Honeywell P520- Manual

Honeywell P520

Honeywell P520– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
Page: / 16

Table of Contents:

  • Page 2 – INSTALLATION; When Installing this Product...; Grounding and Shielding
  • Page 3 – Card Frames
  • Page 5 – Wiring the Viewing Head
  • Page 6 – Power Supply; OPERATION
  • Page 7 – Set Points
  • Page 8 – Additional Set Points
  • Page 9 – SETUP AND ADJUSTMENT; Sighting Adjustment
  • Page 10 – TROUBLESHOOTING; Module Communications
  • Page 16 – Automation and Control Solutions
Loading the manual

USER MANUAL

Put Bar Code Here

66-2066-01

P520 Signal Processor

APPLICATION

The Honeywell P520 is a rack mounting signal processor that

is compatible with viewing heads in the S5XX and S55XB/BE

series. These include models S506, S509, S511 and S512,

and the advanced viewing head series models S550B/BE,

S552B/BE and S556B/BE. There is only one model of the

P520 available, which is DC powered. A rear backplane PC

Board is required for termination (order part number

REARPCB separately for initial installation).

FEATURES

• Rack mounted system, designed to conform to the DIN

41494 19 inch card frame system

• 3U high and 21HP wide, or 5.06 x 4.18 inches with a

length of 8.66 inches (220mm)

• Once rack mounted, together with a power supply and

appropriate viewing head makes up a complete flame

monitoring system

SPECIFICATIONS

Electrical Ratings

Input Power: 22 - 26VDC, 130mA (plus 100mA for each

Viewing Head.)

Battery Backup: 24VDC, 130mA (plus 100mA for each

Viewing Head.) Main Voltage > Battery Voltage

Ambient Temperature:

0°C to 52°C (32°F to 125°F) CSA Rating

0°C to 60°C (32°F to 140°F) FM Rating

Outputs:

Flame Relay: 2 Form C Contacts (DPDT)

Self-Checking Relay: 1 Form C Contact (SPDT)

Contact Ratings: 5A at 30 VDC, 125 VAC and 277 VAC

Max switching voltage 220Vdc, 250Vac

Analog Flame Signal: 0 to 19.8mA current output for

remote meters and 4 to 19.8mA output. (360 ohm max.

resistance.)

Power to Viewing Head:

+26VDC maximum, fused 0.25A (self-resetting)

+14.3VDC pulsing 0.2 seconds ON, 0.8 seconds OFF

Inputs:

Channel Select (Isolated Input):

7.5-30VDC range

Input resistance 3900 ohms

26VDC maximum, 6.4mA

10VDC, 2.3mA

Flame Signal from Viewing Head (Isolated Input):

7.5-30VDC range

Input resistance 3900 ohms

13.6VDC, 3.2mA

Serial Communications:

RS-422 (Differential)

4800 or 9600 baud (user selected)

4 wire / 2 twisted pair

Cable (between viewing head and signal processor):

4 conductor, #16 AWG or #18 AWG, one wire shielded with

braided shield for flame signal. Honeywell C328 cable is

recommended.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell P520

Summary

Page 2 - INSTALLATION; When Installing this Product...; Grounding and Shielding

P520 SIGNAL PROCESSOR 66-2066—01 2 Fig. 1. P520 front faceplate dimensions. Fig. 2. P520 side view dimensions. INSTALLATION When Installing this Product… 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given i...

Page 3 - Card Frames

P520 SIGNAL PROCESSOR 3 66-2066—01 3. Install a ground wire from the ignition transformer case to the igniter assembly. 4. Ensure all igniter wires and cables show no signs of wear. Replace any igniter cables or wires that are frayed or cracked. 5. The viewing head must be electrically isolated from...

Page 5 - Wiring the Viewing Head

P520 SIGNAL PROCESSOR 5 66-2066—01 Wiring the Viewing Head Wiring of the viewing head is made to the terminals on the rear backplane PCB. These terminals are described as follows: Fig. 4 and 5 show four-conductor cable to the viewing head. Note that the flame signal wire going to terminal SIG is shi...