Page 2 - BuIldINg OWNERS; BENEFITS FOR; ENd uSERS; BENEFITS FOR; CONSulTANT; BENEFITS FOR; INSTAllERS
BENEFITS FOR BuIldINg OWNERS With daikin’s proprietary inverter technology and cutting-edge control technology for refrigerant, the VrV ® iii air conditioning system operates with outstanding efficiency. this contributes to high energy savings, which gREATlY REduCES YOuR RuNNINg COSTS and facilitate...
Page 3 - TABlE OF CONTENTS
TABlE OF CONTENTS VrV ® an energy effiCient approaCh 5 oVer 25 years of VrV ® history 6 What is hi-VrV ® ? 8 WhiCh VrV ® outdoor system offers me the best soLution? 10 · air cooled outdoor systems 10 · Water cooled outdoor systems 11 oVerVieW outdoor unit range 12 oVerVieW indoor unit range 14 oVerV...
Page 4 - ABOuT dAIKIN; Daikin quality; optimum; possible in the most extreme climates.; energy saving; features and improved
ABOuT dAIKIN daikin has a worldwide reputation based on almost 85 years’ experience in the successful manufacture of high quality air conditioning equipment for industrial, commercial and residential use. Daikin quality daikin’s much envied quality quite simply stems from the close attention paid to...
Page 5 - With the environment in mind; V R V
Widely acknowledged as the most advanced system of its type on the market, VrV ® represents a powerful combination of advanced inverter and heat pump technologies. as a reverse cycle heat pump, it can provide a complete indoor environment obviating the need for a separate heating system and offering...
Page 7 - geothermal
daikin has extended the operational scope of its acclaimed VrV ® ii inverter driven dx air conditioning system, with a new water cooled version, VRV ® -WII. available in 10, 20 and 30hp models, the system operates on r-410a refrigerant and is available in both heat pump and heat recovery versions. 2...
Page 8 - AIR CONDITIONING; system meets
VRV ® AIR CONDITIONING CONTROL AND MANAGEMENT WhAT IS ? in recent years, design styles for intelligent buildings such as hotels, banks and offices etc. have increasingly featured large areas of glazing with attendant high solar heat gains that can only be dissipated by means of air conditioning. not...
Page 10 - AIR COOlEd; OFFERS ME ThE BEST SOluTION?
for simultaneous heating and cooling from one system › heat exhausted from indoor units in the cooling cycle is merely transferred to › units in areas requiring heat, maximising energy efficiency, reducing electricity costs and leading to high partload efficiencies (up to 9 1 ). operation range in c...
Page 11 - Compact design and stacked configuration possible.
WATER COOlEd OuTdOOR SYSTEMS allows heat recovery within the total building, thanks to the storage of energy in the water circuit. › Compact design and stacked configuration possible. › suitable for multi-storey and large buildings because of the hardly unlimited possibilities of water piping. › gEO...
Page 12 - OVERVIEW OuTdOOR uNIT RANgE; IR; NEW
OVERVIEW OuTdOOR uNIT RANgE Capacity (HP) System Type Product name 4 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 A IR COO l E d H EAT RECOVER y REyHQ-P High COP combination REyQ-P8/P9 Small footprint combination H EAT P u MP RXyHQ-P8 High COP combination RTSyQ-P Heat p...
Page 14 - OVERVIEW INdOOR uNIT RANgE; VrV; 6 different indoor unit models in a total of 110 variations.
OVERVIEW INdOOR uNIT RANgE VrV ® air conditioning brings summer freshness and winter warmth to offices, hotels, department stores and many other commercial premises. it enhances the indoor environment and creates a basis for increased business prosperity and whatever the air conditioning requirement...
Page 16 - OVERVIEW VENTIlATION RANgE
OVERVIEW VENTIlATION RANgE Air flow rate (m 3 /h) Type name Components of indoor air quality 0 200 400 600 800 1,000 1,500 2,000 5,000 10,000 15,000 HEAT RECLAIM VENTILATION 1 VAM-fA 1 Ventila tion VKM-GM 1 Ventila tion2 Humidification3 Air processing VKM-G 1 Ventila tion3 Air processing OuTDOOR AIR...
