Page 3 - Installation Procedure; - Adherence to the following will aid in problem-free installation
Installation Procedure Adherence to the following will aid in problem-free installation with long-term reliability: Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to...
Page 5 - Contents
151209 1 Contents Section 1Introduction .............................................................................................................................................. 1-1 1.1 Overview of Basic System .......................................................................................
Page 11 - Silent Knight Fire Product Warranty and Return Policy
Contents 151209 7 8.7.2 Double Interlock Zone Releasing ................................................................................................... 8-16 Conditions Required for a Pre-Alert Output Activation ...................................................... 8-16Conditions Required for a ...
Page 13 - Overview of Basic System; Hardware Features; Reports events to central station by point or by zone.
151209 1-1 Section 1Introduction The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864. 1.1 Overview of Basic System The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards mounted to an...
Page 14 - Software Features; Advanced smoke detector features:; About this Manual; Terms Used in this Manual
IntelliKnight 5820XL Installation Manual 1-2 151209 1.1.2 Software Features • 125 software zones, 250 output groups. • Advanced smoke detector features: Automatic drift compensationMaintenance alert regionPoint status eliminates calibrated smoke test requirements for NFPA 72 • “JumpStart” feature fo...
Page 15 - Compatible Products
Introduction 151209 1-3 1.3 Compatible Products Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight 5820XL. Note: Models SD500-FRCM, and SD500-FRCM-4 are no longer manufactured, but they are still compatible with the IntelliKnight system. Contact Silent Knight if...
Page 16 - How to Contact Silent Knight; IntelliKnight
IntelliKnight 5820XL Installation Manual 1-4 151209 The following modems have been tested by Silent Knight for compatibility with the 5820XL and the Silent Knight Software Suite software packages: 1.4 How to Contact Silent Knight If you have a question or encounter a problem not covered in this manu...
Page 17 - Limitations of Fire Alarm Systems; Smoke particles may be blown away from detectors by air outlets
Introduction 151209 1-5 Limitations of Fire Alarm Systems Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommen...
Page 19 - cluding smoke detectors and other fire alarm devices:; National Fire Alarm Code
Introduction 151209 1-7 Requirements and recommendations for proper use of fire alarm systems in- cluding smoke detectors and other fire alarm devices: Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or buildin...
Page 21 - IntelliKnight 5820XL can be connected to the phone lines:
151209 2-1 Section 2Agency Listings, Approvals, and Requirements 2.1 Federal Communications Commission (FCC) 1. The following information must be provided to the telephone company before the IntelliKnight 5820XL can be connected to the phone lines: This equipment complies with Part 68 of the FCC rul...
Page 22 - Requirements for All Installations; the
IntelliKnight 5820XL Installation Manual 2-2 151209 This product cannot be adjusted or repaired in the field. It must be returned to the factory for service. This equipment is not designed for use with party line service. Connection to party line service is subject to state tariffs. You may contact ...
Page 23 - Call forwarding shall not be used.
Agency Listings, Approvals, and Requirements 151209 2-3 Restricted Options: • The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL certified installations this number must be set from 1 to 3 hours. • The system allows the use of non-latching spot...
Page 25 - Environmental Specifications
151209 3-1 Section 3Before You Begin Installing This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5820XL panel for the first time. 3.1 What’s in the Box? The IntelliKnight 58...
Page 26 - Electrical Specifications
IntelliKnight 5820XL Installation Manual 3-2 151209 3.3 Electrical Specifications Terminal # and Label Description Rating Earth Ground Faults Voltage Current 1 L AC input (hot) 120 VAC, 60 Hz 2.5 A N/A 2 Earth ground N/A N/A N/A 3 N AC input (neutral) 120 VAC 60 Hz 2.5 A N/A 4 X *I/O 6 Flexput™ Circ...
Page 27 - Wiring Specifications
Before You Begin Installing 151209 3-3 3.4 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines: • Isolate input wiring from high current output a...
Page 29 - Board Assembly Diagram
Before You Begin Installing 151209 3-5 3.5 Board Assembly Diagram Figure 3-2 Model 5820XL Assembly Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL assembly to the cabinet. If you should need to remove the board assembly for repair, remove the four mounting n...
Page 30 - Calculating Current Draw and Standby Battery; Current Draw Worksheet Requirements; device manual for the current ratings.
IntelliKnight 5820XL Installation Manual 3-6 151209 3.6 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 3.6.1 Current Draw Worksheet Requirements The following steps must be taken when determinin...
Page 31 - Current Draw Worksheet for SK SLC Devices; and
Before You Begin Installing 151209 3-7 3.6.2 Current Draw Worksheet for SK SLC Devices Use Table 3-1 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per panel) and 99 SK modules per loop ...
