Table of Contents Table of Contents 1.0 Inverter Single Split ......................................................................................................1 1.1 Product line-up ........................................................................................................11.2 Print...
Page 5 - Safety Cautions; Caution and warnings; • The caution items are classified into “; ” and “; Caution; Caution in Repair; Warning; can generate toxic gases when it contacts flames.
Table of Contents Safety Cautions Caution and warnings • Be sure to read the following safety cautions before conducting repair work. • The caution items are classified into “ Warning ” and “ Caution ”. The “ Warning ” items are especially important since they can lead to death or serious injury if ...
Page 6 - The water inside the unit can spill and wet the furniture and floor.
Table of Contents iv Caution Do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock. Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock. Be sure to provide the grounding...
Page 7 - Cautions Regarding Products after Repair; electrical shock, excessive heat generation or fire.
Table of Contents Cautions Regarding Products after Repair Warning Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock,...
Page 8 - Inspection after Repair; a power outlet all the way.; connections at the soldered or crimped terminals are secure.
Table of Contents vi Caution Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and r...
Page 9 - Inverter Single Split; Nomenclature
Inverter Single Split 1 1.0 Inverter Single Split 1.1 Product line-up 1.1.1 Indoor Unit Nomenclature Classification Remote Controller PCB Air Purification Marking Others BRC52A61 BRC52A62 BRC52B63 BRC52B64 W_2_03C W_2_03D W_2_03E W_2_03E_M W_2_04A W_2_04B Saranet Filter Titanium Apatite UL CE Auto R...
Page 11 - Item Indication on PCB Description
Inverter Single Split 3 1.2 Printed Circuit Board (PCB) connector wiring diagram 1.2.1 Indoor PCB: FTKB09/12AXVJU, FTKN09/12AXVJU, FTXB09/12AXVJU, FTXN09/12AXVJU 1.2.1.1 Main PCB: W_2_03D ; W_2_03E ; W_2_03E_M Item Indication on PCB Description 1 A1 Connector for fan motor 2 A2 Connector for swing m...
Page 12 - Item; Operational LED
Inverter Single Split 4 1.2.1.2 Signal board Item Indication on PCB Description 1 A1 Operational LED 2 A2 Connector for Control PCB 3 A3 Remote controller signal receiver 4 A4 Operation ON/OFF switch 5 A5 Buzzer A1 A2 A3 A4 A5 Applicable Model : FTKB09/12AXVJU FTXB09/12AXVJU Applicable Model : FTKN0...
Page 15 - Item Indication on PCB
Inverter Single Split 7 1.2.3 Outdoor PCB: RKB09/12AXVJU, RKN09/12AXVJU, RXB09/12AXVJU, RXN09/12AXVJU 1.2.3.1 Main PCB Item Indication on PCB Description 1 S11 Connector for S10 on main PCB 2 HL1, HN1, S Connector for terminal board 3 E1, E2 Terminal for earth wire 4 HL2, HN2 Connector for HL3 HN3 o...
Page 16 - Connector for indoor PCB
Inverter Single Split 8 1.2.4 Outdoor PCB: RKB18/24AXVJU, RKN18/24AXVJU, RXB18/24AXVJU, RXN18/24AXVJU 1.2.4.1 Filter PCB Item Indication on PCB Description 1 S11 Connector for indoor PCB 2 FU3 Fuse (20A) 3 V2, V3 Varistor
Page 17 - Connector for filter PCB
Inverter Single Split 9 1.2.4.2 Main PCB Item Indication on PCB Description 1 S10 Connector for filter PCB 2 S20 Connector for electronic expansion valve coil 3 S40 Connector for overload protector 4 S70 Connector for fan motor 5 S80 Connector for four way valve coil 6 S90 Connector for thermistors ...
Page 18 - Model; Outdoor Unit
Inverter Single Split 10 1.3 Piping Length & Elevation Model Max. total piping length, L [ft,(m)] Max. height difference, E [ft,(m)] Pre-charge for o to piping length [ft,(m)] Additional charge [oz/ft (g/m)] RK(X)B09AX RK(X)N09AX 65.6 (20) 32.8 (10) 25 (7.6) 0.21 (20) RK(X)B12AX RK(X)N12AX 65.6 ...