Page 17 - OVERVIEW NETWORK SOluTIONS
OVERVIEW NETWORK SOluTIONS Basic control functions: ON/OFF, temp. Setting, air flow settings Automatic changeover Weekly schedule control Fire emergency stop control Basic monitoring functions: ON/OFF status, operation mode, set point temp. Indication filter replacement Malfunction code Password sec...
Page 18 - POWERFul SElECTION PROgRAMMES; dESIgN TOOl
POWERFul SElECTION PROgRAMMES 1. VRV ® PRO, dESIgN TOOl fEATuRES: the VrV ® pro selection programme is a true VrV ® design tool. the programme enables VrV ® air conditioning systems to be engineered in a precise and economical way, taking into account the complex piping rules. moreover, it ensures o...
Page 19 - quICK quOTATION TOOl
2. VRV ® XPRESS, quICK quOTATION TOOl VrV ® Xpress is a software tool that allows creating on the spot quotations for a daikin VrV ® system. it provides a result in 7 steps to enable a professional budget quotation: 1. select indoor units2. Connect outdoor units to indoor units3. automatic generatio...
Page 20 - OuTdOOR SYSTEMS; SOPhISTICATEd ANd VERSATIlE
AIR COOlEd VRV ® OuTdOOR SYSTEMS air cooled VrV ® air conditioning was introduced to europe by daikin in 1987 and since then has undergone considerable development in performance, capacity, energy efficiency and environmental acceptability. internationally regarded as one of the most SOPhISTICATEd A...
Page 22 - INVERTER TECHNOLOGy; the linear VrV
BENEFITS FOR BuIldINg OWNERS INVERTER TECHNOLOGy the linear VrV ® system makes use of a variable proportional integral (pi) control system which uses refrigerant pressure sensors to give added control over inverter and on/off control compressors in order to abbreviate control steps into smaller unit...
Page 23 - LESS fREQuENT START/STOP CyCLE; the technique adopted by daikin, of regulating the capacity using; ONLy bRAzED CONNECTIONS; ROHS COMPLIANCE; will be totally in line with rohs.
Frequency 30 116 30+on 116+on Capacity 50% 60% 55% 65% LESS fREQuENT START/STOP CyCLE the technique adopted by daikin, of regulating the capacity using › multiple compressors clearly results in minimum switching losses and power surges because of the overlap in capacity and frequency.since daikin ut...
Page 24 - Improvement in corrosion resistance; 6 hours humidity cycle test kfW; ANTI CORROSION TREATMENT
Heat exchanger An anti-corrosion heat exchanger cutaway view Aluminium Hydrophilic film Corrosion-resistant Acrylic resin Improvement in corrosion resistance Performed tests: Vda Wechseltest Contents of 1 cycle (7 days): 24 hours salt spray test ss din 50021 › 96 hours humidity cycle test kfW › din ...
Page 25 - WIDE OPERATION RANGE; the VrV
BENEFITS FOR dESIgN OFFICES ANd CONSulTANTS WIDE OPERATION RANGE the VrV ® system can be installed practically anywhere. advanced pi control of the outdoor unit enables VrV ® series to operate at outdoor ambients up to 43°C (VrV ® iii-s up to 46°C) in cooling mode and down to -20°C (VrV ® iii-C down...
Page 26 - Typical hotel application; TV; MuLTI TENANT fuNCTION; this function ensures that the entire VrV; NO STRuCTuRAL REINfORCEMENT NECESSARy
hoLder 220 V Typical hotel application power off Card Card Card TV TV TV MuLTI TENANT fuNCTION this function ensures that the entire VrV ® system does not shut down when the main power supply of an indoor is switched off. this means that the indoor unit’s main fuse can be turned off when leaving a h...
Page 27 - REfRIGERANT CONTAINMENT CHECK; SHORT INSTALLATION TIME
BENEFITS FOR INSTAllERS REfRIGERANT CONTAINMENT CHECK 1 the refrigerant volume of the complete system is calculated from the following data: outdoor temperature › reference system temperatures › reference pressure temperatures › refrigerant density › types and number of indoor units › When activatin...
