Honeywell 00007 - User Manual
Honeywell 00007 – User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – TECHNICAL SPECIFICATIONS; Power Characteristics; Draft
- Page 3 – Compliances
- Page 4 – Thermostat Ordering Part Numbers
- Page 5 – DIMENSIONS
- Page 6 – Honeywell Building Solutions; GENERAL SAFETY
PRODUCT DATA
TC400A Series Commercial Thermostat
CONNECTED DEVICE FOR COMMERCIAL BUILDINGS
Disclaimer
All images used in this document are for illustrative
purposes only and may not match the actual product.
APPLICATION
TC400A Series Thermostat is an advanced,
con gurable, connected device for commercial buildings.
It controls and monitors RTU, AHU, Heat Pump equipment,
and their con gurations. This device communicates over
Wi-Fi, Bluetooth, BACnet IP, Sylk, easily integrates with the
building automation system.
The built-in intelligent control algorithms of the device
help to achieve the perfect balance between Energy
E ciency and Comfort. The device is packaged with
numerous presets suitable for most commercial building
requirements that enable the easy and quick initial setup.
The rmware of the device can be upgraded via Wi-Fi
network. The device has four universal terminals and a
pair of Sylk terminals to connect with sensors or other
accessories. It also has a built-in temperature sensor,
humidity sensor.
FEATURES
• The device can be easily commissioned through the
Connect mobile app.
• Easily customizable and intuitive UI.
• Supports BACnet system schedule and holiday
con guration.
• Multiple, con gurable, levels of user privilege access
for features such as Reminders, Occupancy set points,
Date/Time, Schedules, Calendars of special events,
remote and local Manual Override, remote and local
Occupancy Override, Choice of language and units, and
screen lockouts to prevent unauthorized settings
changes.
• High level control algorithms such as Auto Changeover,
Adaptive Intelligent Recovery, Pre-occupancy Purge,
Power up disable time, Freeze protection, and Demand
limit controls are supported.
• Settings to switch Fahrenheit to Celsius and vice-versa.
• All set points are limited automatically between 40°F to
120°F.
• Real-Time Clock time keeping accuracy with 72 hour
retention during power loss.
Equipment Control Features
• 2H/2C Heat Pump, 2H/2C Conventional and
modulating heat system
• Constant speed Fan, 2-speed Fan, and Variable Speed
Fan
• Packaged Economizer Coordination Output
• Multiple Dehumidi cation and Humidi cation options
• Service mode to manually command the outputs to test
the operation of the mechanical equipment
• Auto mode to switch between heating and cooling
according to the current space temperature
• Staging control, PID Tuning, CPH, OAT Lockout, DAT
Lockout, Modulating control
• Demand Limit Control to save energy
• System Switch Options
• Smoke Monitor
Draft
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
TC500A-N COMMERCIAL THERMOSTAT 31-00398M-01 | Rev. 10-20 2 TECHNICAL SPECIFICATIONS Power Characteristics Display IO Characteristics Operating Environment Table 1. Power Characteristics Power Supply Rated voltage: 24VAC 50/60Hz, Working voltage range: 20-30VAC, UL listed class-2 transformer or IEC 6...
TC500A-N COMMERCIAL THERMOSTAT 3 31-00398M-01 | Rev. 10-20 Compliances Communication Baud Rates Electrical Characteristics Supported Sensors and Devices • Indoor/Outdoor Air Temp Sensor • Discharge sensor/Supply air sensor • CO2 sensor • Mixed air sensor • Occupancy sensor • Dirty filter • Proof of ...
TC400A Series COMMERCIAL THERMOSTAT 4 Thermostat Ordering Part Numbers Terminal Assignments 24VAC RC 24VAC power from cooling transformer G Fan Y1 Relay output, Compressor contactor (stage1) Y2 Relay output, Compressor contactor (stage2) W1 Relay output, Heat (stage1) W2 Relay output, Heat (stage2) ...