5-Year

Limited

Warranty

INSTALLATION INSTRUCTIONS

62-0194-3

N314

ML4202, ML4302, ML4702, ML4802,

ML8202, ML8302 Fast-Acting,

Two-Position Actuators

FOR FIRE/SMOKE CONTROL APPLICATIONS

APPLICATION

The ML4202, ML4302, ML4702, ML4802, ML8202, ML8302

Fast-Acting, Two-Position Actuators are spring return direct

coupled actuators (DCA) with an integral junction box for

on/off damper control. The actuator accepts an on/off signal from

a single-pole, single-throw (spst) controller. Models are available

with clockwise (cw) or counterclockwise (ccw) spring return.

APPLICABLE LITERATURE

— Motor/Actuator Selection Guide

for Damper Applications

63-8419

— Engineering Manual of Automatic Control

(also called The Gray Manual)

77-1100

— Direct Coupled Actuator

Quick Selection Guide

63-8553

— Damper Torque Calculator

63-8437

SPECIFICATIONS

IMPORTANT

The actuator is designed to meet UL555S standards

at 350°F (176°C). The actuator must be tested with

the damper to achieve this rating.

Models:

See Table 1.

Dimensions:

See Fig. 1.

Minimum Damper Shaft Length:

1-3/4 in. (45 mm).

Device Weight:

5 lb (2.3 kg).

Stroke:

95° ± 3°, mechanically limited.

Electrical Ratings:

See Table 1.

Electrical Connections:

Two color coded 16 in. leads; includes ground screw.

One 7/8 in. hole for conduit connections (fittings not included).

Mounting:

3/8 to 1/2 in. square or round damper shafts.

Actuator can be mounted with shaft in any position. Secure

hub to shaft with: Two 1/4-28 UNF set screws. Use 1/8 in.

Allen wrench to tighten set screws.

IMPORTANT

Honeywell does not recommend using linkages with

these actuators because side-loading of the output

hub reduces actuator life.

Ambient Ratings:

Operating Temperature: 0 to 130°F (-18 to 55°C).

Shipping/Storage Temperature: -40 to 140°F (-40 to 60°C).

Humidity: 5% to 95% rh, noncondensing.

Torque Rating (at rated voltage):

Typical Holding: 100 lb-in. (11.3 N•m).

Stall Maximum: 150 lb-in. (17 N•m).

Spring Return: 20 lb-in. (2.2 N•m).

350°F Driving: 20 lb-in. (2.2 N•m).

Design Life (at Rated Voltage):

60,000 full stroke cycles.

Noise Rating (Maximum):

Driving Open: 65 dBA at 1m.

Holding: 20 dBA at 1m (no audible noise).

Table 1. Models.

Cycling Requirements:

Prolonged holding-period (1 year) testing of these actuators

has been performed with no spring return failures. The

actuator and the internal spring are designed to require no

special cycling during long-term holding.

Honeywell recommends following all local, state and national

codes for periodic testing of the entire smoke control

system. Refer to National Fire Protection Association

(NFPA) National Fire Codes®: NFPA90A, NFPA92A and

NFPA92B for your application.

NFPA recommends periodic examination of each fire/smoke

damper (semi-annually or annually) to ensure proper

performance.

Timing (At Rated Torque and Voltage):

Drive Open:

ML4202, ML4302, ML4702, ML4802: 25 sec maximum,

18 sec typical.

ML8202, ML8302: 25 sec maximum, 22 sec typical.

Spring Close: 15 sec.

Environmental Protection Ratings:

NEMA1.

Approvals:

See Table 2.

Model

Spring

Return

Direction

Power Consumption

Voltage Input

in Vac

Running

Holding

ML4202

cw

0.18A, 18W 0.11A, 9W

120 ±10%,

60 Hz

ML4302

ccw

ML4702

cw

0.13A, 18W 0.10A, 11W 230 ±10%,

50/60 Hz

ML4802

ccw

ML8202

cw

16 VA

8 VA

24 +20%, -10%

50/60 Hz

ML8302

ccw

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.