Page 34 - Current Draw Worksheet for Hochiki SLC Devices
IntelliKnight 5820XL Installation Manual 3-10 151209 3.6.3 Current Draw Worksheet for Hochiki SLC Devices Use Table 3-2 to determine current requirements during alarm/battery standby operation when Hochiki SLC devices are installed. You can install up 127 Hochiki devices per loop (508 max per panel)...
Page 36 - Maximum Battery Standby Load; Installation Tasks Overview
IntelliKnight 5820XL Installation Manual 3-12 151209 3.6.4 Maximum Battery Standby Load Table 3-3 shows the maximum battery standby load for the 5820XL based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-1 for SK devices and...
Page 39 - Mounting the Control Panel Cabinet; Preventing Water Damage
151209 4-1 Section 4Control Panel Installation 4.1 Mounting the Control Panel Cabinet Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure that you select a suitable location. The panel should be accessible to main drop wiring runs. It shou...
Page 40 - AC Connection
IntelliKnight 5820XL Installation Manual 4-2 151209 4.2 AC Connection At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection. The AC terminals are rated at 120 VAC, 50 or 60 Hz, 2.5A. Figure 4-1...
Page 41 - Battery Connection
Control Panel Installation 151209 4-3 4.3 Battery Connection The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6). Wire batteries in series to produce a 24-volt equiv...
Page 42 - RBB Accessory Cabinet
IntelliKnight 5820XL Installation Manual 4-4 151209 4.3.1 RBB Accessory Cabinet The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size...
Page 43 - Screw the cover screw 3/4 of the way into the cover mounting hole.
Control Panel Installation 151209 4-5 3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5. Figure 4-5 Battery Connections in the RBB Cabinet Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-...
Page 44 - SBUS Wiring; Calculating Wiring distance for SBUS modules
IntelliKnight 5820XL Installation Manual 4-6 151209 4.4 SBUS Wiring This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B). 4.4.1 Calculating Wiring distance for SBUS modules The following instructions will guide you in determining...
Page 46 - Wiring Distance calculation example:
IntelliKnight 5820XL Installation Manual 4-8 151209 Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Serial/Parallel Interface Module The ...
Page 47 - Wiring Configurations; Caution
Control Panel Installation 151209 4-9 4.4.2 Wiring Configurations Figure 4-7 illustrates Class A wiring configuration and Figure 4-8 illustrates Class B configuration. Figure 4-7 SBUS Class A Wiring Figure 4-8 SBUS Class B Wiring SupervisedPower Limited Caution For proper system supervision do not u...
Page 48 - Remote Annunciator 5860 Installation; 860 installation involves the following steps:
IntelliKnight 5820XL Installation Manual 4-10 151209 4.5 Remote Annunciator 5860 Installation The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same functions as the on-board annunciator. Operation is identical. Up to 8 annunciators can be added to the IntelliKnight 5820X...
Page 51 - Flush Mounting with an Electrical Box; Flush Mounting Steps; Remove knockout holes as needed for wires.
Control Panel Installation 151209 4-13 Flush Mounting with an Electrical Box The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double-gang. If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunci...
Page 52 - Drill holes in the surface to match the screw holes on the back box.
IntelliKnight 5820XL Installation Manual 4-14 151209 4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. Figure 4-13 Flush Mounting th...
Page 53 - Model 5860 Connection to the Panel; Connect the 5860 to the panel as shown in Figure 4-14.
Control Panel Installation 151209 4-15 4.5.2 Model 5860 Connection to the Panel Connect the 5860 to the panel as shown in Figure 4-14. Figure 4-14 Model 5860 Connection to the Panel SupervisedPower Limited
Page 54 - Model 5895XL Installation Instructions
IntelliKnight 5820XL Installation Manual 4-16 151209 4.6 5815XL Installation The 5815XL SLC expander lets you add 127 addressable devices. Up to three 5815XLs (adding 381 SLC devices for a total of 508 points) can be used with the system. To install the 5815XL: 1. Make sure power is off at the panel...
Page 55 - 815XL Connection to the Panel
Control Panel Installation 151209 4-17 4.6.1 5815XL Connection to the Panel Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is connected to the panel, it must be added to the system. This programming step is described in Section 4.10. Figure 4-16 5815XL Connection t...
Page 56 - 824 Serial/Parallel Interface Module; 824 installation involves the following steps:
IntelliKnight 5820XL Installation Manual 4-18 151209 4.7 5824 Serial/Parallel Interface Module Installation The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instr...
Page 57 - Configuring the 5824 includes the following steps:; To Parallel Printer
Control Panel Installation 151209 4-19 Figure 4-18 Printer Connection 4.7.1 Selecting 5824 Options Configuring the 5824 includes the following steps: • Add the module to the system. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.3.2). • Sel...
