PRODUCT DATA

60-2032-4

®U.S Registered Trademark
Copyright © 2005 Honeywell Inc. All Rights Reserved

Q179A,B Gas Pilot Burner Assemblies

GENERAL

Q179A,B Gas Pilot Burner Assemblies use the flame

rectification principle to prove the flame. Q179A,B are used in

conjunction with a suitable electronic flame safeguard control

on industrial or commercial gas and gas pilot ignited oil

burners.

FEATURES

• Q179A is a gas pilot assembly with a flame electrode

(rod) and ignition electrode, making it suitable for

applications requiring an interrupted or intermittent

electrically ignited gas pilot burner.

• Q179A1183 is an “I” port burner with an ignition

electrode (spark) only.

• Q179B has only the flame electrode and is suitable for

use in continuous pilot applications.

• Primary aerated type burner is equipped with stainless

steel fins that provide the proper flame rod area to

ground area ratio for maximum flame signal and flame

stabilization.

• Stainless steel electrode(s) are mounted in ceramic

insulators, which permit electrode adjustment.

• Rajah connectors facilitate disconnecting.
• Bracket permits side or end mounting.

Contents

General .............................................................................

1

Features ...........................................................................

1

Ordering Information ........................................................

2

Specifications ...................................................................

2

Installation ........................................................................

4

Checkout ..........................................................................

5

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - ORDERING INFORMATION

Q179A,B GAS PILOT BURNER ASSEMBLIES 60-2032—4 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number, or specify: 1. Order numbr 2. Burner tip 3. Thermo...

Page 4 - INSTALLATION; When Installing this Product...; WIRING; CAUTION

Q179A,B GAS PILOT BURNER ASSEMBLIES 60-2032—4 4 a On some ground areas, one or more prongs were intentionally removed at the factory. b Orifice 0.025 in. (0.635 mm) diameter. c Orifice 0.0130 in. (0.330 mm) diameter (order separately). d Orifice 0.028 in. (0.711 mm) diameter. INSTALLATION When Insta...

Page 5 - CHECKOUT; Pilot Turndown Test

Q179A,B GAS PILOT BURNER ASSEMBLIES 5 60-2032—4 Use high tension wire, of a type found acceptable by a nationally recognized testing agency, for the wiring to the ignition electrode (Q179A). High tension wires should be rated electrically equivalent to type GTO-10 and should have temperature and hum...

Other Honeywell Models