Honeywell N20- User Manual

Honeywell N20

Honeywell N20– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – Fig. 2. Setting units and control elements; Contents of Package; XX
  • Page 3 – Feedback Signal and Manual Adjustment; Power Off/On Behavior; Autoadapt Dip Switch for Normal Operation
  • Page 4 – Voltage/Current Control Signal Selection Dip Switch; Position Indication; Limitation of Rotation Stroke; INSTALLATION; IMPORTANT; Mounting Instructions
  • Page 5 – Wiring; Access cover; Fig. 12. Actuator with access cover removed
  • Page 6 – Wiring Diagrams; MODULATING CONTROL; connecting cable; MODULATING
  • Page 8 – Automation and Control Solutions; Honeywell International Inc.; DIMENSIONS
Loading the manual

PRODUCT DATA

63-2587-1

N20, N34 Series MN7220, MN7234

NON-SPRING RETURN DAMPER ACTUATOR

20/34 Nm (175/300 lb-in) FOR MODULATING CONTROL

GENERAL

These direct-coupled damper actuators provide modulating

control for:

• rotary valves,

• air handling units,

• ventilation flaps,

• louvers, and

• reliable control for air damper applications with up to 50

sq.ft. (20 Nm / 175 lb-in) or 85 sq. ft. (34 Nm / 300 lb-in)

(seal-less damper blades; air friction-dependent).

FEATURES

• New self-centering shaft adapter
• Access cover to facilitate connectivity
• Declutch for manual adjustment
• Mechanical end limits (MN7220 only)
• Field-installable auxiliary switches
• Rotation direction selectable by switch
• Mountable in any orientation (no IP54 if upside down)
• Mechanical position indicator

SPECIFICATIONS

Supply voltage

24 Vac

±

20%, 50/60 Hz;

24 Vdc -10...+20%

Nominal voltage

24 Vac, 50/60 Hz; 24 Vdc

All values stated hereinafter apply to operation under

nominal voltage conditions.

Power consumption

MN7220

6 VA / 6 W

MN7234

8 VA / 6 W

Ambient limits

Ambient operating limits

-5...+140 °F (-20...+60

°

C)

Ambient storage limits

-40...+175 °F (-40...+80

°

C)

Relative humidity

5...95%, non-condensing

Safety

Protection standard

IP54 (non-USA models)
NEMA2 (USA models)

Protection class

II as per EN 60730-1

Overvoltage category

II

Lifetime

Full strokes

60000

Repositions

1.5 million

Mounting

Round damper shaft

3/8...1-1/16” (10...27 mm)

Square damper shaft

3/8...11/16” (10...18 mm);
45° steps

Shaft length

min. 7/8” (22 mm)

Control signal

0(2)...10 Vdc
0(4)...20 mA

Input impedance

100 k

Ω

[0...10 V]

500

Ω

m [0...20 mA]

Feedback signal

Limits

±

1 mA at 0...10 V

Auxiliary switch (when included)

Rating

5 A (resistive) / 3 A (inductive)

Triggering points

5

°

/ 85

°

Torque rating

MN7220

175 lb-in (20 Nm)

MN7234

300 lb-in (34 Nm)

Runtime

95 sec (60 Hz) / 110 sec (50 Hz)

Rotation stroke

95

°

±

3

°

Dimensions

see “Dimensions” on page 8

Weight

3 lbs. (1.35 kg)

Noise rating

40 dB(A) max. at 1 m

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell N20

Summary

Page 2 - Fig. 2. Setting units and control elements; Contents of Package; XX

N20, N34 SERIES MN7220, MN7234 63-2587—1 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further informat...

Page 3 - Feedback Signal and Manual Adjustment; Power Off/On Behavior; Autoadapt Dip Switch for Normal Operation

N20, N34 SERIES MN7220, MN7234 3 63-2587—1 Rotary Movement The control signal and the corresponding rotation direction (clockwise or counterclockwise) can be selected using the rotation direction switch (see part Rotation direction switch in Fig. 2), thus eliminating the need to re-wire. To ensure t...

Page 4 - Voltage/Current Control Signal Selection Dip Switch; Position Indication; Limitation of Rotation Stroke; INSTALLATION; IMPORTANT; Mounting Instructions

N20, N34 SERIES MN7220, MN7234 63-2587—1 4 Voltage/Current Control Signal Selection Dip Switch In its default shipping position, the voltage/current control signal dip switch (see Fig. 4) is set to OFF (= voltage control). as shown in Fig. 4. Setting it to ON results in current control. Position Ind...

Other Honeywell Models