To edit the zone name, press 1. Y...
Page 103 - Heat Detector Sensitivity; Zone Accessory Options; Figure 9.82 View Zone Points Screen
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 103 Heat Detector Sensitivity Use this feature to set the temperature at which high temperature detectors will respond. All detectors in the zone will respond in the same way. The range for the SD505-HEAT heat detector is from 135°F to 150°F. The ran...
Page 104 - Figure 9.83 Group Properties Screen Programming Options
104 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 9.4.1 Edit Group In the edit group option you can program the name of an output group (Section , "Edit Group Name") and change the properties of that group. To edit a group, follow these steps: 1. Enter the installer code. 2. Select 7 for P...
Page 105 - Table 9.17 : Point Programming for Internal SLC Module
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 105 You can use words to display a descriptive name for a group. 7. Right arrow to the OPG and select Yes or No to select which output group to include in the template. 9.5 Point You may need to change characteristics of individual input points (detect...
Page 107 - Point Programming For Internal or External Power Module; Enter the installer code.
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 107 9.5.2 Point Programming For Internal or External Power Module To program for an internal or external power module points, follow these steps: 1. Enter the installer code. 2. Select 7 for Program Menu. 3. Press 4 to enter point menu. 4. Press the up...
Page 108 - Table 9.18 Menu choices for Internal/External Power Modules
108 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 11. Repeat Steps 1 through 10 for all circuits. 9.5.3 Point Programming For 5880 and 5865 Modules To program for a 5880 or 5865 module points, follow these steps: 1. Enter the installer code. 2. Select 7 for Program Menu. 3. Press 4 to enter point ...
Page 110 - Figure 9.86 Phone Lines Editing Screen; Dialing Prefix; Enter the desired number of answer rings, then press ENTER.; Dial Format
110 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 6. Select the phone line to be edited (1 or 2) by pressing the up or down arrow, then press ENTER. Figure 9.86 Phone Lines Editing Screen Dialing Prefix Enter up to 9 characters to be used for such things as PBX dial-out codes, a pause, and so on...
Page 111 - Edit Ethernet; Figure 9.87 Edit Ethernet Message; AlarmNet Timers
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 111 Monitor Line Enable the line monitor for each phone line that will be used. See Figure 9.86 for location of this field on the phone lines screen. When the phone line monitor has been enabled for a phone line, a trouble condition will occur if the...
Page 112 - Figure 9.88 AlarmNet Timers; Phone Line Gains; Figure 9.89 Phone Line Gains; Water Flow Delay; Figure 9.90 Water Flow Delay Programming Screen
112 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 • Old Alarm *30 minutes, 15 minutes, 10 minutes, none, 24 hours,12 hours, 6 hours, 4 hours,2 hours, 1 hour *defaults Figure 9.88 AlarmNet Timers Phone Line Gains 1. Enter the installer code. The panel will automatically go to the main menu. 2. Sele...
Page 113 - Figure 9.91 Low AC Report Delay Programming Screen; AC Line Frequency; Low AC Report delay
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 113 Alarm Verify You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds). To set the alarm verification: 6. Enter the desired number of seconds for the alarm verification time. 7. Press the right arrow or ENTER to make yo...
Page 114 - Yes
114 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 9.6.4 Daylight Saving Options To edit Daylight Savings: 1. Enter the installer code. 2. Select 7 for Program Menu. 3. Select 5 for System Options. 4. Select 6 for Daylight Savings. Automatic Daylight Saving Adjustment The control panel has an autom...
Page 115 - Figure 9.92 SLC family change
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 115 : Figure 9.92 SLC family change 9.7 JumpStart ® Autoprogramming Panels support an incremental JumpStart. For Example: After initial JumpStart ® & customization, if you add more devices, when you JumpStart again the additional devices are added ...
Page 116 - Section 10: System Operation; Annunciator Description; Figure 10.93 Control Panel Annunciator
116 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 10: System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this entire section carefully before operating the...
Page 117 - Basic Operation; Disable / Enable NACs by Template; To move through the menus:
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 117 10.2.3 Single Key Acknowledge This feature allows the user to press the ACK and display the oldest un-acknowledged event in the system. Pressing ACK again will acknowledge the event, then display the next oldest un-acknowledged event without pressi...
