INSTALLATION INSTRUCTIONS

60- 0915- 4

L4006A,B,E,H

Aquastat® Controllers

APPLICATION

These boiler-mounted, immersion type controllers

operate in response to temperature changes in hydronic
heating systems.

L4006A breaks the circuit on a temperature rise to the

control setting. It is used for high limit or low limit control.
When used as a controller or as a low limit, a separate

high limit must be used.

L4006B makes the circuit on a temperature rise. It is
used as a circulator controller, delaying circulator

operation when boiler water temperature is below the
control setting.

L4006E,H includes a trip-free manual reset switch.

These models are designed to break the control circuit
whenever the temperature of the controlled medium

reaches the high limit setting. A reset button on the front
of the case must be pressed to re-establish the control

circuit. L4006H also includes bracket and clamp for
surface mounting on pipe or tank.

A plastic bag of heat-conductive compound is included

with the L4006A,B,E Aquastat® Controllers for use when
the sensing bulb is inserted into a well designed for a

large bulb than the one used on the L4006A,B,E. A
124904 Well Adapter, for use on old wells that do not fit

the L4006A,B,E immersion well clamp, can be ordered;
see form 68-0040, Wells and Fittings for Temperature

Controllers.. A setting stop is included to prevent setting
above a desired temperature on limit.

If a well adapter or other accessories are needed, refer to

form 68-0040, Wells and Fittings for Temperature
Controllers, for part numbers and ordering information.

INSTALLATION

When Installing This Product…

1.

Read these instructions carefully. Failure to follow

them could damage the product or cause a
hazardous condition.

2.

Check the ratings given in the instructions and on
the product to make sure the product is suitable for

your application.

3.

Installer must be a trained, experienced service

technician.

4.

After installation is complete, check out product

operation as provided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause serious injury, death or equipment
damage.

Disconnect the power supply before beginning
installation to prevent electrical shock or

equipment damage.

Installing Immersion Well Models
(L4006A,B,E)

IMPORTANT

Obtain the best thermal response with a well
that snugly fits the sensing bulb. The bulb

should be inserted until it rests against the
bottom of the well. Use a well of correct length

and bend the tubing, if necessary, to provide
enough force to hold the bulb against the

bottom of the well. Do not make a sharp bend in
the tubing. A sharp bend can produce a break in

the tubing and cause a loss of fill. This condition
will cause the high and low limit controls to be
made continuously.

If the well is not a snug fit on the bulb, use the

heat-conductive compound as follows. Fold the
plastic bag of compound lengthwise and twist

gently. Snip the end of the bag and insert into
the well. Slowly pull out the bag while squeezing

firmly to distribute the compound evenly in the
well. Insert the bulb into the well. Bend the

tubing, if necessary, to provide force to hold the
bulb against the bottom of the well and to hold

the out end of the bulb in firm contact with the
side of the well. Wipe off any excess compound.

NOTE: Some models have an adjustable capillary

tubing length to 3 inches (76 mm). In these
models, pull out extra tubing from inside the

case, if needed.

Follow the boiler manufacturer instructions, if available;
otherwise, proceed as follows.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - If the Old Well Is Unsuitable.

L4006A,B,E,H AQUASTAT® CONTROLLERS 60-0915—4 2 1. Remove the old control. 2. Refer to the cover insert of the old control to identify and tag each lead as it is disconnected. 3. Leave the old well in place if it is suitable. If Well is Otherwise Suitable But Does Not Fit The L4006 Immersion Well Cla...

Page 3 - Wiring; WARNING

L4006A,B,E,H AQUASTAT® CONTROLLERS 3 60-0915—4 6. Make sure the end of the well fits into the hole in the case. Position the immersion well clamp snugly over the well flange and tighten the clamp screw securely. Mounting Surface Mount Model (L4006H) The L4006H is designed for surface mounting on pip...

Page 4 - OPERATION; ADJUSTMENT; Manual Reset; CHECKOUT

L4006A,B,E,H AQUASTAT® CONTROLLERS 60-0915—4 4 Fig. 5. Typical hookup for gas-fired system with domestic hot water. OPERATION For proper selections of settings, follow boiler manufacturer recommendations: 1. High limit controller: Shuts off burner when water temperature exceeds high limit setting. B...