Page 58 - Printer and Output Port Options; to
IntelliKnight 5820XL Installation Manual 4-20 151209 Printer and Output Port Options 1. From the Installer Main Menu, select for Program Menu. 2. Select for Module. 3. Select for Edit Module. 4. From the list that displays, select the 5824 module you want to configure. 5. Press to bypass the next tw...
Page 60 - FACP Connection
IntelliKnight 5820XL Installation Manual 4-22 151209 4.8.2 FACP Connection The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-21. After the 5880 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10. Figure 4-21 ...
Page 61 - LED Wiring
Control Panel Installation 151209 4-23 4.8.3 LED Wiring There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED output...
Page 62 - Dry Contact Wiring
IntelliKnight 5820XL Installation Manual 4-24 151209 4.8.4 Dry Contact Wiring The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tam...
Page 66 - Configuring Modules
IntelliKnight 5820XL Installation Manual 4-28 151209 4.10 Configuring Modules This section describes how to configure any system hardware modules that have been added to the system. 4.10.1 Assigning Module IDs When installing a hardware module (such as, 5815XL, 5824, 5860, 5895XL, 5865-3 or 5865-4),...
Page 67 - Telephone Connection
Control Panel Installation 151209 4-29 4.11 Telephone Connection Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available from Silent Knight for this purpose. A number of programmable options are available for customizing telephone lines. These options are describe...
Page 68 - Conventional Notification Appliance; To install a circuit:
IntelliKnight 5820XL Installation Manual 4-30 151209 4.13 Flexputs ™ I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the control panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as au...
Page 70 - To install a Class A notification appliance circuit:
IntelliKnight 5820XL Installation Manual 4-32 151209 4.13.1.2 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as s...
Page 71 - Conventional Input Switch Circuits; To install a Class B switch:
Control Panel Installation 151209 4-33 4.13.2 Conventional Input Switch Circuits This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations. 4.13.2.1 Class B Inputs You can connect conventional Class B switches, such a...
Page 72 - To install a Class A switch:
IntelliKnight 5820XL Installation Manual 4-34 151209 4.13.2.2 Class A Inputs You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel. To install a Class A switch: 1. Wire the Class A switch as shown in Figure ...
Page 75 - Conventions used for wiring 4-wire Class B loops:
Control Panel Installation 151209 4-37 4.13.4 Installing 4-Wire Smoke Detectors Any compatible U.L. listed four-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed four-wire ...
Page 76 - Figure 4-37 illustrates how to install 4-wire Class A detectors.
IntelliKnight 5820XL Installation Manual 4-38 151209 4.13.4.2 Installing 4-Wire Class A Smoke Detectors Figure 4-37 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once. ...
Page 77 - To install an auxiliary power circuit:; Use a UL listed door holder ESL DHX-1224, for this application.
Control Panel Installation 151209 4-39 4.13.5 Auxiliary Power Installation Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are: • Door Holder (see Section 4.13.5.1) • Constant (see Section 4.13.5.2) • Resettable Power (s...
Page 78 - To install one or two programmable relays, follow these steps.
IntelliKnight 5820XL Installation Manual 4-40 151209 4.13.5.3 Resettable Power Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system re...
Page 79 - Remote Station Applications; Program control panel Relay 1 for alarm.
Control Panel Installation 151209 4-41 4.15 Remote Station Applications 4.15.1 Keltron Model 3158 Installation The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles. The steps for connecting the...
Page 80 - City Box Standby Current:
IntelliKnight 5820XL Installation Manual 4-42 151209 4.15.2 City Box Connection Using the 5220 Module This section describes how to connect the control panel to a local energy municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service....
Page 81 - using a short piece of conduit (must not exceed 20 feet in length).
Control Panel Installation 151209 4-43 4.15.3 NFPA 72 Polarity Reversal Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having compatible rating. 4.15.3.1 Using the 5220 Module When the 5220 is wired and programmed for polarity reversal, it re...
Page 82 - To install the 7644 for polarity reversal:; on the terminals of the Flexput circuit used.
IntelliKnight 5820XL Installation Manual 4-44 151209 4.15.3.2 Using the 7644 Module When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until...
Page 84 - 4 VDC nominal
IntelliKnight 5820XL Installation Manual 4-46 151209 4.15.5 Using a MR-201/T Control Relay From Air Products When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to re...
Page 85 - Transmitter Activated by Dry Contacts
Control Panel Installation 151209 4-47 4.15.6 Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the 5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line res...
Page 87 - List of SK SLC Devices
151209 5-1 Section 5Hochiki and SK SLC Device Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 5.1 List of SK SLC Devices The following SK SLC devices can be used with the control panel. See th...
