LIQUID FLOW SWITCHES

SPECIFICATION DATA & MOUNTING INSTRUCTIONS

S6065A1003

S6065A2001

GENERAL

The S6065A1003 and S6065A2001 Liquid Flow Switches are
designed for monitoring flow rates in pipes employed in HVAC
applications. They are suitable for monitoring flow in water,
oil, cooling circuits, and lubrication systems. The S6065A2001
is designed for monitoring aggressive liquids.
See Table 1 for the reset and switch points for water. Data for
other media must be determined empirically.

FEATURES

Cost-effective flow switches for HVAC applications.

High-capacity,

fully-encapsulated NC/NO micro-switch.

A single type suitable for pipes with a diameter of 1 to 8".

COMMON SPECIFICATIONS

Switching capacity

15 (8) A, 24...250 Vac

Lifetime

50000 cycles at nominal load

Working temperature

-40...+85 °C at 90% rel. humidity,
non-condensing

Electrical connection

Screw terminal, wire up to 1.5 mm

2

cable

6...9

mm

Protection class

I according to EN60730

Protection standard

IP65 according to EN60529

Housing material

ABS and corrosion-protected steel

Accessories

PA2 Paddle set

MOUNTING

The S6065A1003 and S6065A2001 Liquid Flow Switches can
be mounted in any desired position far from elbows, valves,
and filters.

NOTE:

The arrow on the housing must point downstream.

When using multiple paddles, the paddles must be
arranged in order of decreasing length downstream,
i.e. with the longest paddle facing the oncoming
liquid.

In the case of vertical pipes, reset the range to balance the
paddle weight. To prevent malfunction caused by impurities in
the medium, do not mount the device with the housing
pointing downwards.

MODELS

Specification

S6065A1003

S6065A2001

Flow medium

non-aggressive liquid

aggressive liquid

Mounting

Rp 1" (ISO7/1)

Rp 1" (ISO7/1)

Maximum pipe temperature

120 °C

120 °C

Pressure

11 bar

30 bar

Paddle material

1.4401

1.4401

Lever yellow

brass

1.4404

Sensor body

yellow brass

1.4404

Housing dimensions

113 x 70 x 65 mm

108 x 70 x 72 mm

Weight

850 g

850 g

Approvals TÜV-approved

TÜV-approved