Loading the manual

X-XX UL

INSTALLATION INSTRUCTIONS

® U.S. Registered Trademark
Copyright © 1996 Honeywell Inc. • • All Rights Reserved

Q7300L

Series 2000 Commercial

Thermostat Subbases

APPLICATION

The Q7300L Thermostat Subbase is used with the
T7300D,F Thermostat to provide electronic control of
commercial 24 Vac single zone HVAC equipment. The
T7300/Q7300L is designed for heat-cool applications using
a valve and valve actuator combination for hydronic
heating. See Table 1. It can also be used to control single-
stage conventional heating systems. It provides two-speed
fan control. Terminals are provided for the T7047 Remote
Sensor or the T7147 Remote Sensor and Override
Module. LEDs on the thermostat are prewired and labeled
to indicate heat and cool operation. See Fig. 9 and 10 for
hookup drawings. Refer to form 63-4355 for installation
and operation of the T7300/Q7300.

Table 1. Valve and Valve Actuator Combinations.

IMPORTANT

The valve will not close if the wrong valve and
valve actuator combination is used.

Electrical Rating:
20 to 30 Vac, 50/60 Hz.

System Current :
6 VA maximum at 30 Vac, 50 or 60 Hz.

Output Relay Current:
See Table 2.

Table 2. Maximum Amps at 30 Vac.

Temperature:
Ratings:

Operating Ambient: 40

°

F to 110

°

F (4

°

C to 43

°

C).

Shipping: -30

°

F to +150

°

F (-34

°

C to +65

°

C).

Display Accuracy:

+1

°

F (+0.5

°

C).

Setpoint:

Range: 45

°

F to 95

°

F (7

°

C to 35

°

C).

Differential: 2

°

F (1

°

C).

Humidity Ratings:
5% to 90% RH, noncondensing.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do n

ot

place your old

control in the trash

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

Valve Model

Valve Actuator Model

V5011A, C

ML7984A3019

V5011F, G

ML7984A3001

V5013A, C

ML7984A3019

V5013F

ML7984A3001

Relay

Running (A)

Inrush (A)

Fan

1.6

3.5

Heat

1.6

3.5

Cool

1.6

7.5

Auxillary (Economizer)

1.6

3.5

62-0131-2

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Location

62-0131—2 2 Q7300L SERIES 2000 COMMERCIAL THERMOSTAT SUBBASE Location Subbase without Remote-MountedTemperature Sensor Install the thermostat about 5 ft (1.5m) above the floor inan area with good air circulation at average temperature.See Fig. 1. Do not install the thermostat where it can be affecte...

Page 3 - Mounting Subbase

62-0131—2 3 Q7300L SERIES 2000 COMMERCIAL THERMOSTAT SUBBASE M4839 T T SUBBASE T T T7047C T T T7047C T T T7047G M4842 T T T T SUBBASE T7047C T T T7047C T T T7047C T T T7047C T T T7047C T T T7047C T T T7047C T T T7047C T T T7047C M4841 T T SUBBASE T T T7047G T T T7047G T T T7047G T T T7047G T T T7047...

Page 4 - WIRING SUBBASE; CAUTION

62-0131—2 4 Q7300L SERIES 2000 COMMERCIAL THERMOSTAT SUBBASE WIRING SUBBASE All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instructions whenavailable. Refer to Fig. 9 and 10 for typical hookups. A letter code is located near each terminal for ...