INSTALLATION INSTRUCTIONS

66-1085-04

SIL

3

Capable

RM7800E,G,L,M; RM7840E,G,L,M

7800 SERIES Relay Modules

APPLICATION

The Honeywell RM7800/RM7840 Relay Modules are

microprocessor-based integrated burner controls for

automatically fired gas, oil, or combination fuel single burner

applications. The RM7800/RM7840 Relay Modules are used

for UL/CSA On/Off, UL/CSA Modulating, and FM/IRI

Modulating burner applications. The RM7800/RM7840 system

consists of a Relay Module. Keyboard Display Modules

(standard with RM7800), Dust Cover (standard with RM7840),

Subbase, Amplifier, and Purge Card. Options include DATA

CONTROLBUS MODULE™, Remote Display Mounting, First-

Out Expanded Annunciator and Communications through

Modbus™.

Functions provided by the RM7800/RM7840 include

automatic burner sequencing, flame supervision, system

status indication, system or self-diagnostics and

troubleshooting. The RM7800/RM7840 is a solid state

replacement for the electromechanical R4140 Automatic

Programming Control.

This document provides installation and static checkout

instructions. Other applicable publications are:

65-0084:Q7800A,B 22-Terminal Wiring Subbase Product

Data.

65-0089:ST7800A Plug-In Purge Timer Installation

Instructions.

65-0090:S7800A Keyboard Display Module Product Data.

65-0091:S7810A Data ControlBus Module™ Product Data.

65-0095:S7820 Remote Reset Module Product Data.

65-0097:221729C Dust Cover Packing Sheet.

65-0101:S7830 Expanded Annunciator Product Data.

65-0109:R7824, R7847, R7848, R7849, R7851, R7852,

R7861, R7886 Flame Amplifiers for the 7800 SERIES

Product Data.

65-0131:221818A Extension Cable Assembly Product

Data.

65-0229:7800 SERIES RELAY MODULES Checkout and

Troubleshooting Product Data.

65-0249:S7810M ModBus™ Module Product Data.

SPECIFICATIONS

Electrical Ratings, see Table 3:

Voltage and Frequency: 120 Vac (+10/-15%), 50 or 60 Hz

(±10%).

Power Dissipation: RM7800/RM7840: 10W maximum.

Maximum Total Connected Load: 2000 VA.

Fusing: 15A maximum, Type SC or equivalent Fast Blow.

Environmental Ratings:

Ambient Temperature:

Operating: -40°F to +140°F (-40°C to +60°C).

Storage: -40°F to +150°F (-40°C to +66°C).

Humidity: 85% relative humidity continuous, noncondensing.

Vibration: 0.5G environment.

SIL 3 Capable:

SIL 3 Capable in a properly designed Safety Instrumented

System. See form number 65-0312 for Certificate Agree-

ment.

Approvals:

Underwriters Laboratories Inc. Listed: File No. MP268,

Guide No. MCCZ.

Canadian Standards Association Certified: LR9S329-3.

Factory Mutual Approved: Report No. J.I.1V9A0.AF.

Swiss Re (formerly IRI): Acceptable.

Federal Communications Commission, Part 15,

Class B—Emissions.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous

condition.

2.

Check the ratings given in the instructions and marked

on the product to make sure the product is suitable for

the application.

3.

Installer must be a trained, experienced, flame

safeguard service technician.

4.

After installation is complete, check out the product

operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury,

or death.

To prevent possible hazardous burner operation, verify

safety requirements each time a control is installed on

a burner.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell RM7800G

Summary

Page 2 - Location; Humidity; Mounting Wiring Subbase; WARNING

RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES 66-1085—04 2 WARNING Electrical Shock Hazard. Can cause serious injury or death. Disconnect the power supply before beginning installation. More than one power supply disconnect may be required. IMPORTANT 1. Wiring connections for the relay modu...

Page 3 - Final Wiring Check

RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES 3 66-1085—04 a. Do not run high voltage ignition transformer wires in the same conduit with the flame detector, Data Controlbus Module™, or Remote Reset Module wiring. b. Do not route flame detector, Data Controlbus Module™, or Remote Reset Modu...

Page 10 - SAFETY SHUTDOWN

RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES 66-1085—04 10 Fig. 5. RM7800/RM7840 Relay Module exploded view. SAFETY SHUTDOWN Safety Shutdown (Lockout) occurs if any of the following occur during the indicated period: 1. INITIATE Period: a. Purge card is not installed or is removed. b. Purg...