Page 28 - AuTOMATIC CHARGE fuNCTION; uNIfIED REfNET PIPING; -way piping connection; AuTOMATIC TEST
AuTOMATIC CHARGE fuNCTION Conventional Way: 1. calculation of additional refrigerant charging volume 2. charging the unit with additional refrigerant 3. measuring the weight of the cylinder 4. judgment based on pressure (test operation) VRV ® With VrV ® however, these 4 steps are omitted since the V...
Page 29 - “SuPER WIRING” SySTEM; the cross wiring check facility available on the VrV; MODuLAR DESIGN
“SuPER WIRING” SySTEM Simplified wiring a super Wiring system is used to enable the shared use of wiring between indoor units, outdoor units and the centralised remote control. this system makes it easy for the user to retrofit the existing system with a centralised remote control, simply by connect...
Page 30 - SMART CONTROL bRINGS COMfORT; system thus maintains comfortable; LOW INDOOR uNIT OPERATION SOuND LEVEL; Continuous research by daikin into reducing operation
SMART CONTROL bRINGS COMfORT an electronic expansion valve, using pid control, continuously adjusts the refrigerant volume in respond to load variations of the indoor units. the VrV ® system thus maintains comfortable room temperatures at a virtually constant level, without the temperature variation...
Page 31 - with low sound level at night:; Mode 1 Automatic mode; SILENT MODE
— — — Soundlevel 5HP 8HP 10HP 12HP 14HP 16HP 18HP Step 1 50dB Capacity (kW) 14.7 19.9 19.9 20.9 19.9 20.1 20.2 100% 98% 78% 69% 55% 49% 44% Step 2 45dB Capacity (kW) 11.9 15.1 15.1 15.6 15.5 15.6 15.6 93% 74% 59% 51% 43% 38% 34% Peak in the outdoor temperature Peak in the outdoor temperature Night m...
Page 32 - The motor comprises powerful neodymium magnets; AdVANCEd
1 2 SINE WAVE DC INVERTER optimizing the sine wave curve, results in smoother motor rotation and improved motor efficiency. RELuCTANCE bRuSHLESS DC COMPRESSOR the reluctance brushless dC motor provides significant increases in › efficiency compared to conventional aC inverter motors, simultaneously ...
Page 33 - maximum 10 % increase in airflow (16hp) due to dual dC fans; E-PASS HEAT EXCHANGER
3 4 5 6 DC fan motor structure DC fAN MOTOR the use of a dC fan motor offers substantial improvements in operating efficiency compared to conventional aC motors, especially during low speed rotation. DuAL DC fANS 1 maximum 10 % increase in airflow (16hp) due to dual dC fans › increased output and re...
Page 34 - hIgh COP ANd SMAll FOOTPRINT COMBINATION; BENEfITS; TOP ENERGy EffICIENCy
VRV ® hEAT RECOVERY hIgh COP ANd SMAll FOOTPRINT COMBINATION BENEfITS › TOP ENERGy EffICIENCy the high Cop combination has a top energy efficiency within the daikin heat recovery range. it is up to 11% more efficient, compared to the small footprint combination. HP 16 20 22 24 High COP combination c...
Page 35 - CONTINuOuS HEATING DuRING DEfROST; ensuring the highest comfort level during defrost and oil return; benefits of the system; high comfort
VRV ® II Heat recovery VRV ® III Heat recovery CONTINuOuS HEATING DuRING DEfROST ensuring the highest comfort level during defrost and oil return benefits of the system high comfort › no cold draft during defrost & oil return - no big temperature fluctuations in the room -higher integrated heati...
Page 36 - fLEXIbLE PIPING DESIGN; With the VrV; IMPROVED COMfORT THANKS TO VRV
fLEXIbLE PIPING DESIGN VrV ® offers an extended piping length of 165m (190m equivalent piping length) with a total system piping length of 1,000m. in case the outdoor unit is located above the indoor unit the height difference is 50m standard. it can be extended to 90m*.in case the outdoor unit is l...
Page 37 - SPECIfICATIONS
VRV ® Heat recovery - High COP combination SPECIfICATIONS › REYHQ-P 16 20 22 24 Outdoor unit REMQ8P9 REMQ8P9 REMQ10P8 REMHQ12P8 REMQ8P9 REMHQ12P8 REMHQ12P8 REMHQ12P8 Nominal capacity cooling kW 45.0 56.0 61.5 67.0 heating kW 50.0 62.5 69.0 75.0 COP heating 4.36 4.36 4.24 4.37 EER cooling 4.29 4.04 3...