Page 19 - Dimension; FOR ILLUSTRATIVE PURPOSES ONLY
Inverter Single Split 11 1.4 Outline & Dimension 1.4.1 Indoor Unit Model: FTK(X)B09/12AX, FTK(X)N09/12AX Dimension Model A B C D E F G H I J K L M 09/12 35-1/16 (890) 11-11/16 (297) 8-1/4 (210) 4-1/16 (104) 5-9/16 (141) 1-3/16 (30) 1-13/16 (46) 2-3/16 (55) 2-3/16 (56) 6 (153) 7-1/8 (181) 8-1/8 (...
Page 25 - Tr = Room Temperature
Algorithm & Control 17 2.0 Function & Control 2.1 Temperature Control The temperature is detected by the room temperature thermistor (either on the unit or on the wired panel). The set temperature can be selected either through remote controller or wired controller by user. Target temperatur...
Page 27 - Automatic Cooling / Heating Function; Cold Draft Prevention; Temperature of
Algorithm & Control 19 2.4 Fan Mode • Compressor and Outdoor Fan OFF. Indoor Fan remains ON. • Only High, Medium and Low fan speeds are allowed. • When changing cool mode to fan mode, the compressor will stop and outdoor fan stops based on fan OFF control. • Compressor only ON if the minimum sto...
Page 28 - Cool mode; activated; User set
Algorithm & Control 20 2.7 Sleep Mode SLEEP Mode can be activated through the remote controller to keep the thermal comfort while sleeping. SLEEP Mode continues operation at the target temperature for the first hour, then automatically raises the target temperature slightly in case of cooling, o...
Page 29 - Powerful function; TURBO; Indoor; Send Signal; and the system will be restarted
Algorithm & Control 21 2.10 Powerful function • Press (for FTK(X)B-AX models) or “ TURBO ” for (FTK(X)N-AX models) for powerful mode. • When POWERFUL/TURBO button is pressed, the fan speed will run at maximum speed for 20 minutes. • Press again to deactivate the function.• Available in HEAT and ...
Page 30 - Functions of Thermistor; Thermistor
Algorithm & Control 22 2.12 Thermistors in RK(X)B, RK(X)N Functions of Thermistor Thermistor Functions Discharge pipe 1. The discharge pipe thermistor is used for controlling discharge pipe temperature. If the discharge pipe temperature (used in place of the inner temperature of the compressor) ...
Page 31 - Minimum Off Time Control; after power resume from failure.; Auto Random Restart; Default setting; Cut off the jumper
Algorithm & Control 23 2.13 Minimum Off Time Control To prevent frequent compressor ON/OFF & to allow pressure equalization • The compressor will be on 3 minutes stand-by after turning OFF before it is allowed to turn ON. • Outdoor fan OFF delay to improve pressure equalization & to prev...
Page 32 - Four Way Valve Control; Operating mode; Outdoor Fan Control
Algorithm & Control 24 Applicable for PCB W_2_04A & W_2_04B (For all class 18/24) 2.16 Four Way Valve Control Change over switching is only carried out during operation.OFF delayed is applied when the coil switches from ON to OFF Operating mode 4-way valve is Heat, except for defrost ON Cool...
Page 33 - Rotation Regulating Functions; To prevent liquid flood back to the compressor.
Algorithm & Control 25 2.18 Rotation Regulating Functions Upper limit rotation Limit rotation Command rotation Starting rotation ∆ T Defrost* Lower limit rotation Target rotation * Defrost control for heat pump model only 2.18.1 Starting Rotation Starting Control To avoid excessive oil discharge...
Page 34 - • The system is in heating condition
Algorithm & Control 26 2.18.3 Limit Rotation Determine from • Upper limit rotation A minimum value was determined among the upper limits rotation, i.e. protection controls. • Lower limit rotation A maximum value was determined among the lower limits rotation, i.e. protection controls.Generally, ...
Page 36 - Discharge Pipe Temperature Control; will stop and considered trip.; Overall Current Control; considered total current overload.
