• Does the lamp connected to the L510 have its switch? Is this switch in the OFF position or Open? If so, consider re-wiring
the lamp to remove this switch to prevent someone from turning off the switch in the future.
• The L510 is not configured correctly. Was it configured via EngINN/PC503? Have you tried to push the configuration from
EngINN to L510 again and see if it allows L510 to turn ON/OFF as expected?
• How are you trying to turn on/off or control the L510?
From a switch locally connected to the H4 4-pin socket on the L510?
If so, verify the switch is working with a meter set to measure continuity. Is the switch shorting the input when closed? Is
the switch fully/correctly connected to the L510 H4 header? Have you configured L510 via EngINN such that its low
voltage input on the H4 RJ9 connection controls its local light output?
From an Inncom switch inside the guest room such as a Modeva or Evora, pressing a button on this switch is supposed to
turn on/off or dim up/down the light(s) connected to the L510?
If so, have you verified the configuration of the Evora/Modeva is correct and is sending the correct/expected commands to
the L510? Have you traced the in-room commands sent from the Evora/Modeva when you press the button and are they
as expected?
2.
The L510 is supposed to dim the lamp connected to it but is only turning full On or OFF.
Possible Reasons:
Are you sure the load/lamp connected to the L510 is dimmable? If it is, what was defined in the INNTool project for the particular
L510? Is the INNTool project configuring the L510 as ON/Off only with no dimming?
Verify the settings in EngINN:
• Select the desired L510 in the particular room
• Click Configure > Advanced Configuration> Outputs.
• Find the “Enable Dimming” option. Is the checkbox cleared? If so, the configuration settings into the L510 from EngINN
have dimming disabled. Change this option to enable dimming, update the room type the L510 is associated with, and
then re-configure the L510 from EngIN.
You can also send a dialog command to the L510 to check if dimming is enabled or disabled. CBL32 Registry 7:3:X:23 DimSetup
(X typically is always 1) controls the Dimming control in the L510. The upper Bit 7 in the value stored in 7:3:1:23 is the “DE”
Dimming Enable bit. It needs to be set for the L510 to be able to Dim its output.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
INCOMM L510 LAMP CONTROLLER USER GUIDE 31-00593-01 16 v1.5 October 26, 2022 • If it is only this one room or a handful of rooms where you need to adjust the L510 Min Dim level, or you want to test just 1 room before applying the change to all rooms, consider creating a new Room Type and assigning th...
INCOMM L510 LAMP CONTROLLER USER GUIDE 31-00593-01 18 v1.5 October 26, 2022 4. In the “Room Commands” section, set the Address and P5 channel to that used by the L510 (Add 2, P5 Chan 1 in this exam - ple), check the “As Query” option, and enter the command “0018C07030114” into the “Command to be sen...
® U.S. Registered Trademark ©2022 Honeywell International Inc. 31-00593-01I Rev. 10-22 The material in this document is for information purposes only. The content and the product described are subject to change without notice. Honeywell makes no representations or warranties with respect to this doc...