Honeywell S7999B- Manual
Honeywell S7999B– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – ORDERING INFORMATION; PREFACE
- Page 3 – SPECIFICATIONS
- Page 4 – SAFETY FEATURES; WARNING
- Page 12 – PAGE NAVIGATION; Common OI Display Page Symbols
- Page 13 – Configure Button; Configuration Password
- Page 14 – Keyboard; Login
- Page 15 – Change Parameter Settings; Verify
- Page 16 – History Button
- Page 18 – Operation Button
- Page 19 – Diagnostics Button
- Page 20 – Configuration
- Page 23 – DHW Storage Configuration
- Page 26 – Pump Configuration Parameters
- Page 27 – Statistics Configuration Parameters
- Page 28 – Stack Limit Configuration Parameters
- Page 30 – Safety Configuration Parameters
- Page 32 – Safety Parameter Verification
- Page 35 – Fan Parameters
- Page 38 – DETAILS
- Page 40 – Burner Control Status
- Page 46 – INSTALLER CHECKOUT; Diagnostics Tests
- Page 48 – ADVANCED SETUP
- Page 51 – Trend Analysis Snapshot; Diagnostics
PRODUCT DATA
65-0303-05
S7999B, S7999C SOLA
Local Operator Interface
APPLICATION
The S7999B and S7999C are microprocessor-based touch-
screen Operator Interface (OI) displays that provide an
operator interface for monitoring and configuring parameters
in the Sola Hydronic Control and Sola Steam Control system.
The S7999B can be used to monitor an individual boiler but is
primarily used for multiple boiler applications in a lead/lag
arrangement. COM 2 port is available for Building Automation
applications. The S7999B display is flush mounted into a
panel cutout (8-1/8 in. W x 5-7/8 in. H). Wiring connections to
the S7999B are through a removable 9-pin wiring header.
The S7999C display is used for individual boiler monitoring.
The S7999C is mounted:
• onto a panel using the wallplate provided.
• from the front into a panel cutout (7.6 in. W X 5.4 in. H)
using 4 #6-32 screws and nuts (provided).
• From behind into a panel cutout (5.45 in. W X 4.3 in. H)
using 4 #6-32 screws, nuts and 4 standoffs (provided).
Wiring connections to the S7999C are made via a 4-pin
connector on the back of the display.
NOTE: If display S7999B is used to monitor a lead/lag sys-
tem, display S7999C can NOT be used.
FEATURES
• Individual boiler status, configuration, history, and
diagnostics.
• Allows configuration and monitoring of the Sola
Controls (R7910A Hydronic Controls or R7911 Steam
Control) burner control sequence, flame signal,
diagnostics, historical files, and faults.
• S7999B OI Display only:
— Allows switching view between multiple boilers
— Allows viewing Lead-Lag Master
— Ethernet port for downloading software upgrades
(when required)
— Real-time data trending analysis and transferring
saved trend data to Excel spreadsheet.
— Audible Alarm
— COM 2 Modbus port for Building Automation System
applications.
— LED indicators:
• Power
• Network
• COM 2
• COM 1
— Models available:
• S7999B1026 has Blue Border
• S7999B1067 has Black Border
• S7999C OI Display only:
Contents
Preface .............................................................................
Specifications ...................................................................
Installation Instructions (S7999B OI Display) ...................
Wiring (S7999B OI Display) .............................................
Starting the S7999B OI Display ........................................
Configuration .................................................................... 20
Details .............................................................................. 38
R7910A or R7911 Diagnostics ......................................... 44
S7999B or S7999C Display Setup and Diagnostics ......... 47
Advanced Setup ............................................................... 48
Table 61 Configurable Parameters. .................................. 53
Table 62 Other Tables. ..................................................... 61
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell S7999B
Summary
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need f...
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 3 65-0303—05 The software upgrade is automatic after the above steps. The OI Display connects to the Honeywell server, which verifies the configuration file, erases the old application and downloads the new one. The OI Display may have difficulty finding ...
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 4 required to correct the interference at his own expense. This Class A digital apparatus complies with Canadian ICES-003. Cet Appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. SAFETY FEATURES The OI Displays contain ...