Algorithm & Control 28 2.22 Discharge Pipe Temperature Control Used as a measure of the compressor’s internal temperature.Compressor frequency is control to keep this temperature from going up further when it rises above a certain level. Discharge temperature Stop zone Drop zone Frequency keep z...
Page 37 - Overall Frequency Control; For Cooling Only Model
Algorithm & Control 29 2.24 Overall Frequency Control The compressor frequency is determined according to the difference between the room thermistor temperature and the target temperature. (*): only for heat pump models Initial frequency PI control Defrost control (*) Lower limit function Four w...
Page 39 - Service Diagnosis; LED blinks here; Operation / Fault Indication
Service Diagnosis 31 3.0 Service Diagnosis 3.1 Error Indication from Indoor 3.1.1 Indoor model FTK(X)N09/12/18/24AX • LED display will either be ON during operation or blinking (blue color) when any error occur as in below table. • The blinking pattern does not indicate error details • The error det...
Page 41 - Error Code retrieved by remote controller; ’’ indication flashes on; Last State Error retrieved by remote controller BRC52A & BRC52B; Operating Guide
Service Diagnosis 33 3.2 Error Code retrieved by remote controller 3.2.1 Remote controller model BRC52A & BRC52B OFF TIMER CANCEL button ON TIMER CANCEL button Mode button ON/OFF button B 2 5 C R B A 2 5 C R B ON TIMER CANCEL button OFF TIMER CANCEL button Operating Guide1. Hold down ON TIMER CA...
Page 42 - Error code description for Inverter; ERROR CODE
Service Diagnosis 34 3.3 Error code description for Inverter No. ERROR CODE ERROR DESCRIPTION RK(X)B09/12/18/24AX RK(X)N09/12/18/24AX 1 00 NORMAL O 2 A1 INDOOR PCB ABNORMALITY O 3 A5 ANTIFREEZE PROTECTION OR HIGH PRESSURE CONTROL O 4 A6 INDOOR FAN MOTOR ABNORMALITY O 5 C4 INDOOR HEAT EXCHANGER THERM...
Page 43 - Description; INDOOR PCB ABNORMALITY; Possible Root; Faulty connector connection at indoor.; Troubleshooting
Service Diagnosis 35 A1 Description INDOOR PCB ABNORMALITY Possible Root cause 1. Faulty indoor PCB. 2. Faulty connector connection at indoor. Troubleshooting No Any sign of loose or abnormal. Yes Turn off unit. Check indoor PCB connector conditions (including PCB to terminal block and all PCB wire ...
Page 44 - ANTIFREEZE PROTECTION OR HIGH PRESSURE CONTROL; Indoor air filter, heat exchanger block due to dust accumulation.
Service Diagnosis 36 A5 Description ANTIFREEZE PROTECTION OR HIGH PRESSURE CONTROL Possible Root cause 1. Indoor air filter, heat exchanger block due to dust accumulation. 2. Indoor air short circuit. 3. Indoor coil thermistor faulty. 4. Indoor PCB faulty. 5. Fan blower dirty. Troubleshooting Any ai...
Page 45 - INDOOR FAN MOTOR ABNORMALITY; Indoor fan motor winding short, or the motor lead wire broken.; INDOOR HEAT EXCHANGER THERMISTOR ABNORMALITY
Service Diagnosis 37 A6 Description INDOOR FAN MOTOR ABNORMALITY Possible Root cause 1. Indoor fan motor winding short, or the motor lead wire broken. 2. Indoor PCB faulty. Troubleshooting Does it rotate? Does it connect properly? No Yes Change fan motor. Check fan motor connector condition. Yes No ...
Page 46 - INDOOR ROOM THERMISTOR ABNORMALITY
Service Diagnosis 38 C9 Description INDOOR ROOM THERMISTOR ABNORMALITY Possible Root cause 1. Thermistor, connector faulty. 2. Indoor PCB faulty. Troubleshooting Yes Normal? No Yes Normal? # Refer thermistor resistance table.(Page 67, item 6.1) Replace PCB. Check thermistor resistance value. Check t...