Page 39 - bS box for heat recovery system
bS box for heat recovery system REYQ-P8/P9 30 32 34 36 38 40 42 44 46 48 Modules REYQ8P9REYQ10P8REYQ12P9REYQ14P8REYQ16P8 Modules REMQ8P9 1 1 REMQ10P8 1 1 1 REMQ12P8 1 1 2 1 REMQ14P8 1 1 REMQ16P8 1 2 1 1 1 1 2 2 2 3 Number of outdoor units 2 2 3 3 3 3 3 3 3 3 Nominal capacity cooling kW 85.0 90.0 95....
Page 40 - ACCESSORIES
ACCESSORIES › notes: 1 all options are kits 2 Central drain pan kit shall be combined based on the outdoor multi connection table 3 only 1 option per installation is needed 4 only available for standard bsVQ boxes (not possible for central bsVQ). allows to reduce operating sound of bsVQ box (require...
Page 42 - hIgh COP COMBINATION
VRV ® hEAT PuMP hIgh COP COMBINATION BENEfITS › TOP ENERGy EffICIENCy the high Cop combination has a top energy efficiency within the daikin heat pump range. it is up to 16% more efficient.compared to the small footprint combination. fLEXIbLE PIPING DESIGN VrV ® iii offers an extended piping length ...
Page 46 - HIGH COP AT LOW AMbIENTS; WIDE HEATING OPERATION RANGE; STAbLE HEATING CAPACITy
VRV ® hEAT PuMP OPTIMISEd FOR hEATINg (VRV ® III-C) BENEfITS › HIGH COP AT LOW AMbIENTS the use of two stage compression technology results in improved energy saving performance at low ambients, with a Cop of more than 3.0 at -10°C outdoor ambient. annual power costs are therefore, considerably lowe...
Page 47 - HIGH HEAT uP SPEED; SHORT DEfROST TIME
35 30 25 20 15 60 50 40 30 20 10 0 -10 -20 °C positie blauwe lijnen:X +10 -5 0 5 6 10 14 15 20 HIGH HEAT uP SPEED heat up time is dramatically reduced, particularly under low ambient conditions. the required time for discharge temperature to reach 40°C has been reduced by 50%. Indoor heat exchanger ...
Page 48 - uNIQuE TECHNOLOGIES; TWO STAGE COMPRESSION
uNIQuE TECHNOLOGIES › TWO STAGE COMPRESSION two stage compression technology enables the system to create higher pressures resulting in a higher heating capacity under low ambient conditions.the second inverter compressor (located in the function unit) is specially designed to provide higher pressur...
Page 50 - SMAll FOOTPRINT COMBINATION; COMPACT COMbINATIONS PROVIDE THE SMALLEST fOOTPRINT; less space needed
SMAll FOOTPRINT COMBINATION BENEfITS › COMPACT COMbINATIONS PROVIDE THE SMALLEST fOOTPRINT Compact combinations from 5 to 54 hp provide the smallest footprint. up to 33% less installation space needed compared to the high Cop combination. fLEXIbLE PIPING DESIGN VrV ® offers an extended piping length...
Page 55 - CONNECTAbLE INDOOR uNITS
CONNECTAbLE INDOOR uNITS VRV ® hEAT PuMP WITh CONNECTION TO STYlISh INdOOR uNITS BENEfITS › VrV ® technology combined with the stylish and silent indoor units. ideal for luxery hotels or spaces where you want to add a stylish touch to the indoor environment.Via the bp box (bpmks967b2/b3) up to 29 in...
Page 56 - bP box for connection to stylish indoor units
SPECIfICATIONS › VRV ® Heat pump with connection to stylish indoor units RXYQ-PR 8 10 12 14 16 18 Nominal capacity cooling kW 22.4 28.0 33.5 40.0 45.0 49.0 heating kW 25.0 31.5 37.5 45.0 50.0 56.5 Capacity range HP 8 10 12 14 16 18 Max n° of indoor units to be connected 13 16 19 23 26 29 Indoor inde...
