INSTALLATION INSTRUCTIONS

69-0251-3

AT120A, AT140A, AT150A, AT175A

Universal Transformers

APPLICATION

These transformers are for use in 24 Vac nominal control
circuits. They are typically used in heating/cooling control
systems but can be used in any application that does not
exceed the load ratings. They meet National Electrical

Code Class 2 “not wet” and Class 3 “wet” requirements
and are Underwriters Laboratories (UL) Inc. listed under
UL 1585. They can be mounted through a 7/8 in. knock-
out on the accessory mounting plate (included), or with
the integral mounting feet. See Table 1 for additional
specifications.

INSTALLATION

When Installing this Product …

1.

Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.

3.

Installer must be a trained, experienced service
technician.

4.

After installation is complete, check out product
operation as provided in these instructions.

CAUTION

Electrical Hazard.
Can cause electrical shock or equipment
damage.

Disconnect power supply before beginning
installation.

Table 1. Model Specifications.

Model

Number

Primary

Secondary

Output Rating at

100 Percent Power

Factor

Input

Voltage

(60 Hz)

Wiring

Connections

Voltage

Wiring

connections

Open

Circuit

At Rated

Power

Output

AT120A

120/208/
240

9 in. leads

27.0

24.0

Screw
terminals

20 VA

AT140A

120

9 in. leads

27.0

24.0

Screw
terminals

40 VA

120/208/
240

120/240

208/240

AT150A

120/208/
240

9 in. leads

27.5

24.0

Screw
terminals

50 VA

AT175A

120/208/
240

9 in. leads

27.5

24.0

Screw
terminals

75 VA

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Mounting; Foot Mounting; Plate Mounting; MOUNTING PLATE TO TRANSFORMER

AT120A, AT140A, AT150A, AT175A UNIVERSAL TRANSFORMERS 69-0251-3 2 Mounting The transformer can be mounted in one of three ways:— foot mounting.— plate mounting.— mounting through outlet box knockout hole. Foot Mounting 1. Mount the transformer using screws (not supplied) through the four 3/16 in. x ...

Page 3 - Mounting Through Outlet Box Knockout Hole; sections of knockout.

AT120A, AT140A, AT150A, AT175A UNIVERSAL TRANSFORMERS 3 69-0251-3 Fig. 3. When screw is tightened, clamp holds plate on transformer. MOUNTING PLATE AT LAMINATIONS 1. Remove the large rectangular knockout in the mounting plate as shown in Fig. 4. 2. Hold the transformer so the clamp on the end bell f...

Page 4 - Automation and Control Solutions; Mounting Through Outlet Box Knockout; WIRING; CAUTION; Voltage Check; Fig. 6. Schematics for single and multitap

AT120A, AT140A, AT150A, AT175A UNIVERSAL TRANSFORMERS Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark© 2...

Other Honeywell Models