Q539A, H and J Subbases

Installation Instruction for the Trained Service Technician.

Application

Q539 Subbases provide cooling anticipators, and mounting for T87F Thermostats. Q539 Subbases also provide system

and fan switching for heating, cooling, and heating-cooling thermostats. For subbase specifications, refer to Tables 1 and 2.

TABLE 1—SUBBASE SPECIFICATIONS.

Model Description

System

Switch

Fan

Switch

Terminals

See

Fig.

Q539A provides system and fan switching and cooling
anticipator for heating cooling systems. Includes indicator
LOCKOUT LED for use in oil burner systems.

HEAT -
OFF-
COOL

AUTO-ON RH

-

RC-W-Y-G-X

3

Q539H provides fan switching with Z terminal for low voltage
fan switch to control fan in AUTO position.

NONE

AUTO-ON R-W-Y-G-X-Z

4

Q539J provides system switching for control of heating and
cooling for heat pump and electric heating. Auto fan operates
through fan relay on both heating and cooling.

HEAT -
OFF-
COOL

AUTO-ON R-W-Y-G-X-P-O-B

5

TABLE 2—TERMINAL DESIGNATIONS.

Terminal

Connection

R

Transformer.

RC

a

Cooling Transformer.

RH

b

Heating Transformer.

W

Heating Relay or Valve Coil.

Y

Cooling Contactor Coil.

B

c

Heating Damper Motor or Changeover
Valve (if used).

O

d

Cooling Damper Motor or Changeover
Valve (if used).

G

Fan Relay Coil.

X

e

Clogged Filter Switch or Lockout Switch
(primary control).

P

Heat Pump Contactor Coil.

Z

Q539H low voltage fan switch for control
of fan relay in AUTO position for both
heating and cooling control.

a

Cooling transformer in systems with separate heating and
cooling circuits.

b

Heating transformer in systems with isolated heating and
cooling circuits.

c

Circuit only completed between R and B with system
switch in HEAT position.

d

Circuit only completed between R and O with system
switch in COOL position.

e

Only available on subbases with indicator LEDs.

M3375

Mercury Notice

This control contains mercury in a sealed tube. Do n

ot

place control in the trash at the end of its useful life.

If this control is replacing a control that contains mer­

cury in a sealed tube, do

not

place your old control in the

trash.

Contact your local waste management authority for

instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

instructions can damage product or cause a hazardous

condition.
2. Check ratings given in instructions and on product to

make sure product is suitable for your application.

3. Make sure installer is a trained, experienced service

technician.

4. After completing installation check out product opera­

tion as provided in these instructions.

LOCATION

Locate the subbase about 5 ft (1.5m) above the floor in

an area with good air circulation at average temperature.

®U.S. Registered Trademark
Copyright © 2002 Honeywell •

• All Rights Reserved

95-6486-9

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell Q539

Summary

Page 2 - CAUTION; MOUNTING AND WIRING; To prevent interference with the thermostat

Do not mount the subbase where it may be affected by: — drafts or dead spots behind doors or in corners. — hot or cold air from ducts. — radiant heat from the sun, fireplaces, or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall. CAUTION • Disconnect pow...

Page 3 - Settings; SUBBASE SETTING; Checkout; HEATING

Settings SUBBASE SETTING The subbase switching positions control the system operation as described below. SYSTEM SWITCH (some subbases do not have all of the following functions): COOL—cooling system is automatically controlled by the thermostat. Heating system is off. OFF—both the heating and cooli...

Page 4 - COOLING; FAN

COOLING CAUTION If outside air or heat exchange medium (water) is below 10 A C (50 A F), do not operate cooling. Move the system switch on the Q539 to COOL and the fan switch to AUTO. Move the cooling setpoint dial to about 6 A C (10 A F) below room temperature. Cooling equipment should start and th...