Page 57 - PIPING DESIGN; the VrV; minimum length
1 all options are kits2 Central drain pan kit shall be combined based on the outdoor unit combination table3 only 1 option per installation is needed4 1 option per module is required5 the option should be installed inside the outdoor unit, only needed in case outdoor unit is installed above indoor V...
Page 59 - HIGH COP VALuES; a major feature of VrV; SPACE SAVING DESIGN; the VrViii
VRV ® III-S hEAT PuMP BENEfITS › 1 nominal cooling capacities are based on: indoor temperature: 27°Cdb, 19°CWb, outdoor temperature: 35°C, equivalent refrigerant piping: 5m, level difference: 0m. 2 nominal heating capacities are based on: indoor temperature: 20°Cdb, outdoor temperature: 7°Cdb, 6°CWb...
Page 60 - SuPER AERO GRILLE; ADVANCED TECHNOLOGIES
2 1 3 SMOOTH AIR INLET bELL MOuTH AND AERO SPIRAL fAN these features assist in significantly reducing noise. guides are added to the bell mouth intake to reduce turbulence in the air flow generated by fan suction. the aero spiral fan features fan blades with bent blade edges, further reducing turbul...
Page 62 - , there are some applications; MulTI STOREY hIgh RISE COMPlEXES; in which maximum refrigerant pipe distances can; gEOThERMAl
WATER COOlEd VRV ® OuTdOOR SYSTEMS despite the remarkable energy efficiency and installation flexibility of the air cooled VrV ® , there are some applications for which the water cooled version provides a more economic and sustainable solution. these apply primarily to MulTI STOREY hIgh RISE COMPlEX...
Page 64 - BENEFITS; HIGH ENERGy EffICIENCIES RESuLTS fROM 2-STAGE HEAT RECOVERy; Heat recovery also available on heat pump units; stage 2
BENEFITS HIGH ENERGy EffICIENCIES RESuLTS fROM 2-STAGE HEAT RECOVERy VrV ® -W benefits from a 2-stage heat recovery facility. the first stage is achieved within the refrigerant system and applies to heat recovery units only. heat exhausted from indoor units in cooling mode is merely transferred to u...
Page 65 - Heat recovery between indoor units
Stage 1: for heat recovery Simultaneous heating and cooling within the refrigerant system. When mainly cooling is required, the system recycles heat exhausted from the cooling operation for heating purposes.When mainly heating is required, the system uses cooled post-heating operation refrigerant fo...
Page 66 - flexible water piping; Water cooled VrV; Long refrigerant piping length; -W outdoor unit is above the indoor units) in; STACKED CONfIGuRATION
fLEXIbLE PIPING DESIGN flexible water piping Water cooled VrV ® uses water as its heat source, so it is optimal for large buildings, including tall, multi-storey buildings, because the system can tolerate water pressure of up to 1.96 mpa. furthermore, if the currently installed heat source’s water t...
Page 67 - Daikin indoor units
Water pipingRefrigerant piping WIDE OPERATION RANGE standard water cooled outdoor units have a wide operation range of between 10°C & 45°C inlet water temperature, both in heating and cooling. for the geothermal series the operation range is extended even more, down to -10°C* in heating and 5°C ...
Page 68 - RELuCTANCE bRuSHLESS DC COMPRESSOR; The motor comprises powerful neodymium magnets; SINE WAVE DC INVERTER; improved motor efficiency.
1 2 3 “Normal” torqueReluctance torque Rotating Stator field Iron Neodymium Magnet Low pressure side High pressure side Suction Scroll Discharge ReluctanceDC Motor 8:00 12:00 16:00 20:00 Time Power consumption (KVV) AdVANCEd WATER COOlEd VRV ® TEChNOlOgIES RELuCTANCE bRuSHLESS DC COMPRESSOR the relu...
Page 69 - With the VrV
IMPROVED COMfORT THANKS TO VRV ® III bS bOX individual change over from cooling to heating or vice versa of the indoor units is possible. this means that all indoor units who do not change over continue to provide optimum comfort for the users during this process. VRV ® WII When switching from cooli...
