Honeywell EXCEL 10 W7753A- User Manual

Honeywell EXCEL 10 W7753A

Honeywell EXCEL 10 W7753A– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
Page: / 12

Table of Contents:

  • Page 2 – EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER; INSTALLATION
  • Page 3 – Wiring; Power; Heating and Cooling; IMPORTANT
  • Page 4 – Fig. 6. Transformer power wiring details for one Excel 10; Communications
  • Page 5 – Wiring Details
  • Page 6 – Fig. 9. Typical W7753A unit ventilator application wiring; WALL MODULE; UNIT
  • Page 7 – Fig. 12. Typical 4 to 20 mA Humidity and Enthalpy Sensor
  • Page 8 – CHECKOUT; Step 1. Check Installation and Wiring; first; Fig. 14. Typical 2 to 10 Volt DC humidity sensor to
  • Page 9 – Verify Termination Module Placement; W7753A CONTROLLER STATUS LED; Broadcasting the Service Message; Assign ID; Step 4. Verify Sequences of Operation
  • Page 10 – Name of alarm or error bit
  • Page 12 – Automation and Control Solutions; Honeywell International Inc.
Loading the manual

INSTALLATION INSTRUCTIONS

Put Bar Code Here

95-7520—02

Excel 10

W7753A Unit Ventilator Controller

PRODUCT DESCRIPTION

The W7753A Unit Ventilator Controller is a Free Topology

Transceiver (FTT) L

ON

M

ARK

® Compliant Unit Vent controller

in the Excel 10 family product line.

This controller can be used to monitor/control HVAC

equipment, lighting, and other miscellaneous loads in a

distributed network. The controller is field-mounted to the

equipment that it controls, and the controller wiring is attached

to the screw terminals located on the controller (see Fig. 1).

The W7753A Controller communicates via the 78 kilobaud

Echelon

®

LonWorks

®

E-Bus Network.

Allowable input/output connections consist of wall module

points plus two additional resistive sensor inputs, two voltage/

current inputs, four digital inputs and eight digital Triac

outputs.

For the W7753A, any hardware driven by the Triac outputs

must have a minimum current draw, when energized, of

25 mA and a maximum current draw of 500 mA.

Fig. 1. Excel 10 W7753A Unit Ventilator Controller.

M12688

1

2

3

4

5

6

7

8

9 10 11 12 13 14

15 J3

31 30 29 28 27 26

25 24 23 22 21 20

19 18 17

16

E

GND

LED BYPASS SNSR GND SET PT AI-1

OHM

GND A1-2

OHM

AI-3

V/mA

GND AI-4

V/mA

22VDC

OUT

E-BUS E-BUS

JACK

DI-4 GND DI-3 DI-2 GND

DI-1 24

VAC

24

VAC

COM

1

OUT

2

OUT

3

OUT

4

OUT

5

OUT

6

OUT

7

OUT

8

OUT

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER; INSTALLATION

EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER 95-7520—02 2 INSTALLATION Mount the W7753A in a position that allows clearance for wiring, servicing and controller removal. Avoid mounting the W7753A in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or i...

Page 3 - Wiring; Power; Heating and Cooling; IMPORTANT

EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER 3 95-7520—02 Fig. 3. W7753A DIN rail mounting. Wiring All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams. Controller wiring on the W7753A is terminated to the screw terminal blocks located ...

Page 4 - Fig. 6. Transformer power wiring details for one Excel 10; Communications

EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER 95-7520—02 4 Fig. 5. Power wiring details for two or more Excel 10s per transformer. Fig. 6. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only). Communications Refer to E-Bus Wiring Guidelines, form 74-2865, for a comple...

Other Honeywell Models