Page 119 - Reset Communicator; 1 Check Detector Sensitivity Through Point Status
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 119 If you do not end the walk test manually within four hours, it will end automatically. If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the walk test. 10.4.7 Conduct a Communicator Test 1. From the Main M...
Page 120 - A screen similar to those shown in Figure 10.95 will display.; Figure 10.95 Checking Detector Sensitivity Compliance; From the Main Menu, select 2 for Point Status.; About Panel
120 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 5. A screen similar to those shown in Figure 10.95 will display. Figure 10.95 Checking Detector Sensitivity Compliance You can print detector status by uploading the detector status to and printing from HFSS Honeywell Fire Software Suite. 10.4.12 V...
Page 121 - Press 6 from the System Information menu for AlarmNet Info; AlarmNet Temp Pin; Operation Mode Behavior; Figure 10.96 Highest Priority Event Display
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 121 Ethernet Info 1. Press 5 from the System Information menu for Ethernet Information. AlarmNet Info 1. Press 6 from the System Information menu for AlarmNet Info 2. Cell Strength: 0 to 100% 3. Status: Registered/Not Registered AlarmNet Temp Pin...
Page 122 - Operation Mode Behavior; Operation; Normal
122 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 10.6 Operation Mode Behavior The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 10.19 describes the behavior of the panel in each of these modes. Operat...
Page 124 - Releasing Operations; Prealarm
124 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 10.6.1 Multi-Site Annunciator and Multi-Site User Access Multi-site Annunciators are unique as they can display the status and event history of all sites they are assigned to. These displays can be especially useful in guard shacks or security cent...
Page 125 - Figure 10.98 Wiring Configuration for Solenoid; Conditions Required for an Pre-Alert Output Activation; Table 10.20 Approved Releasing Solenoids
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 125 When a Single or Double Interlock Zone releasing is selected the system will automatically default the 5496 Intelligent Power Module in the following system parameters: • Output Group 2 is created. Output Group 2 will be defaulted as an “Alarm” out...
Page 126 - Table 10.21 : Input Conditions and Output Results
126 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Conditions required for an General Alarm and Release Output Activation If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the “Release” outputs will activate. (Also refer to Table 10.21.) 10.7.2 Double Inte...
Page 127 - Conditions Required for a Release Output Activation; Smoke Alarm Verification; Figure 10.99 Smoke Verification Cycle; From the idle screen, press and hold the F-Key for 5 seconds.; Table 10.22 Double Lock Zone Operation
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 127 Conditions Required for a Release Output Activation Any release requires the activation of an interlock switch, and either a manual release switch or 2 activated addressable detectors. When these conditions are met, the “Release” and “General Ala...
Page 130 - Section 11: Reporting; Receivers Compatible with the Control Panel; Table 11.23 shows receivers compatible with the control panel.; Table 11.23 Receivers Compatible with the Control Panel
130 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 11: Reporting This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Con-tact ID formats. 11.1 Receivers Compatible with the Control Panel Table 11.23 shows re...
Page 131 - Table 11.2 Reporting Formats Table
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 131 F3 Mapping Inhibited Restoral FJ 2003 FJNN002003 3 570 00 003 F4 Mapping Inhibited FT 2004 FTNN002004 1 570 00 004 F4 Mapping Inhibited Restoral FJ 2004 FJNN002004 3 570 00 004 Fire Reset OR 0 ORNN000000 1 401 00 000 Fire System Overridden FS 0 FSN...
Page 142 - Section 12: Testing and Troubleshooting; Troubleshooting
142 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 12: Testing and Troubleshooting 12.1 Troubleshooting This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem when installing the control panel. If these sugges...
Page 143 - Built-in Troubleshooting and Testing Tools; SLC device locator can be used to locate a device on a SLC loop.
6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 143 3. If new batteries were installed, wait 48 hours before completing this step. Remove AC power, activate initiating device and check that:• the ALARM indicator lights.• all active Notification Appliances sound. Measure battery voltage while the Not...