Page 88 - List of Hochiki SLC Devices
IntelliKnight 5820XL Installation Manual 5-2 151209 5.2 List of Hochiki SLC Devices The following Hochiki SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information. Note: T...
Page 89 - Maximum Number of Devices; SK Devices–A 5820XL system can support a total of 396 SK detectors; OR; Wiring Requirements for SLC Devices; Wiring 5815XL in Style 4 (Class B) Configuration
Hochiki and SK SLC Device Installation 151209 5-3 5.3 Maximum Number of Devices The 5820XL supports SK or Hochiki devices on one 5820XL system. The maximum number of devices per system varies depending on device protocol and the number of 5815XL signaling circuit loop (SLC) expanders added to the sy...
Page 92 - Wiring SK SLC Detectors; To wire SK detectors:
IntelliKnight 5820XL Installation Manual 5-6 151209 5.5 Wiring SK SLC Detectors This section describes how to install SK heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information. This information appl...
Page 93 - Addressing SK SLC Devices; ONES
Hochiki and SK SLC Device Installation 151209 5-7 5.6 Addressing SK SLC Devices All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in ...
Page 94 - Hochiki Detector Installation; Wiring Hochiki Detectors; Set the address for each device as described in Section 5.8.
IntelliKnight 5820XL Installation Manual 5-8 151209 5.7 Hochiki Detector Installation The information in this section applies to the following Hochiki models: SD505-AHS Heat Detector, SD505-AIS Ionization Smoke Detector, and SD505-APS Photoelectric Smoke Detector. Also see Section 5.8 for informatio...
Page 95 - Addressing Hochiki Devices
Hochiki and SK SLC Device Installation 151209 5-9 5.8 Addressing Hochiki Devices This section tells how to address detectors and modules. 5.8.1 SD505-APS, SD505-AHS, & SD505-AIS The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easil...
Page 96 - SLC Devices with Dip Switches
IntelliKnight 5820XL Installation Manual 5-10 151209 5.8.2 SLC Devices with Dip Switches Input and relay module addresses are set using the dip switches on the module board. The chart below shows the available addresses. For example, to select address 3, place dip switches 1 and 2 in the up position...
Page 97 - JumpStart Autoprogramming; See Section 6.1.3 for complete details about running JumpStart.
151209 6-1 Section 6Programming Overview This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully, especially if you are programming the control panel for the first time. The JumpStart feature automates many programmi...
Page 98 - Input Points
IntelliKnight 5820XL Installation Manual 6-2 151209 6.1.1 Input Points JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not need...
Page 99 - to accept Hochiki if
Programming Overview 151209 6-3 3. From the next menu, select for JumpStart. 4. The message "WARNING Will DELETE all system options" displays on the LCD. Select Yes to continue. A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can ta...
Page 100 - Mapping Overview
IntelliKnight 5820XL Installation Manual 6-4 151209 6.2 Mapping Overview This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7. Mapping is an important concept with the control panel. In general terms, map...
Page 101 - Input Point Mapping
Programming Overview 151209 6-5 6.2.1 Input Point Mapping Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone.) Figure...
Page 102 - Output Circuit Mapping
IntelliKnight 5820XL Installation Manual 6-6 151209 6.2.2 Output Circuit Mapping Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5. Figure 6-3 Assigning Output Circuits...
Page 103 - Zone Event Mapping; Manual Pull Alarm
Programming Overview 151209 6-7 6.2.3 Zone Event Mapping There are 8 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may be used (see Sectio...
Page 105 - Mapping LED Points
Programming Overview 151209 6-9 6.2.4 Mapping LED Points Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when Models 5865-3/4 and/or...
Page 106 - Programming Using an Annunciator
IntelliKnight 5820XL Installation Manual 6-10 151209 6.3 Programming Using the 5660 Silent Knight Software Suite You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely. SKSS is an optional software package that lets you easily program the control pan...
Page 107 - Entering & Exiting the Program Menu; To enter Program Mode:; The display prompts you to press the; key to bring up the Main Menu (see Figure; To exit Program Mode:
Programming Overview 151209 6-11 6.4.1 Entering & Exiting the Program Menu To enter Program Mode: 1. Enter the Installer Code (factory programmed default code is 5820). 2. The display prompts you to press the or key to bring up the Main Menu (see Figure 6-7). Figure 6-7 Keypad Enabled Screen 3. ...
Page 109 - Programming Menu Quick Reference
Programming Overview 151209 6-13 6.5 Programming Menu Quick Reference This section of the manual lists all Program Menu options in the order they appear on the sub-menus. Default settings are indicated in text or marked with an asterisk. The comments column provide quick information and a reference ...
