Page 2 - LR
Daikin Europ e N.V . CE - DECLARA TION-OF-CONF O RMIT Y CE - KONFORM ITÄTSE RKLÄRUNG CE - DECLARA TION-DE-CONF O RMIT E CE - CONFORM ITEIT SVERKL ARING CE - DECLARACION-DE-CONFORMIDAD CE - DICHIARAZI O NE -DI-CONFORMIT A CE - ΔHΛΩΣ Η ΣΥ Μ ΜΟΡΦΩ ΣΗΣ CE - DECL ARAÇÃO-DE-CONFORM IDADE CE - ЗАЯВ ЛЕНИЕ-О...
Page 4 - CONTENTS; -1 Safety Precautions; WARNING; Installation manual
Installation manual 1 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 CONTENTS 1. FIRST OF ALL ......................................................................... 1 1-1 Safety Precautions............................................................ 11-2 Special Notice of Product ...................
Page 5 - DANGER: RISK OF EXPLOSION; -2 Special Notice of Product; CAUTION
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 2 • Do not allow children to climb on the outside unit and avoid placing objects on the unit. Injury may result if the unit becomes loose and falls. • Be sure to earth the CONVENI-PACK. Do not earth the unit to a utility pipe, lightn...
Page 6 - To fix the fluorinated greenhouse gases label; -3 Disposal Requirements; BEFORE INSTALLATION; -1 Standard Supplied Accessories; Note; -2 Example of System Configuration; RXXX
Installation manual 3 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Important information regarding the refrigerant usedThis product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.Refrigerant type: R410AGlobal warming potential (GWP) value: 2087.5 To fix the fluorinate...
Page 7 - -3 Indoor Unit Constraints (Refrigeration and; Restrictions; SELECTION OF LOCATION; Installation Space Examples; Capacity class; When installed as a single unit
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 4 1 Manuals and labels 2 Accessory pipes (Installed on bottom frame) 2-3 Indoor Unit Constraints (Refrigeration and Freezer) • The design pressure for the indoor unit is 2.5 MPa or more.• Install an R410A expansion valve on each indo...
Page 8 - • Ensure the base is high enough that intakes are not clogged by; HANDLING THE UNIT; Decide on the transportation route.
Installation manual 5 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 CAUTION 1. An inverter CONVENI-PACK may cause electronic noise gener-ated from AM broadcasting. Examine where to install the main CONVENI-PACK and electric wires, keeping proper distances away from stereo equipment, personal comput...
Page 9 - PLACING THE UNIT; REFRIGERANT PIPING; To Piping Work Contractors
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 6 5. PLACING THE UNIT • Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise. • The base should be bigger around than the width of the unit’s legs (66 mm), and should support the unit.If ...
Page 10 - -1 Selection of Piping Material and Size; • Use the following type of refrigerant piping.
Installation manual 7 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 6-1 Selection of Piping Material and Size • Make sure that the inner side and outer side of the piping used is clean and free of contaminants, such as sulphur, oxide, dust, chips, oil and fat, and water. It is desirable that the ma...
Page 11 - -2 Selection of Refrigerant Branching
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 8 6-2 Selection of Refrigerant Branching When selecting refrigerant branching, follow the rules outlined below. Allowed refrigerant branch kits A: Choose the refnet joint so that incoming and outgoing piping diam-eters (refer to 6-1 ...
Page 12 - Precautions when knocking out knock holes
Installation manual 9 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 1. Directions to bring out the pipesThe local interunit piping can be connected either forward or to the sides (taken out through the bottom) as shown in the following figure.When passing out through the bottom, use the knock hole ...
Page 15 - Expansion Valve Selection; To Electric Engineering Contractors
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 12 7. Expansion Valve Selection This model has a larger degree of subcooling (subcooling ratio= condensing temperature - liquid refrigerant temperature at outdoor unit outlet) for the liquid refrigerant of a refrigerator than that of...
Page 16 - -1 Example of Wiring Entire System; • Be sure to connect the power wiring to the power wiring terminal; -2 To Open the Electrical Component Box of the; Capacity for operation output : 0.5A or less at AC 220 to 240V.
Installation manual 13 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 8-1 Example of Wiring Entire System Note • Use conduit for power supply wiring.• Make sure the weak electric wiring (i.e. for the remote controller, between units, etc.) and the power wiring do not pass near each other, keeping th...
Page 17 - -3 Procedure for Incoming Wiring; -4 Procedure for Power Supply Wiring; Procedure for Power Supply Wiring
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 14 Note When closing the unit the electrical component box cover, make sure that the sealing material on the lower back side of the cover is not caught and bend towards the inside. 1 Electrical component box cover2 Front side3 Power ...
Page 18 - Operation output wiring connections
Installation manual 15 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Point for attention regarding quality of the public electric power supply This equipment complies with respectively: EN/IEC61000-3-11 (1) provided that the system impedance Z sys is less than or equal to Z max and EN/IEC61000-...
Page 19 - -5 Procedure for Wiring Inside Units; When routing high-voltage wiring (power supply wiring, earth; INSPECTION AND PIPE INSULATION; • Vacuum drying
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 16 • Do not finish strand wire with solder. 8-5 Procedure for Wiring Inside Units • Referring to the following figure, secure and wire the power and transmission wiring using clamps. • Lay the ground wire so that it will not come in ...
Page 20 - -2 Thermal Insulation Work; -3 Checking of Device and Installation Conditions; Insulation material
Installation manual 17 LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 *2 Refer to the instruction label on the front panel of the outdoor unit (below) for the position of the service port. CAUTION • Conduct an airtight test and vacuum drying precisely through the service ports of both liquid and gas...
Page 21 - CHECKS AFTER WORK COMPLETION; Control box; RUN switch; DO NOT MOVE; ON
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 18 10. CHECKS AFTER WORK COMPLETION • Make sure the following works are complete in accordance with the installation manual. Piping work Wiring work Air tight test/Vacuum drying Installation work for indoor unit Installatio...
Page 23 - MAINTENANCE AND SERVICE; • This product must fill the refrigerant in the field.
LRYEQ16A7Y1 CONVENI-PACK 4P448939-1A – 2016.07 Installation manual 20 *1Set the operating switch to the "OFF" position to reset the power sup-ply and then return the switch to the "ON" position to restart the unit. If the problem persists, refer to the Service Manual. • If you have c...