Table of Contents:
- Page 2 – ORDERING INFORMATION
- Page 3 – MS7505 Spring Return Direct Coupled Actuator; SPECIFICATIONS; C7046 Discharge Air Sensors
- Page 4 – Fig. 3. Approximate dimensions of C7400A Solid State; Terminal Connections:
- Page 6 – Fig. 5. Approximate dimensions of back mounting bracket; W7459A,C Solid State Economizer Logic Module; Fig. 6. Approximate dimensions of W7459 Solid State; SPECIFICATIONS: W7212A LOGIC MODULE
- Page 7 – CAUTION
- Page 8 – Personal Injury Hazard.; Location and Mounting; C7046C Discharge Air Temperature Sensor; Location
- Page 9 – Fig. 10. Mounting C7046C Air Temperature Sensor on duct; Wiring; Can Cause Electrical Shock or Equipment Damage.
- Page 10 – LOCATION; Mounting Sensing Elements; Mounting Thermostat
- Page 11 – Economizer Logic Module; Equipment Damage Hazard.
- Page 12 – Temperature Sensor Location and Mounting; OPERATION AND CHECKOUT; resistance versus temperature.; C7400A Solid State Enthalpy Sensor
- Page 13 – Economizer Logic Module performance curves.
- Page 14 – W7459A,C Solid State Economizer Logic; W7212A Optional Applications; SETTINGS AND ADJUSTMENTS; Adjusting Minimum Damper Position
- Page 15 – M7415 Minimum Position Adjustment; W7459A ECONOMIZER LOGIC MODULE
- Page 16 – Remote Minimum Position Control; SEQUENCE OF OPERATION; Economizer Sequence of Operation; (WITH AND WITHOUT DIFFERENTIAL ENTHALPY)
- Page 18 – SETTINGS AND ADJUSTMENTS: W7212; Demand Control Ventilation Setpoint; Minimum Position Adjustment
- Page 19 – EQUATION 1. FORMULA TO AID MINIMUM POSITION ADJUSTMENT.; DCV Maximum Position Adjustment; Enthalpy Changeover Setpoint; Differential Enthalpy Changeover Setting; Exhaust Setpoint; CHECKOUT AND TROUBLESHOOTING
- Page 31 – CHECKOUT AND TROUBLESHOOTING:
- Page 32 – Automation and Control Solutions; Step
PRODUCT DATA
63-2484-2
Solid State Economizer System
(CONSISTING OF: C7046C DISCHARGE AIR SENSOR
OR
C7150B MIXED AIR SENSOR, C7400A
SOLID STATE ENTHALPY SENSOR
OR
C7650A SOLID STATE TEMPERATURE SENSOR, M7415
OR
M8405 DAMPER ACTUATORS
OR
MODULATING DIRECT COUPLED ACTUATORS (MS7505),
T6031H THERMOSTAT AND W7459
OR
W7212 SOLID STATE ECONOMIZER LOGIC MODULE)
APPLICATION
The Solid State Economizer System provides an economical
method of providing cooling air by incorporating outdoor air in
the first stage of cooling in heating, ventilating and air
conditioning (HVAC) systems. The Solid State Economizer
System consists of the C7046C Discharge Air Sensor
or
C7150B Mixed Air Sensor, C7400A Solid State Enthalpy
Sensor
or
C7650A Solid State Temperature Sensor, M7415
or
M8405 Damper Actuators
or
Modulating Direct Coupled
Actuators (MS7505), T6031H Thermostat and W7212
or
W7459A,C Solid State Economizer Logic Module.
FEATURES
C7046C Discharge Air Sensors have probe lengths of 8 in.
(203 mm) and nominal sensor resistance of 3000 ohms at
77°F (25°C).
• No setting or calibration required.
• Solid state components not affected by dust or dirt.
• Fast reacting.
• Rugged aluminum insertion probe.
C7150B Mixed Air Sensor is used with the W7212/W7459
Economizer Module to sense mixed or discharged air in roof-
top packaged air conditioning equipment.
• No setting or calibration required.
C7400A Solid State Enthalpy Sensor and C7650A Solid State
Temperature Sensors are used with the W7212/W7459 Solid
State Economizer Logic Module to sense outdoor and return
air enthalpy or temperature.
• C7400A senses and combines temperature and
humidity (enthalpy) of outdoor air (heat index).
• C7650A senses temperature only.
• When enthalpy/temperature of outdoor air increases,
the outdoor air damper closes to a preset minimum
position.
• When enthalpy/temperature of outdoor air is low, the
outdoor air damper opens to reduce the building
cooling load.
• Additional economizer savings are achieved when two
C7400A Solid State Enthalpy Sensors are connected to
one Logic Module for differential enthalpy changeover
control.
C7150B
M7415/M8405
C7046C
W7459A,C
C7400A/C7650A
W7212
T6031H
Contents
Application ........................................................................
Features ...........................................................................
Ordering Information ........................................................
Specifications ...................................................................
Specifications: M7215 ......................................................
Specifications: W7212A Logic Module .............................
Installation: M7215, M7415, M8405 .................................
Wiring: M7215, M7415, M8405 ........................................
Operation and Checkout .................................................. 12
Settings and Adjustments ................................................. 14
Sequence of Operation .................................................... 16
Operation: W7212 ............................................................ 17
Settings and Adjustments: W7212 ................................... 18
Checkout and Troubleshooting ........................................ 19
Checkout and Troubleshooting: W7212 ........................... 31
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell M8405
Summary
SOLID STATE ECONOMIZER SYSTEM 63-2484—2 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further informati...
SOLID STATE ECONOMIZER SYSTEM 3 63-2484—2 MS7505 Spring Return Direct Coupled Actuator The MS7505 Series Spring Return Direct Coupled Actuators (DCA) are control actuators that provide proportioning control for valves and dampers. They accept a voltage signal from an economizer to position a damper ...
SOLID STATE ECONOMIZER SYSTEM 63-2484—2 4 Fig. 2. Approximate dimensions of C7150B Mixed/ Discharge Air Sensor in in. (mm). Fig. 3. Approximate dimensions of C7400A Solid State Enthalpy Sensor/C7650A Solid State Temperature Sensor in in. (mm). M7415A, M8405A Damper Actuators Provides control of econ...