Page 117 - UL 864 Programming Requirements; NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND; This product incorporates field programmable software. In
151209 7-1 Section 7Programming This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using the 5660 Silent Knight Software Suite (SK...
Page 118 - SLC Family; Initializing; Modules
IntelliKnight 5820XL Installation Manual 7-2 151209 7.2 SLC Family The 5820XL supports Hochiki protocol SLC devices or SK series SLC devices. You must configure the 5820XL to accept the protocol of the devices you are installing. You cannot mix SLC devices of different protocols. 1. Press or to disp...
Page 119 - Edit Modules
Programming 151209 7-3 7.3.1 Edit Modules The features that can be edited when this option is selected are module name and class of wiring (Class A or Class B), or features that are specific to the module to be edited. To edit an existing module: 1. Enter the installer code. 2. Press or to display t...
Page 120 - Adding a Module; to display the main menu.
IntelliKnight 5820XL Installation Manual 7-4 151209 7.3.1.2 Setting the 5815XL Wiring Class 8. Choose the class of wiring you wish to use for this module by pressing the or arrow, then press . 7.3.2 Adding a Module If you need to add a new hardware module to the system, follow these steps. You must ...
Page 121 - Deleting a Module; If you ever need to delete a module, follow these steps.; Zone; Edit Zone
Programming 151209 7-5 7.3.3 Deleting a Module If you ever need to delete a module, follow these steps. You must be in the Main Menu to perform this task. If necessary, enter the Installer Code. 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. Display re...
Page 123 - Alarm Delay Characteristics
Programming 151209 7-7 Alarm Delay Characteristics 3. Select the alarm delay characteristics (see Table 7-1) by pressing the or arrow. 4. Press . Heat Temperature Setting Use this feature to set the temperature at which heat detectors will respond. The range is 135° to 150° F. All detectors in the z...
Page 124 - Mapping to Zone Events; To map zone events to outputs:
IntelliKnight 5820XL Installation Manual 7-8 151209 7. Then press . 7.4.1.3 Zone Outputs Output groups and cadence patterns are mapped to events. They can be programmed to output when an event occurs in a zone. Some system trouble events can be mapped for the entire system. Section 6.2 of this manua...
Page 125 - ple of how you might map a zone.; Zone Mapping Example; Suppose you want to program Zone 1 so that:
Programming 151209 7-9 8. Select options for each event that could occur in this zone. Figure 7-3 is a complete exam- ple of how you might map a zone. Figure 7-3 Selecting Output Groups/templates and Cadence Patterns for a Zone Event Zone Mapping Example Suppose you want to program Zone 1 so that: •...
Page 126 - groups. Figure 7-4 shows how you would program this application.
IntelliKnight 5820XL Installation Manual 7-10 151209 groups. Figure 7-4 shows how you would program this application. Figure 7-4 Zone Mapping Example
Page 128 - Add Zone; Delete Zone
IntelliKnight 5820XL Installation Manual 7-12 151209 7.4.2 Add Zone To add a zone, follow these steps: 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. Display reads: Initializing Please wait . . . 4. Press to enter zone menu. 5. Press to add a zone. A z...
Page 129 - View Zone Points; To view the points in a zone, follow these steps:
Programming 151209 7-13 7.4.4 View Zone Points To view the points in a zone, follow these steps: 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. Display reads: Initializing Please wait . . . 4. Press to enter zone menu. 5. Press to view zone points. 6. ...
Page 130 - Group; Edit Group
IntelliKnight 5820XL Installation Manual 7-14 151209 7.5 Group An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify programming because you have to program the output characteristics that are common to all of the group points once, ...
Page 131 - Silencing Options
Programming 151209 7-15 8. Select the characters for the zone name by pressing the or arrow until the desired character is shown then press . OR Enter the Numerical Designator for the character you want, then press . See Appendix B of this manual for a list of available characters and their numeric ...
Page 132 - Response with System-Wide Conditions
IntelliKnight 5820XL Installation Manual 7-16 151209 Response with System-Wide Conditions You can select whether an output group will respond to various system-wide occurrences. (See Figure 7-8 for location of this field.) 11. To get to this menu item repeat steps 1 through 6 of Section 7.5.1. 12. T...
Page 133 - Add Group; Delete Group
Programming 151209 7-17 16. Press . 17. Enable group activation for a condition (see Table 7-3) by pressing the or arrows to select Y (yes) or N (no). 18. Press . 19. Repeat steps 14 and 15 for all the activation options. 7.5.2 Add Group To add a group: 1. Enter the installer code. 2. Press or to di...
