Honeywell R4795A- Manual
Honeywell R4795A– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – SPECIFICATIONS • ORDERING INFORMATION; Specifications
- Page 4 – INSTALLATION; Installation; Vibration; CAUTION; Humidity; WIRING TO SUBBASE
- Page 5 – Wiring Hookups; The typical wiring hookups in Fig. 2 and 3 show the; the entire connected electrical load.
- Page 6 – Flame Detector Wiring
- Page 7 – Replace cover and securely tighten thumbscrew.
- Page 8 – CHECKOUT; Checkout; CHECKOUT SUMMARY; PRELIMINARY INSPECTION; IMPORTANT: Anytime you reset the safety switch, wait at
- Page 9 – PILOT TURNDOWN TEST; IMPORTANT: If the R4795 is used to prove a pilot flame,; FLAME CURRENT CHECK
- Page 10 – IMPORTANT: Repeat ALL required checkout tests after all; Flame Failure; IMPORTANT: At the completion of all Checkout tests,
- Page 11 – OPERATION • TROUBLESHOOTING; Operation; SAFETY OPERATION; Troubleshooting; IMPORTANT: At the completion of any troubleshooting
- Page 12 – TROUBLESHOOTING; Clean contacts only when instructed to do so in a
- Page 13 – TROUBLESHOOTING • SERVICE; H. Miscellaneous problems; What it is. Ignition interference is a false signal; Service; GENERAL
1
60-2285—7
R4795A
Flame Safeguard
Primary Controls
The R4795A Protectorelay™ Primary Control
provides solid state electronic flame safeguard
protection for commercial and industrial gas or oil
burners. It provides a prepurge period before each
start, and intermittent pilot.
■
120V models meet the requirements of Underwrit-
ers Laboratories Inc. Standard 795 for mechanical
draft and atmospheric burner inputs from 400,000 to
2,500,000 Btu.
■
Meets Underwriters Laboratories Inc. requirements
for oil burner group 8 when 30, 60, or 90 second pre-
purge timer is used.
■
Selection of solid state, plug-in prepurge timers pro-
vides 7, 10, 30, 60, or 90 second prepurge time.
■
Includes terminals for connection of air flow switch
to prove airflow before prepurge period starts, dur-
ing purge, and during the entire Run period.
■
Choice of interchangeable, color-coded, solid state,
plug-in flame signal amplifiers allows use with rec-
tification or ultraviolet type flame detectors.
■
Safe-start feature prevents start when flame or flame
simulating condition is present.
■
Recycles through prepurge if the flame goes out
while burner is running. If pilot flame is not re-
established, safety switch trips and locks out system.
■
A tripped safety switch must be manually reset to
restore operation.
■
Push-to-reset safety switch is dust-resistant enclosed.
■
Optional spdt alarm contacts operate external alarm
on safety switch lockout.
■
Ignition interference circuit (rectification amplifier
only) protects electronic network from high voltage
ignition crossover and provides visual indication
when interference occurs.
■
Solid state circuitry eliminates vacuum tube replace-
ment and increases resistance to vibration. Applica-
tion of power not required during Off cycle; no tube
warmup before starting.
■
Easy-to-replace plug-in components result in faster
service and reduced inventory.
■
Flame current jack, located on the amplifier, provides
means of plugging in a microammeter to measure the
flame signal with system operating.
■
Easy mounting and removal through use of captive
mounting screws, which also serve as electrical
connections.
■
Durable thermoplastic mounting base.
■
Models available with -40
°
F (-40
°
C) temperature
rating.
S.Y. • Rev. 12-94 • ©Honeywell Inc. 1994
60-2285-7
CONTENTS
Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 4
Checkout ......................................................... 8
Operation ..................................................... 11
Troubleshooting ........................................... 11
Service .......................................................... 13
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell R4795A
Summary
60-2285—7 2 R4795A SPECIFICATIONS • ORDERING INFORMATION Specifications R4795A Flame Safeguard Primary Control recycles once after flame failure to try to re-establish pilot before lockout.Use with R7289A Amplifier and rectifying flame rod, recti-fying photocell, or C7012A,C Purple Peeper Ultraviole...
60-2285—7 4 R4795A INSTALLATION Installation Vibration Do not install the R4795A where it could be subject to excessive vibration. Vibration shortens the life of the elec-tronic and mechanical components. Weather The R4795A is not designed to be weathertight. If it is installed outdoors, use a suita...
5 60-2285—7 R4795A INSTALLATION IMPORTANT: Do not run high voltage ignition trans- former wires in the same conduit with the flamedetector wiring. 5. For ignition installations in a contaminating environ- ment, use Honeywell Specification no. R1239001 High Ten-sion Ignition Cable or equivalent. This...