Page 70 - STANdARd SERIES
VRV ® -W Heat recovery - Standard series BS BOX BSVQ100P8B BSVQ160P8B BSVQ250P8B Total capacity of connectable indoor units x ≤ 100 100 < x ≤ 160 160 < x ≤ 250 Maximum number of connectable indoor units 5 8 5 Casing galvanised steel plate Dimensions HxWxD mm 207x388x326 Weight kg 14 14 15 Pipi...
Page 73 - gEOThERMAl SERIES; HEATING WITH GROuND SOuRCED WATER AS A RENEWAbLE ENERGy SOuRCE; EXTENDED OPERATION RANGE
gEOThERMAl SERIES BENEfITS › HEATING WITH GROuND SOuRCED WATER AS A RENEWAbLE ENERGy SOuRCE this water cooled system uses the renewable energy from ground water, water from lakes, rivers, …because the temperature of for example ground water remains relatively constant during the year, this systems h...
Page 76 - INdOOR uNITS; heat pump; NO lESS
INdOOR uNITS as many as 64 separate indoor units can be operated from the single refrigerant circuit of a 54 hp VrV ® heat pump system. in fact, the daikin VrV ® indoor unit range, one of the widest on the market, currently comprises NO lESS ThAN 26 dIFFERENT STYlISh ANd ElEgANT MOdElS IN 110 dIFFER...
Page 78 - 60° air discharge ensures uniform air flow and temperature; flexible installation and Easy maintenance; reduced installation height: 214mm for class 20-63; Examples of
FXFq-P8 ROuNd FlOW CEIlINg MOuNTEd CASSETTE Comfort & Efficiency 360° air discharge ensures uniform air flow and temperature › distributionair discharge from the corners avoids dead zones that may be subject › to temperature differences modern style decoration panel is available in 2 variations:...
Page 82 - Compact casing (575mm in width and depth) enables unit to fit
FXZq-M9 4-WAY BlOW CEIlINg MOuNTEd CASSETTE 600 X 600MM Comfort & Efficiency modern style decoration panel in white (raL9010) › the use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency and very low sound levelhome leave operation saves energy d...
Page 88 - flexible installation; Compact dimensions, can easily be mounted in a narrow ceiling void
FXKq-MA CEIlINg MOuNTEd CORNER CASSETTE Comfort & Efficiency the use of inverter type outdoor units results in an air conditioning › system with a high energy efficiencyhome leave operation saves energy during absence › Comfortable horizontal air discharge ensures draughtfree operation › and pre...
Page 90 - designed for hotel bedrooms; filter; supply of clean air; flexible Installation; for easy mounting, the drain pan can be located to the left or the
FXdq-M9 SMAll CONCEAlEd CEIlINg uNIT Comfort & Efficiency designed for hotel bedrooms › blends unobtrusively with any interior décor: only the suction and › discharge grilles are visible the use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency ...
Page 92 - mounted in a ceiling void
FdBq-B 25 SMAll CONCEAlEd CEIlINg uNIT Comfort & Efficiency designed for hotel bedrooms › blends unobtrusively with any interior décor: only the suction and › discharge grilles are visiblethe use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency...
Page 94 - Compact dimensions, can easily be mounted in a ceiling void of only
FXdq-PB SlIM CONCEAlEd CEIlINg uNIT Comfort & Efficiency blends unobtrusively with any interior décor: only the suction and › discharge grilles are visiblethe use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency and very low sound levelhome lea...
Page 98 - powerful mode can be selected for rapid cooling or heating; steady supply of clean air
FdXS-E/C 25-35-50-60 SlIM CONCEAlEd CEIlINg uNIT Comfort & Efficiency blends unobtrusively with any interior décor: only the suction and › discharge grilles are visiblethe use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency and very low sound ...
Page 100 - reduction of power consumption of 20% (compared to previous; allows multi tenant applications (option pCb required)
FXSq-P INVERTER dRIVEN CONCEAlEd CEIlINg uNIT Comfort & Efficiency reduction of power consumption of 20% (compared to previous › series) through use of new dC fan improved comfort thanks to 3-step airflow control › blends unobtrusively with any interior décor: only the suction and › discharge gr...