Page 134 - View Group Points; Edit Output Group Templates
IntelliKnight 5820XL Installation Manual 7-18 151209 7.5.4 View Group Points 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. Display reads: Initializing Please wait . . . 4. Press to enter group menu. 5. Press to view group points. 6. Enter the group nu...
Page 135 - Point; Point Programming For 5815XL Module
Programming 151209 7-19 eight output groups. To create Output Group Templates: 1. From the Main Menu, select for Program Menu. 2. From the Program Menu, select for Group. 3. At the next screen, select for Edit OPG Template. 4. Select the template number (01 - 08). 5. Select output group number. See ...
Page 136 - Select the type of device by pressing the
IntelliKnight 5820XL Installation Manual 7-20 151209 8. Press . 9. Select the type of device by pressing the or arrows. Refer to Table 7-5 under col- umn heading “Type Selection” for a list of choices. Table 7-5: Point Programming Options for 5815XL Modules Type Selection Function Latching Option Co...
Page 141 - Or
Programming 151209 7-25 Or Press to skip point name edit. 16. Repeat Steps 1 through 15 for all circuits. Table 7-6: Menu choices for Internal/External Power Module Choices Type Selections Function Selections for each Type Comments Enter Point or Circuit Select Type UNUSED B NOTIF A NOTIF AUX PWR CO...
Page 143 - System Options
Programming 151209 7-27 14. Repeat Steps 1 through 13 for all points. 7.6.3.1 Assigning a Name to Points You can assign a name to a point to make it easier to recognize on a display. To edit a point name:1. Do steps 1 through 4 in Section 7.6.3. 2. Using the or arrow, select the module of the point ...
Page 144 - Reporting Account; To access the Reporting Accounts screen:
IntelliKnight 5820XL Installation Manual 7-28 151209 7.7.1 Reporting Account Up to four reporting accounts can be used with the control panel. Events in accounts are reported by zone. Each account is assigned an up-to-6-digit account number. Each account is also assigned a unique ID (1-4) which dete...
Page 145 - Edit Account Number; Select a reporting format for each account. Options are:
Programming 151209 7-29 7.7.1.1 Edit Accounts 6. From the next menu, select for Edit Account. A screen similar to one shown in Figure 7-12 will display. The following subsections describe the options on each field. Figure 7-12 Reporting Account Editing Screen Select Account (ID) The control panel pr...
Page 146 - Events to Report
IntelliKnight 5820XL Installation Manual 7-30 151209 Events to Report The next six options select which types of events (or event families) will be reported to this account. (See Figure 7-12 for location of these options on the screen.) Events are reported by zone. 10. Press the or arrow to select M...
Page 147 - Repeat step 14 for the secondary phone line.; Telephone Number; Enter up to 40 characters for phone number for this account.
Programming 151209 7-31 15. Repeat step 14 for the secondary phone line. Telephone Number Enter up to 40 characters for phone number for this account. The following special characters are available: Use the number buttons on the annunciator or the up- and down-arrow keys to select special characters...
Page 149 - Select the phone line to be edited (1 or 2) by pressing the
Programming 151209 7-33 6. Select the phone line to be edited (1 or 2) by pressing the or arrow, then press . Figure 7-13 Phone Lines Editing Screen 7.7.2.1 Dialing Prefix Enter up to 8 characters to be used for such things as PBX dial-out codes, a pause, and so on. The following special characters ...
Page 150 - Enter the desired number of answer rings, then press
IntelliKnight 5820XL Installation Manual 7-34 151209 7.7.2.2 Number of Answer Rings This option is used in conjunction with the 5660 SKSS. Use the option to determine the number of rings before the panel answers a call from the computer. Range is 00-15 rings. This option is factory-programmed as 06 ...
Page 151 - by pressing the
Programming 151209 7-35 disabled by default. For 5211 installation, see Section 4.12. Note: Ground start cannot be used in UL installations. 12. Select Y (ground start used monitor line) or N (ground start not used don’t monitor line) by pressing the or arrow, then press . 7.7.2.7 Answering Machine ...
Page 154 - Miscellaneous Options 1
IntelliKnight 5820XL Installation Manual 7-38 151209 7.7.4 Miscellaneous Options 1 Through this programming option you can set the water flow delay time, low AC report delay, enable or disable automatic daylight savings time adjustment, clock format, and AC clock frequency. 7.7.4.1 Water Flow Delay ...
Page 156 - Yes
IntelliKnight 5820XL Installation Manual 7-40 151209 7.7.4.2 Low AC Report Delay Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations. You can adjust the number of hours before a Low AC report will be sent to the central station. To program low AC...
Page 157 - Miscellaneous Options 2
Programming 151209 7-41 7.7.5 Miscellaneous Options 2 Through this programming option you can turn the strobe synchronization during silence feature On or Off, and select the control panel to report events by zone or by point. To edit miscellaneous options 2: 1. Enter the installer code. 2. Press or...
