PRODUCT DATA

® U.S. Registered Trademark
© 2004 Honeywell International Inc.
All Rights Reserved

63-2511—1

ML6194, ML6294

Non-Spring Return

Direct Coupled Actuators

APPLICATION

The ML6194 and ML6294 Non-Spring Return Direct Coupled

Actuators (DCA) provide floating single-pole, double-throw

(spdt) control of dampers or valves in heating, ventilating, and

air conditioning (HVAC) applications. The ML6294 has an

internal, electrically isolated feedback potentiometer that can

be used to provide indication of motor output hub position or

slave a Series 90 actuator.

FEATURES

• Mount directly on 1/2 in. to 3/4 in. (13 to 19 mm) round

or square shaft. Mount on 1 in. (26 mm) round shafts

with appropriate insert. All models shipped with 1 in.

insert.

• 300 lb-in. (34 N•m) torque.
• Magnetic coupling eliminates need for mechanical

stops or limit switch adjustments by limiting stall

torque, which is dependent on temperature. Nominal

stall torque at room temperature of 68°F (20°C) is 410

lb-in.

• 95° stroke provides necessary compression of

rubber/neoprene gaskets commonly used on 90° low

leakage dampers.

• Declutch feature allows manual adjustment.
• 165 second synchronous timing can eliminate need for

feedback position indication in closed-loop

temperature control applications.

• Both single-point and three-point mounting

compatibility to allow installation flexibility.

• Models available with or without time-out feature.

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information ........................................................

2

Installation ........................................................................

4

Wiring ...............................................................................

6

Operation ..........................................................................

7

Checkout ..........................................................................

8

Troubleshooting ................................................................

8

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell ML6194

Summary

Page 2 - ORDERING INFORMATION; Torque Ratings at Rated Voltages:

ML6194, ML6294 NON-SPRING RETURN DIRECT COUPLED ACTUATORS 63-2511—1 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional quest...

Page 4 - INSTALLATION; WARNING; Mounting; CAUTION; Changing Hub Inserts.

ML6194, ML6294 NON-SPRING RETURN DIRECT COUPLED ACTUATORS 63-2511—1 4 Device Weight: 3.0 lb (1.36 kg). Noise Rating: 45 dBA maximum at 1 meter. Position Indicator: Mounted on actuator hub. Actuator Design Life: Full Stroke Cycles: 50,000. Repositions: 1,500,000 minimum. Approvals: Underwriter’s Labo...

Page 5 - Actuator Damage Hazard.; Preparation

ML6194, ML6294 NON-SPRING RETURN DIRECT COUPLED ACTUATORS 5 63-2511—1 Fig. 3. Installing mounting bracket on ML6194/ML6294 Non-Spring Return DCA. A typical actuator mechanical connection is shown in Fig. 5; see Fig. 6 through 13 for wiring diagrams. CAUTION Actuator Damage Hazard. Using actuator as ...

Other Honeywell Models