Page 102 - maximum external static pressure (esp) is 100pa
FBq-C 35-50-60 INVERTER dRIVEN CONCEAlEd CEIlINg uNIT Comfort & Efficiency reduction in power consumption thanks to dC inverter fans › improved comfort thanks to 3-step airflow control › blends unobtrusively with any interior décor: only the suction and › discharge grilles are visiblethe use of ...
Page 108 - WAll MOuNTEd uNIT; Can be installed in both new and existing buildings
FXAq-MV 20-25-32-40-50-63 20-25-32-40-50-63 10° 70° 10° 25° 40° 55° 70° 10° Cooling 70° Heating 10° Cooling 70° Heating 10° 70° 10° 25° 40° 55° 70° WAll MOuNTEd uNIT Comfort & Efficiency Vertical auto-swing function moves the discharge flaps up and down › for efficient air distribution throughou...
Page 110 - Design; movement sensor saves power consumption in unoccupied rooms
FTXg-E/ CTXg-E 25-35-50 WAll MOuNTEd uNIT Design good design award: unique evaluation criterion for industrial design › in Japan available in 2 colour variations › Comfort & Efficiency movement sensor saves power consumption in unoccupied rooms › night set mode saves energy by preventing overcoo...
Page 112 - energy saving during standby mode: reduction of energy from
FTXS-g 20-25-35-42-50 WAll MOuNTEd uNIT Comfort & Efficiency energy saving during standby mode: reduction of energy from › 10W to 2W Weekly timer: allows to program the unit on a weekly basis › night set mode saves energy by preventing overcooling or › overheating during night time 2 area intell...
Page 116 - CEIlINg SuSPENdEd uNIT; Wider air discharge thanks to Coanda effect: up to 100 degrees; flexible installation & Easy maintenance; Can be installed in both new and existing buildings.
FXhq-MA 32-63-100 CEIlINg SuSPENdEd uNIT Comfort & Efficiency Wider air discharge thanks to Coanda effect: up to 100 degrees › the use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency home leave operation saves energy during absence › flexible ...
Page 120 - air can be discharged in any of 4 directions
FXuq-MA 71-100-125 Examples of Airflow Patterns 4-WAY BlOW CEIlINg SuSPENdEd uNIT Comfort & Efficiency air can be discharged in any of 4 directions › the use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency home leave operation saves energy dur...
Page 122 - FlOOR STANdINg uNIT; Comfort; ideal for installation beneath a window; requires very little installation space, only 222 mm deep and
FXlq-MA 20-25-32-40-50-63 FlOOR STANdINg uNIT Comfort ideal for installation beneath a window › the use of inverter type outdoor units results in an air conditioning › system with a high energy efficiency home leave operation saves energy during absence › flexible Installation requires very little i...
Page 124 - ideal for installation below a window
FXNq-MA 20-25-32-40-50-63 CONCEAlEd FlOOR STANdINg uNIT Comfort ideal for installation below a window › blends unobstrusively with any interior decor: only the suction and › discharge grilles are visiblethe use of inverter type outdoor units results in an air conditioning › system with a high energy...
Page 128 - FlEXI TYPE uNIT; night set mode saves energy by preventing overcooling or; allows both ceiling suspended as floor standing installation.
FlXS-B 25-35-50-60 FlEXI TYPE uNIT Comfort & Efficiency night set mode saves energy by preventing overcooling or › overheating during night timeCan fit on either ceiling or lower wall. its low height enables it to fit › beneath a window powerful mode can be selected for rapid cooling or heating ...
Page 130 - INTEgRATEd VENTIlATION; Heat Reclaim Ventilation
INTEgRATEd VENTIlATION daikin offers a variety of solutions for the provision of fresh air ventilation to offices, hotels, stores and other commercial outlets – each one complementary to and as flexible as the VrV ® system itself. Heat Reclaim Ventilation proper ventilation is a key component of cli...
Page 132 - hEAT REClAIM VENTIlATION; models to choose from
VAM-FA hEAT REClAIM VENTIlATION the daikin heat reclaim ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. a balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning syst...
Page 133 - ventilation
1 sound pressure level is measured in heat exchange mode. VAM-fA VENTILATION VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000FA VAM1500FA VAM2000FA Air flow rate m 3 /h 150 250 350 500 650 800 1,000 1,500 2,000 Sound pressure level (max.) 1 dBA 27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/3...
