Page 2 - INTRODUCTION; Device Description
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 2 INTRODUCTION Device Description The T7350H is a L ON M ARK® certified thermostat that provides networking capability in a L ON W ORKS® system using a transformer-coupled Free Topology Transceiver (FTT). See Fig. 1. The T7350H communicates with many ...
Page 3 - Network Control Provided; MODELS; Products Covered
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 3 63-4368 Network Control Provided The T7350H communicates with other network devices, or nodes, for sharing data such as local inputs. Through the network, a Command Display (S7760) is used to view or modify T7350H operational modes including: • Weekly Sched...
Page 4 - Applicable Literature; ABBREVIATIONS AND DEFINITIONS
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 4 Applicable Literature The following list of documents contains general information related to the T7350H Communicating Commercial Thermostats. Table 3. Applicable Literature ABBREVIATIONS AND DEFINITIONS Application —A special use Building Control f...
Page 5 - Performance Specifications
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 5 63-4368 Network Variables —A class of variables defined in Neuron C that allows communication over the L ON W ORKS® network to other nodes on the network. An output network variable in one node can be bound to a corresponding input network variable(s) in ot...
Page 7 - Communications
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 7 63-4368 Fig. 2. Dimensions of thermostat and subbase in in. (mm). Communications The T7350H provides networking capability in a L ON W ORKS® system using a Free Topology Transceiver (FTT) transformer- coupled communications port running at 78 kilobits per s...
Page 8 - Functional Profile
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 8 L ON M ARK® Functional Profile Fig. 3. T7350H L ON M ARK® Space Comfort Controller Rooftop Object (8504) with Node Object. nv28 nv26 nvoSpaceTempSNVT_ temp_p nv27 nvoUnitStatus SNVT_hvac_status nvoEffectSetptSNVT_temp_p Hardware Output Hardware Outp...
Page 9 - NETWORK CONFIGURATIONS
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 9 63-4368 NETWORK CONFIGURATIONS The T7350H can be configured to perform a variety of activities in which data is sent to and/or received from other nodes on the L ON W ORKS® network. Information that can be shared with other network devices includes: — Curre...
Page 10 - APPLICATION STEPS; Overview
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 10 value will be used in the T7350H as the primary controlled variable. The local space temperature sensor of the T7350H is ignored until the network sensor fails. • Space Humidity Sharing: If a valid humidity value is received at the T7350H Space Hum...
Page 11 - Step 1. Plan the System; Step 2. Determine Required Network Devices; Bus Layout
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 11 63-4368 Refer to the Light Commercial Building Solution System Communication Guide form 71-3123 and the E-Bus Wiring Guidelines, form 74-2865 for a complete description of network topology rules. Prepare Wiring Diagrams, for wiring details. Plan to configu...
Page 12 - Cable Termination; Singly Terminated Network Segment; Doubly Terminated Daisy-Chain Network Segment; CAUTION; Wiring Details
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 12 Cable Termination The FTT network segment requires termination for proper data transmission performance. Use a 209541B Termination Module to connect two of the three termination module wires to the L ON W ORKS® Bus terminals. Refer to L ON W ORKS® ...
Page 15 - General Considerations
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 15 63-4368 General Considerations Table 8 lists wiring types, sizes and distances for the T7350 and Excel 10 products. The T7350 terminal strip accepts 18 through 22 AWG (0.82 to 0.34 sq. mm) wire. Table 8. Field Wiring Reference. NOTE: 1. The X, RH and RC te...
Page 17 - Step 5. Order Equipment
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 17 63-4368 Step 5. Order Equipment After compiling a bill of materials through completion of the previous application steps, refer to Table 10, Ordering Information. Table 10. Ordering Information. Step 6. Configure T7350 Use Excel L ON S PEC ™ Software to co...
Page 18 - Step 7. Troubleshooting
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 18 Step 7. Troubleshooting Table 11. Troubleshooting Information. Symptom Possible Cause Action Display will not come on. Thermostat is not being powered. Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH ...
Page 20 - APPENDIX A - NETWORK TOOLS & WORKSTATIONS
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 20 APPENDIX A - NETWORK TOOLS & WORKSTATIONS Table 12. T7350H Operational Support. Network Tools & Workstations Summary of T7350H Operational Support L ON S PEC ™ L ON S T A TION ™ W 776 0B - XL 15B Cmd Dis p lay - S776 0 CA RE LNS Plugin Da t...
Page 21 - APPENDIX B - NETWORK ALARM REPORTING
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 21 63-4368 APPENDIX B - NETWORK ALARM REPORTING Table 13. T7350H Alarm Change of State Event. A T7350H alarm change of state event is reported by the manufacturer defined output network variable nvoAlarmH. nvoAlarmH Field Description subnet The L ON W ORKS® s...
Page 22 - Identifying Five Most Recent T
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 22 Table 15. Identifying Five Most Recent T 7350 Alarms. The five most recent T7350 alarms are identified in the manufacturer defined output network variable nvoAlarmLog. nvoAlarmLog Field Description alarm1 Alarm log: Most recent alarm. Alarm Codes 0...
Page 23 - APPENDIX C - NETWORK ERROR REPORTING; Reporting T
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 23 63-4368 APPENDIX C - NETWORK ERROR REPORTING Table 16. Reporting T 7350H Errors. T 7350H errors are reported through the manufacturer defined output network variable, nvoError. nvoError Field Description errLoclSpaceSensr Local space temperature sensor not...
Page 25 - APPENDIX D - NETWORK ACCESS TO LOCAL SENSOR DATA
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 25 63-4368 APPENDIX D - NETWORK ACCESS TO LOCAL SENSOR DATA APPENDIX E - SCHEDULING NETWORK DEVICES A T7350H can be used to time schedule the following Honeywell controllers: • Another T7350H. • T7300/Q7300. • XL15C application objects (Control loops/StartSto...
Page 26 - APPENDIX G - NETWORK CONNECTIONS TO OTHER LCBS DEVICES
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 26 APPENDIX G - NETWORK CONNECTIONS TO OTHER LCBS DEVICES Table 18. Network Connections to XL15A AP Inputs. T7350H Network Variable Outputs can be used as inputs to XL15A application objects. XL15A Application Object Application Input Source T7350H Ne...
Page 34 - APPENDIX H - T7350H NETWORK VARIABLE SUMMARY
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 34 APPENDIX H - T7350H NETWORK VARIABLE SUMMARY Table 21. T7350H Network Variable Summary. Nv Name L ON S PEC ™ Ref Name Class Description nciApplVer Application version CONFIG Application type: identifies the current application number for this devic...
Page 44 - Class Description
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT 63-4368 B.B. 11-04 www.honeywell.com Automation and Control Solutions Honeywell International Honeywell Europe S.A. Honeywell Latin American Honeywell International Inc. Honeywell Limited-Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Doug...