INSTALLATION INSTRUCTIONS

63-2235-05

Q7130A, Q7230A, Q7330A

Modutrol IV Interface Modules

APPLICATION

The Q7130, Q7230, and Q7330 Modutrol IV Interface

Modules are used with Series 90 Modutrol IV Motors (M91XX)

for conversion to electronic (Series 70) control.

FEATURES

• Mounts inside the wiring box of any Series 90 Modutrol

IV Motor (M91XX models). Module protected from

weather by the Modutrol IV NEMA 3 wiring box.

• Mates to quick-connect terminals in motor wiring box

and provides screw terminals for control wiring

connections.

• Features solid state circuitry with surface mount

components.

• Plastic enclosure provides easy handling and

protection for circuitry.

• Q7130A provides selectable voltage range (4-7, 6-9, or

10.5-13.5 Vdc). Adapts M91XX Modtrol IV Motor to

function as M71XX model for M734H,J, M744D,

M745G,P replacements. Includes reversing switch to

allow replacement of electrically normally open or

electrically normally closed motors.

• Q7230A provides current or voltage control (4-20 mA

and 2-10 Vdc) with adjustable zero and span. Adapts

the M91XX Modutrol IV Motor to function as M72XX

model for M744S,T,Y or M745S,T,Y replacements.

Includes reversing switch to allow replacement of

electrically normally open or electrically normally

closed motors.

• Q7330A is an interface to W936 and W945 controls.

Adapts the M91XX Modutrol IV Motor to function as

M73XX model for M734D, M744A, M745A replacements.

Q7130A

Q7230A

Q7330A

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - SPECIFICATIONS

Q7130A, Q7230A, Q7330A MODUTROL IV INTERFACE MODULES 63-2235—05 2 SPECIFICATIONS IMPORTANT: The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifica- tions. Also, this product is tested and calibrated...

Page 3 - INSTALLATION; When Installing This Product...; Installing Terminal Block; CAUTION; SETTINGS AND ADJUSTMENTS; Module Adjustments

Q7130A, Q7230A, Q7330A MODUTROL IV INTERFACE MODULES 3 63-2235—05 INSTALLATION When Installing This Product… 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condi- tion. 2. Check the ratings and description given in this specifi- cation to m...

Page 5 - Fig. 5. Sequential operation of three motors with Q7230A; Fig. 6. Typical wiring diagram for Q7230A Interface

Q7130A, Q7230A, Q7330A MODUTROL IV INTERFACE MODULES 5 63-2235—05 Fig. 5. Sequential operation of three motors with Q7230A Interface Module. 11. Recheck the fully open position and readjust the span potentiometer, if necessary. (Turn the span potentiome- ter clockwise to close the motor, countercloc...