Page 144 - Earth Fault Resistance; Table 12.5 Earth Faults in Ohms
144 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 4. Select the SLC loop. 5. Enter up to 8 SLC addresses for the devices you wish to locate.The LEDs on the selected devices will start flashing. 6. Press the left arrow key to exit SLC multi-locater function. 12.3.3 I/O Point Control This feature al...
Page 146 - Section 13: Installation Records; SD SLC Device Point Record; You can use Table 13.7 to keep track of SK SLC detectors and modules.
146 6700 Manual — P/N LS10148-001SK-E::C 09/28/2017 Section 13: Installation Records This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed. 13.1 SD SLC Device Point Record You can use Table 13.6 to keep track of SD SLC device points. ...
Page 148 - Appendix A: Compatible Devices; A.1 Notification Appliances; feature. This control is UL listed for panel wide Synchronization.; Table A.8 Compatible Notification Appliances
148 6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 Appendix A: Compatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. Table be...
Page 156 - Apollo
156 6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 Manufacturer Model Name or Number (Base model name or number in parentheses.) Compatibility ID # per Loop Head Base Apollo 55000-350 (45681-200) 55000-350 45681-200 24 / loop 55000-250 (45681-200) 55000-250 45681-200 24 / loop 55000-225 55000-225 45...
Page 157 - Photo w/ Therm Sounder; Table A.10 Compatible Four-Wire Smoke Detectors
6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 157 A.3 Four Wire Smoke Detectors/Devices (UL Listed Smoke Detector/Base Detector Type Max StandbyCurrent (mA) Alarm Current (mA) Fenwal CPD-7021 (w/70-201000-005 Base) Ionization 0.10 * Fenwal PSD-7125 Photoelectric 0.10 * Fenwal PSD-7126 (w/70-201000-...
Page 158 - Table A.12 lists relays compatible with the fire control panel.; Table A.12 Compatible Relays
158 6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 A.4 Door Holders (UL Listed) Table A.11 lists door holders that are compatible with the fire control panel A.5 Relays (UL Listed) Table A.12 lists relays compatible with the fire control panel. System Sensor RRS-MOD I 3 Reversing Relay/Sync Module ....
Page 159 - SPW; Table A.14 Low Frequency Bases
6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 159 A.6 Compatible 520Hz Signaling Speakers A.7 Compatible 520Hz Low Frequency Bases Model Number Description SPR Wall High-Fidelity Speaker, Red SPW Wall High-Fidelity Speaker, White SPCR Ceiling High-Fidelity Speaker, Red SPCW Ceiling High-Fidelity Sp...
Page 160 - Appendix B: Editing Text Using the Built-In Programmer; B.8 Characters Used for Editing Text; Figure B.102 Edit Name Example
160 6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 Appendix B: Editing Text Using the Built-In Programmer This section contains tables of programmable characters that may be used for device, module, site, template, group, and zone names. T9 style editing is used. B.8 Characters Used for Editing Text...
Page 162 - Appendix C: Expanded Receiver/Panel Relationship
162 6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 Appendix C: Expanded Receiver/Panel Relationship The available receiver number will correspond with what panel number you entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See Sectio...
Page 164 - Appendix D: Cadence Patterns
164 6700 Manual — P/N LS10148-001SK-E:C 09/28/2017 Appendix D: Cadence Patterns The cadence patterns shown below are available for use with the control panel.
Page 166 - Panel Security; Security and Data Protection
166 6700 Manual – LS10148-001SK-E:C 09/28/2017 Panel Security Panel installation / maintenance security checklist System Description: ________________________________________________________________ System Location: __________________________________________________________________ Installer: ______...
Page 168 - Limited Warranty
168 6700 Manual – LS10148-001SK-E:C 09/28/2017 Limited Warranty Honeywell International Inc. warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) monthsfrom the date of manufacture, under normal use and service. Products aredate stamped at time ...
Page 169 - Model 6700 Basic Operating Instructions
Cut Along the Dotted Line Model 6700 Basic Operating Instructions These Instructions must be framed and displayed next to the 6700 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Operation Task to Perform Silence Alarms and...
Page 172 - Honeywell Silent Knight
Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.silentknight.com LS10148-001SK-E | Rev C | 11/17©2018 Honeywell International Inc.