PRODUCT DATA
63-2584—7
MS4120F; MS4620F,S;
MS8120F,S; S2024-F; S20230-F
Fast-Acting, Two-Position Actuators
APPLICATION
The MS4120F, MS4620F, MS8120F, S2024-F, and S20230-F
Fast-Acting, Two-Position Actuators are spring return direct
coupled actuators (DCA) for on/off damper control. The
actuator accepts an on/off signal from a single-pole, single-
throw (spst) controller. Reversible mounting allows actuator to
be used for either clockwise (cw) or counterclockwise (ccw)
spring rotation.
Designed to operate reliably in smoke control systems
requiring Underwriter’s Laboratories Inc. UL555S ratings up to
350°F.
APPLICABLE LITERATURE
— Specification Data Sheet
63-2592
— Motor/Actuator Selection Guide
for Damper Applications
63-8419
— Engineering Manual of Automatic Control
(also called The Gray Manual)
77-1100
— Direct Coupled Actuator
Quick Selection Guide
63-8553
— Damper Torque Calculator
63-8437
FEATURES
• 175 lb-in. (20 N•m) minimum driving torque at 350°F
(176°C).
• Reversible mounting facilitates use in either clockwise
(cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Stainless steel internal spring.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding.
• No audible noise during holding.
• Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac applications.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
• Housing design allows flush mounting to damper.
• Self-centering shaft adapter (SCSA), patent pending.
• Designed to operate reliably in smoke control systems
requiring Underwriter’s Laboratories Inc. UL555S
ratings up to 350°F.
MS4120F, MS4620F, MS8120F
• High temperature Teflon
®
lead wires.
• Models available with integral high temperature (350°F)
SPST position-indicating switches (7°, 85° stroke).
S2024-F, S20230-F, MS4620S, MS8120S
• Double-insulation rating.
• High-temperature, halogen-free, silicone-free
leadwires.
• Models available with integral high temperature (350°F)
SPDT position-indicating switches (7°, 85° stroke).
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS 63-2584—7 4 INSTALLATION When Installing this Product... 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instru...
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS 5 63-2584—7 Fig. 4. Mounting shaft coupling to actuator opposite side. Mounting CAUTION Device Malfunction Hazard. Improper shaft coupling tightening causes device malfunction. Tighten shaft coupling with proper tor...
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS 63-2584—7 6 WIRING See Fig. 6 through 10 for typical wiring diagrams. WARNING Electrical Power Hazard. Line voltage can cause death or serious injury and short equipment circuitry. Disconnect power supply before ins...