Page 47 - OUTDOOR PCB ABNORMALITY
Service Diagnosis 39 E1 Description OUTDOOR PCB ABNORMALITY Possible Root cause 1. Micro Controller program run-away due to external factor such as Noise, Momentary voltage drop, Momentary power failure. 2. Damage of EEPROM. 3. Faulty outdoor unit PCB. 4. Broken hardness between PCB. Troubleshooting...
Page 48 - COMPRESSOR OVERLOAD; Electronic expansion valve defective.
Service Diagnosis 40 E5 Description COMPRESSOR OVERLOAD Possible Root cause 1. Refrigerant Shortage. 2. 4 way valve malfunction. 3. Stop valve malfunction. 4. Outdoor unit PCB defective. 5. Water mixed in refrigerant. 6. Electronic expansion valve defective. 7. Disconnection of discharge pipe thermi...
Page 49 - Electronic expansion valve defective.
Service Diagnosis 41 E5 Description COMPRESSOR OVERLOAD Possible Root cause 1. Refrigerant Shortage. 2. 4 way valve malfunction. 3. Electronic expansion valve defective. 4. Outdoor unit PCB defective. 5. Water mixed in refrigerant. Troubleshooting #Compressor winding resistance 1.18 #Refer page 69 i...
Page 51 - OUTDOOR FAN MOTOR LOCK
Service Diagnosis 43 E7 Description OUTDOOR FAN MOTOR LOCK Possible Root cause 1. Fan motor breakdown. 2. Harness or connector disconnected between fan motor and PCB or in poor contact. 3. Foreign matter stuck in fan. 4. Defective outdoor unit PCB. Troubleshooting Turn on the power. Check rotation p...
Page 52 - AC INPUT OVER CURRENT; Over current due to compressor failure.
Service Diagnosis 44 E8 Description AC INPUT OVER CURRENT Possible Root cause 1. Over current due to compressor failure. 2. Over current due to defective outdoor unit PCB. 3. Over current due to defective power transistor. 4. Over current due to short-circuit. Troubleshooting Any abnormal? Compresso...
Page 53 - EA; WAY VALVE ABNORMALITY; Foreign substance mixed in refrigerant.
Service Diagnosis 45 EA Description 4 WAY VALVE ABNORMALITY Possible Root cause 1. Thermistor defective. 2. 4 way valve defective. 3. Outdoor PCB defective. 4. Insufficient gas. 5. Foreign substance mixed in refrigerant. 6. Stop valve defective. 7. Disconnect of 4 way valve coil. Troubleshooting Har...
Page 54 - DISCHARGE PIPE OVERHEAT
Service Diagnosis 46 F3 Description DISCHARGE PIPE OVERHEAT Possible Root cause 1. Refrigerant shortage. 2. Four way valve malfunctioning. 3. Discharge pipe thermistor defective. 4. Outdoor PCB defective. 5. Water mixed in the local piping. 6. EXV defective. 7. Stop Valve defective. Troubleshooting ...
Page 55 - HEAT EXCHANGER OVERHEAT; The installation space is not large enough.
Service Diagnosis 47 F6 Description HEAT EXCHANGER OVERHEAT Possible Root cause 1. The installation space is not large enough. 2. Faulty outdoor fan motor. 3. Faulty EXV. 4. Faulty outdoor heat exchanger thermistor. 5. Faulty stop valve. 6. Dirty heat exchanger. 7. Unit overcharge. 8. Defective outd...
Page 56 - COMPRESSOR SENSOR SYSTEM ABNORMAL
Service Diagnosis 48 H0 (Class 18/24) Description COMPRESSOR SENSOR SYSTEM ABNORMAL Possible Root cause 1. Broken and disconnected harness. 2. Outdoor unit PCB defective. 3. Defective compressor. Troubleshooting # Disconnect the reactor wire and measure resistance between terminal. Any abnormal? Yes...
Page 58 - Input voltage out of specification.
Service Diagnosis 50 H6 (Class 09/12) Description POSITION SENSOR ABNORMAL (COMPRESSOR) Possible Root cause 1. Compressor relay cable disconnected. 2. Compressor itself defective. 3. Outdoor PCB defective. 4. Stop valve closed. 5. Input voltage out of specification. Troubleshooting Normal? Electrica...