Page 158 - Miscellaneous Options 3; On
IntelliKnight 5820XL Installation Manual 7-42 151209 7.7.6 Miscellaneous Options 3 From Miscellaneous Options 3, you set the alarm verification time, turn the Plex Door option on/off, and set the start and end week and month of Daylight Saving Time. To edit Miscellaneous Options 3: 1. Enter the inst...
Page 160 - Edit Banner Message
IntelliKnight 5820XL Installation Manual 7-44 151209 7.7.7 Edit Banner Message The banner is the message that displays on the panel LCD when the system is normal, that is, when no alarms or troubles exist and no one is currently using system menus. You can create a customized message, which can be u...
Page 162 - Computer Account; To program computer account information:
IntelliKnight 5820XL Installation Manual 7-46 151209 7.9 Computer Account An installer at the panel site can initiate communications between the panel and a computer running the 5660 SKSS (see also Section 8.5.16). In order for this communication to function properly both the computer (running the s...
Page 163 - To change an access code:
Programming 151209 7-47 7.10 Access Codes Access codes provide the user access to the control panel functions. Each access code can be customized for each user. This allows some users the ability to access programming and other higher level panel functions, while other users may only need access to ...
Page 164 - Select Profile 01
IntelliKnight 5820XL Installation Manual 7-48 151209 Please wait . . . 4. Select for System Options. Display reads: Select Profile 01 Fire Fighter’s Key 5. Select the access code you wish to edit by pressing the or arrow. 6. Then press . 7.10.1 Profile Edit Menu From the Profile Edit Menu you can ch...
Page 165 - Press; User and Installer Default Codes
151209 8-1 Section 8System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this entire section carefully before operating the panel. Press to view Main Menu: Select the ...
Page 166 - LCD Displays; Key Operation
IntelliKnight 5820XL Installation Manual 8-2 151209 8.2.1 LCD Displays The control panel LCD displays system messages, annunciates alarms, supervisories and troubles; provides status information; and prompts for input. These messages can be up to 80 characters, displaying over four lines of 20 chara...
Page 167 - Menu System; Main Menu Overview
System Operation 151209 8-3 8.4 Menu System The control panel is easy to operate from Main Menu. To view the Main Menu press the or button on the control panel or remote annunciator, then turn the firefighter’s key clockwise or enter your access code. The Main Menu will appear as shown in Section 8....
Page 168 - Using the Menus; Basic Operation; Setting Time and Date
IntelliKnight 5820XL Installation Manual 8-4 151209 8.4.2 Using the Menus 8.5 Basic Operation 8.5.1 Setting Time and Date 1. From the Main Menu, select for Set Date and Time. 2. Make changes in the fields on the screen. Use (right arrow) to move through the fields. Use the and to select options in t...
Page 169 - View Event History
System Operation 151209 8-5 8.5.4 View Event History Use the View Event History feature to display events on LCD. From the Main Menu, press to select Event History. Events will begin displaying with most recent events first. The panel can store up to 1000 events. When it reaches its 1000-event capac...
Page 170 - Conduct a Walk Test; for Walk Test-No Rpt. The LCD will display “WALK TEST STOPPED” on; Conduct a Dialer Test
IntelliKnight 5820XL Installation Manual 8-6 151209 8.5.7 Conduct a Walk Test 1. From the Main Menu, press for System Tests. 2. Select for Walk Test-No Rpt. The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER = start test” on Line 2. If you select this option, central station report-ing wi...
Page 171 - Silence alarms or troubles; 1 Check Detector Through Point Status
System Operation 151209 8-7 8.5.9 Silence alarms or troubles Press and enter your code or rotate the key at the prompt. If an external silence switch has been installed, activating the switch will silence alarms or troubles. If you are already using system menus when you press , you will not need to...
Page 173 - 6 Communicating with a Remote Computer; To initiate communication:
System Operation 151209 8-9 8.5.16 Communicating with a Remote Computer An installer at the panel site can initiate communications between the panel and a computer running the SKSS 5660. You can use this feature to upload a panel configuration. For example, if you have made programming changes to an...
Page 175 - Operation Mode Behavior
System Operation 151209 8-11 8.6 Operation Mode Behavior The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the behavior of the panel in each of these modes. Table 8-1: Operation Mode Behavi...
Page 178 - Releasing Operations
IntelliKnight 5820XL Installation Manual 8-14 151209 8.7 Releasing Operations This control panel supports two types of releasing, Double Interlock Zone, and Single Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the system, and the Single Interlock does not....
