PRODUCT DATA
68- 0105- 2
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
R8182D,E,F,H,J Combination
Protectorelay™ and Hydronic
Heating Controls
GENERAL
The R8182 is a combination Protectorelay™ intermittent
ignition oil burner primary and immersion type Aquastat®
controller for oil-fired, hydronic heating systems.
FEATURES
• Depending on model, these single unit devices provide
combinations of high limit, low limit, and circulator
control.
• All models use a 24V thermostat and C554A Cadmium
Sulfide Flame Detector.
• R8182D,E,H and J have auxiliary terminals ZC and ZR
for circulator zone control. Additional zones require a
separate 24V thermostat and R845 Relay.
• All models have capability for zone control with zone
valves. Each additional zone requires a separate 24V
thermostat and a V8043 or V8044 Zone Valve.
• Ideal for packaged boiler systems requiring compact,
multipurpose controls.
• R8182D,E,F mode
• R8182H,J models mount on a 4 x 4 inch junction box,
and have a 5 ft (1.5m) armored capillary for remote
sensor location.
• Aquastat® Controller section is field replaceable.
• Oil burner circuit includes an improved safety shutoff
in the event the burner fails to start.
• Flame failure during the running cycle results in a
45 second attempt to restart. If unsuccessful, safety
shutoff occurs, requiring manual reset before burner
can be restarted.
Contents
General .............................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Operation .......................................................................... 12
Startup and Checkout ....................................................... 14
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell R8182H
Summary
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS 5 68-0105—2 Fig. 7. Internal view of R8182H. Fig. 8. Internal view of R8182J. INSTALLATION WARNING Explosion Hazard. Can cause severe injury, death or property damage. This product is intended for use only in systems with a pres...
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS 68-0105—2 6 NOTE: Do not make sharp bends in the tubing. A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case. d. Fit the contro...
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS 7 68-0105—2 Fig. 9. Positioning the sensing bulb in the immersion well. WIRING IMPORTANT Use Underwriters Laboratories Inc. listed connectors when making external circuit connections to the orange and white line voltage burner a...