Page 59 - Input voltage out of specification
Service Diagnosis 51 H6 (Class 18/24) Description POSITION SENSOR ABNORMAL (COMPRESSOR) Possible Root cause 1. Compressor relay cable disconnected. 2. Compressor itself defective. 3. Outdoor PCB defective. 4. Stop valve closed. 5. Input voltage out of specification Troubleshooting Remark: Refer to A...
Page 60 - AC CURRENT SENSOR ABNORMALITY
Service Diagnosis 52 H8 Description AC CURRENT SENSOR ABNORMALITY Possible Root cause 1. Internal wiring broken. 2. Outdoor unit PCB defective. Troubleshooting *Remark: This error is only applicable for model Class 18/24. Connection correct? No Yes Change outdoor PCB. Restart the system and check co...
Page 61 - Thermistor or related abnormality; OUTDOOR AIR THERMISTOR ABNORMALITY; HEAT SINK THERMISTOR ABNORMALITY; Disconnection of the connector for the thermistor.
Service Diagnosis 53 H9, J3, J6, P4 Description Thermistor or related abnormality H9: OUTDOOR AIR THERMISTOR ABNORMALITY J3: COMPRESSOR DISCHARGE PIPE THERMISTOR ABNORMALITY J6: OUTDOOR HEAT EXCHANGER THERMISTOR ABNORMALITY P4: HEAT SINK THERMISTOR ABNORMALITY Possible Root cause 1. Disconnection of...
Page 62 - ELECTRICAL BOX TEMPERATURE RISE (COMPRESSOR OFF); Fin temperature rise due to defective outdoor unit fan.
Service Diagnosis 54 L3 Description ELECTRICAL BOX TEMPERATURE RISE (COMPRESSOR OFF) Possible Root cause 1. Fin temperature rise due to defective outdoor unit fan. 2. Fin temperature rise due to short circuit. 3. Fin thermistor defective. 4. Connector in poor contact. 5. Outdoor unit PCB defective. ...
Page 63 - Heat sink overheat; Fin temperature rise due to short circuit.
Service Diagnosis 55 L4 Description Heat sink overheat Possible Root cause 1. Fin temperature rise due to short circuit. 2. Fin temperature rise due to defective outdoor unit fan. 3. Fin thermistor defective. 4. Connector in poor contact. 5. Outdoor unit PCB defective. 6. Silicon grease is not appli...
Page 64 - IPM ABNORMALITY
Service Diagnosis 56 L5 Description IPM ABNORMALITY Possible Root cause 1. Over current due to defective power transistor. 2. Over current due to wrong internal wiring. 3. Over current due to abnormal supply voltage. 4. Over current due to defective PCB. 5. Error detection due to defective PCB. 6. O...
Page 65 - INSUFFICIENT GAS; outdoor temperature thermistor.
Service Diagnosis 57 U0 Description INSUFFICIENT GAS Possible Root cause 1. Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger,room or outdoor temperature thermistor. 2. Closed stop valve. 3. Refrigerant shortage (refrigerant leakage). 4. Poor compression performance of...
Page 66 - DC VOLTAGE OUT OF RANGE; Power supply voltage is not as specified.
Service Diagnosis 58 U2 Description DC VOLTAGE OUT OF RANGE Possible Root cause 1. Power supply voltage is not as specified. 2. Defective DC voltage detection circuit. 3. Defective over-voltage detection circuit. 4. Defective PAM control part. 5. Disconnection of compressor harness 6. Short circuit ...
Page 67 - COMMUNICATION ABNORMALITY; wires between the indoor and outdoor units
Service Diagnosis 59 U4 Description COMMUNICATION ABNORMALITY Possible Root cause 1. Faulty outdoor unit PCB. 2. Faulty indoor unit PCB. 3. Indoor unit – outdoor unit signal transmission error due to wiring error. 4. Indoor unit – outdoor unit signal transmission error due to disturbed power supply ...
Page 68 - INSTALLATION ABNORMALITY; Wrong outdoor unit PCB mounted or defective.