Page 179 - Single Interlock Zone Releasing; Conditions Required for an Pre-Alert Output Activation
System Operation 151209 8-15 8.7.1 Single Interlock Zone Releasing A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch. Conditions Required for an Pre-Alert Output Activation If any single addressable detector is activated, the “Pre-Alert” o...
Page 180 - Double Interlock Zone Releasing; Conditions Required for a Pre-Alert Output Activation
IntelliKnight 5820XL Installation Manual 8-16 151209 8.7.2 Double Interlock Zone Releasing A Double Interlock Zone uses a minimum of two Addressable detectors, a designated manual release switch, and an interlock switch input. An interlock switch is typically a dry-contact pressure switch and will b...
Page 181 - Smoke Alarm Verification
System Operation 151209 8-17 8.8 Smoke Alarm Verification Figure 8-6 illustrates how the Smoke Alarm Verification cycle operates. Figure 8-6 Smoke Verification Cycle During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
Page 183 - Receivers Compatible with the Control Panel; Table 9-1 shows receivers compatible with the control panel.; Reporting Formats Dialer Outputs
151209 9-1 Section 9Reporting This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Contact ID formats. 9.1 Receivers Compatible with the Control Panel Table 9-1 shows receivers compatible with the control panel. 9.2 R...
Page 192 - Periodic Testing And Maintenance
IntelliKnight 5820XL Installation Manual 10-2 151209 10.2.1 Periodic Testing And Maintenance To ensure proper and reliable operation, it is recommended that system inspection and testing be scheduled monthly or as required by national and/or local fire codes. Testing should be done by a qualified se...
Page 193 - Initiating devices
Testing and Troubleshooting 151209 10-3 3) When necessary, activation of Notification Appliances can be prevented by the DISABLE function Testing: 1) Activate a input via an alarm initiating device and check that the correct outputs activate (Notification Appliances sound/flash, relays activate, ala...
Page 194 - Built-in Troubleshooting and Testing Tools; YES
IntelliKnight 5820XL Installation Manual 10-4 151209 10.3 Built-in Troubleshooting and Testing Tools The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while testing and troubleshooting points and SLC devices. 10.3.1 SLC Device Locator SLC...
Page 196 - Follow these steps to control a I/O point:
IntelliKnight 5820XL Installation Manual 10-6 151209 10.3.3 I/O Point Control This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a point’s output mapping. Follow these steps to control a I/O point: 1. Select (Point Functions) from the Main Me...
Page 199 - SLC Point Record; You can use the chart that begins below to keep track of SLC points.
151209 11-1 Section 11Installation Records This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed. 11.1 SLC Point Record You can use the chart that begins below to keep track of SLC points. Default addresses for ID: On-board: = 33 5815...
Page 205 - Copy these pages if you additional sheets.
Installation Records 151209 11-7 Copy these pages if you additional sheets. 5815-3 68 5815-3 98 5815-3 69 5815-3 99 5815-3 70 5815-3 100 5815-3 71 5815-3 101 5815-3 72 5815-3 102 5815-3 73 5815-3 103 5815-3 74 5815-3 104 5815-3 75 5815-3 105 5815-3 76 5815-3 106 5815-3 77 5815-3 107 5815-3 78 5815-3...
Page 206 - Conventional Output Point Record
IntelliKnight 5820XL Installation Manual 11-8 151209 11.2 Conventional Output Point Record This chart can be used to keep track of how conventional output points (circuits) have been configured. Point/Circuit Group Description 1 2 3 4 5 6 7 8
Page 207 - Notification Appliances
151209 A-1 Appendix ACompatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. Note: Not all devices can use the Sync ...
Page 218 - Two-Wire Smoke Detectors
IntelliKnight 5820XL Installation Manual A-12 151209 A.2 Two-Wire Smoke Detectors Table A-2 lists two-wire smoke detectors that are compatible with the fire control panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. Note: The maximum nu...
Page 221 - Characters used for Naming
151209 B-1 Appendix BSpecial Characters Lists This section contains tables of programmable characters that may be used for device, module, and zone names or phone numbers. B.1 Characters used for Naming Table B-1 list the available character and their associated numeric designator. When programming ...
Page 223 - General Terms and Conditions; . Silent Knight has the authority to determine
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. ...
Page 224 - Advanced Replacement Policy
Advanced Replacement Policy • Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the first 6 months of the warranty period. These items must be returned with transportation charges prepaid and must be accompanied by a return authorization. ...
Page 225 - “SILENT KNIGHT” is a registered trademark.; Li mi ted Warrant y; All returns for credit are
This warranty replaces all previous warranties and is the only warranty made by SILENT KNIGHT. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. “SILENT KNIGHT” is a registered trademark. Li mi ted Warrant y SIL ENT KNIGHT warrants products manu factured...