Page 134 - DX coil; Operation example: humidification & air processing
VKM-gM VKM-g exhaust fan heat exchanger elements damper motor damper ea(exhaust air to outdours) oa(fresh air from outdoors) air supply fan electronics box (Control box) sa (supply air to room) ra(return air from room) DX coil (Direct expansion coil) float switch solenoid valve water sa drain pan dr...
Page 135 - Ventilation, humidification & air processing
VKM-GM VENTILATION, DX coil & humidifier VKM50GM VKM80GM VKM100GM Fresh air conditioning load cooling kW 4.71 7.46 9.12 heating kW 5.58 8.79 10.69 Air flow rate ultra high - high - low m 3 /h 500 - 500 - 440 750 - 750 - 640 950 - 950 - 820 Sound pressure level - 220V ultra high - high - low dBA ...
Page 136 - 00% fresh air intake possible
OuTdOOR AIR PROCESSINg uNIT COMBINEd FRESh AIR TREATMENT ANd AIR CONdITIONINg VIA A SINglE SYSTEM both fresh air treatment and air conditioning can be achieved successfully in a single system via heat pump technology without the usual design problems associated with balancing air supply and discharg...
Page 137 - Ventilation & air processing
FXMQ-MFindoor Units FXMQ125MF FXMQ200MF FXMQ250MF Capacity cooling kw 14.0 22.4 28.00 heating kw 8.9 13.9 17.40 Power Input cooling kw 0.359 0.548 0.638 heating kw 0.359 0.548 0.638 Dimensions HxWxD mm 470x744x1,100 470x1380x1,100 Weight kg 86 123 Air Flow Rate cooling medium m3/min 18.0 28.0 35.0 h...
Page 140 - uSER FRIENdlY CONTROl SYSTEMS; MAXIMuM EFFICIENCY; demands that maximum control of all; STATE OF ThE ART; computerised control systems
uSER FRIENdlY CONTROl SYSTEMS an air conditioning system will only operate as efficiently as its control system allows and the importance of precise, user friendly equipment is as relevant to simple residential room temperature controls as it is to full remote monitoring and regulation of large scal...
Page 143 - WIRED REMOTE CONTROL; maintained
BRC1d52 WIRED REMOTE CONTROL Limit operation (min/max): room temperature is controlled within › adjustable upper and lower limits. Limit operation can be activated manually or by schedule timerreal time clock: indicates real time and day › schedule timer: › - it is possible to programme a weekly sch...
Page 145 - NETWORK SOluTIONS; APPLICATION AREA
NETWORK SOluTIONS basic solution for control and management of up to 2,000 indoor units (sky air & VrV ® ) for more details on ds-net consult the ds-net brochure. APPLICATION AREA a small commercial area of less than › 40 indoor units.Critical applications for centralized monitoring. › SySTEM LA...
Page 150 - INDIVIDuAL CONTROL SySTEMS
ACCESSORIES INDIVIDuAL CONTROL SySTEMS CENTRALISED CONTROL SySTEMS OTHERS notes: 1 installation box is required 2 fixing box is krp1a90 3 mounting plate krp4a96 is required. maximum 2 option pCb can be mounted. 4 up to 2 adapters can be fixed per installation box 5 only 1 installation box can be ins...
Page 153 - bMS: buILDING MANAGEMENT SySTEM
Intelligent Processing unit SoftwareInterface adapters DIII AiDigital inputDigital input / outputPower Proportional DistributionECO ModeWeb Acces Function DESCRIPTION REfERENCE COMMENTS DESCRIPTION REfERENCE COMMENTS L on W orks ® networks compatible Gateway DMS504B51 Up to 64 groups can be connecte...
Page 154 - NOTES
Page 156 - FSC
eC pen 09-200 • 2515 • 02/09 • Copyright © d aikin the present publication supersedes ep Cen 08-200 . printed on non-chlorinated paper. prepared by La m ovida, belgium responsible editor: d aikin europe n .V., Zandvoordestraat 300, b-8400 o ostende the present leaflet is drawn up by way of informati...