Service Diagnosis 60 UA Description INSTALLATION ABNORMALITY Possible Root cause 1. Wrong models interconnected. 2. Wrong indoor unit PCB mounted. 3. Indoor unit PCB defective. 4. Wrong outdoor unit PCB mounted or defective. Troubleshooting OK? No Yes Are the connecting wires connected properly? Yes...
Page 69 - Wiring Connection
Wiring Connection 61 4.0 Wiring Connection Model: FTKB09/12AX-RKB09/12AX ; FTKN09/12AX-RKN09/12AX 1 2 SIG L 1 L 2 GR L N E POWER SUPPLY 208/230V/1Ph/60Hz
Page 73 - Refrigerant Diagram
Refrigeramt Diagram 65 5.0 Refrigerant Diagram Model: FTKB09/12AX - RKB09/12AX , FTKN09/12AX - RKN09/12AX Model: FTKB18/24AX - RKB18/24AX , FTKN18/24AX - RKN18/24AX
Page 75 - Thermistor resistance checking procedures; Resistance value refer to Resistance table below.
Refrigeramt Diagram 67 6.0 Appendix A : 6.1 Thermistor resistance checking procedures Remove the connectors of thermistors at PCB and measure resistance of each thermistor using tester as shown below. Tester Resistance range Resistance value refer to Resistance table below. Class 09/12/18/24 Indoor ...
Page 77 - a. Check if the EXV connector is correctly connected to PCB.; Four way valve performance checking procedures
Refrigeramt Diagram 69 6.2 Electronic Expansion Valve (EXV) checking procedures a. Check if the EXV connector is correctly connected to PCB. b. Turn power off and on again, and check if EXV generates a latching sound. c. If the EXV does not generate a latching sound in above step b., disconnect conn...
Page 78 - Inverter unit refrigerant check procedures
Refrigerant Diagram 70 6.3.2 Class 18/24 Turn power off and then on again. Disconnect four way valve coil from connector and check the continuity. Start heating operation. Replace four way valve. S80 voltage at 220-240VAC with compressor on? Four way valve coil resistance at Yes Yes Replace outdoor ...
Page 79 - Rotation pulse check on outdoor unit PCB; Installation condition check
Refrigeramt Diagram 71 6.5 Rotation pulse check on outdoor unit PCB Make sure that the voltage of 320 ± 30 V is applied.1. Set operation off and power off. Disconnect the connector S71.2. Check that the voltage between the pins 4 & 7 is 320 VDC.3. Check that the control voltage between the pins ...
Page 80 - Outdoor fan system check; DC motor; Diode bridge short circuit check procedures; volt before checking power transistor.; several MΩ
Refrigerant Diagram 72 6.7 Outdoor fan system check Outdoor fan running? No DC motor Yes No Fan motor lead wire connector disconnected? Refer to Appendix A Rotation pulse check on outdoor unit PCB. Outdoor fan system is functioning. Yes Check the outdoor fan system. Reconnect the connector. Refer Pa...
Page 81 - Multimeter; Power supply waveforms check procedures; check the waveform disturbance with oscilloscope.
Refrigeramt Diagram 73 4 + 3 ~ 2 ~ 1 – Multimeter 6.9 Power supply waveforms check procedures Measure the power supply waveform between No. 1(Live) and No. 2(Neutral) on the terminal board, and check the waveform disturbance with oscilloscope. • Check if the power supply waveform is a sine wave (Fig...
Page 82 - Trial Operation and Field Settings
Refrigerant Diagram 74 6.10 Trial Operation and Field Settings 6.10.1 Tips for Servicing 6.10.1.1 Pump Down Operation In order to protect the environment, be sure to conduct pump down operation when relocating or disposing of the unit. <Details> 1. Remove the valve caps from the liquid stop va...
Page 83 - such as louver movement, are working properly.
Refrigeramt Diagram 75 6.10.2 Trial Operation 1. Measure the supply voltage and make sure that it falls within the specified range. 2. Trial operation should be carried out in either cooling or heating operation. 3. Carry out the trial operation in accordance with the operation manual to ensure that...
Page 84 - Cautions on product corrosion
Warning Cautions on product corrosion 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to insta...