Page 2 - WARNING
• Installation should be left to the authorized dealer or another trained professional. Improper installation may cause water leakage, electrical shock, fire, or equipment damage. • Do not install the air conditioner where gas leakage would be exposed to open flames. If the gas leaks and builds up a...
Page 3 - OUTDOOR UNIT
Accessories supplied with the outdoor unit: Accessories Precautions for Selecting the Location (A) Installation Manual (C) Reducer assy (B) Drain socket assy Cannot be installed hanging from ceiling or stacked. 1 1 1 OUTDOOR UNIT 1) Choose a place solid enough to bear the weight and vibration of the...
Page 4 - Indoor/Outdoor Unit Installation Drawings; Be sure to connect at least 2 rooms.; CAUTION; Clamping material
Indoor/Outdoor Unit Installation Drawings For installation of the indoor units, refer to the installation manual which was provided with the units.(The diagram shows a wall-mounted indoor unit.) 1) Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work with...
Page 5 - Installation; Install the unit horizontally.; Precautions on Installation
Installation 4MXS32 ∗ – Up to 45000 Btu ● Install the unit horizontally. ● The unit may be installed directly on a concrete verandah or a solid place if drainage is good. ● If the vibration may possibly be transmitted to the building, use a vibration-proof rubber (field supply). Precautions on Insta...
Page 6 - Shortest allowable length per room is 9.8ft.
Outdoor Unit Installation Guidelines Selecting a Location for Installation of the Indoor Units ● The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the outdoor and indoor units, are listed below. (The shorter the refrigerant piping, the better the...
Page 7 - to never insert drain sockets into the wrong drain holes; NOTE; Refrigerant Piping; to
Refrigerant Piping Work (1) 1 Installing Outdoor Unit ● When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Indoor/Outdoor Unit Installation Drawings”. ● If drain work is necessary, follow the procedures below. 2 Drain Work ● Use drain plug for drainage. ● If...
Page 8 - Check the machine nameplate; Precautions when adding R410A; Evacuation for; at least 1 hour; ) Remove covers from liquid stop value and gas stop valve.
Refrigerant Piping Work (2) 4 Purging Air and Checking Gas Leakage ● When piping work is completed, it is necessary to purge the air and check for gas leakage. 5 Refilling The Refrigerant Check the machine nameplate for the type of refrigerant to be used . Precautions when adding R410A Fill from the...
Page 9 - Flaring the Pipe End; Charging with Refrigerant; Cautions on Pipe Handling; Selection of copper and heat insulation materials; reduces
Refrigerant Piping Work (3) Wall If no flare cap is available, cover the flare mouth with tape to keep dirt or water out. Be sure to place a cap. Rain Gas pipe Liquid pipe Gas pipe insulation Liquid pipe insulation Finishing tape Drain hose Inter-unit wiring 8 Flaring the Pipe End 1) Cut the pipe en...
Page 11 - Forced Operation; ground
Lock nut Conduit Conduitmounting plate Knockout hole Forced Operation Wiring (1) 1) Turn the Operation Mode switch (SW2) to “COOL.” 2) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to stop forced cooling. ● Forced operation also stops ...
Page 12 - Ground; so that the terminal numbers match.; Be sure to match the symbols for wiring and piping.
Room A Room C Room D Room B power supply Wiring (2) Stranded wire Round crimp-styleterminal When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling.Problems with the work may cause heat and fires. CAUTION (2) In case using stranded wires is una...
Page 13 - Priority Room Setting; About the Priority Room Setting function; ) Operation mode priority; Be sure to only set one room
Priority Room Setting ● To use Priority Room Setting, initial settings must be made when the unit is installed. Explain the Priority Room Setting, as described below, to the customer, and confirm whether or not the customer wants to use Priority Room Setting.Setting it in the guest and living rooms ...
Page 14 - Night Quiet Mode setting; About Night Quiet Mode; Setting procedure; JST products; Arrow view
Night Quiet Mode setting COOL/ HEAT mode lock <S15> ● If Night Quiet Mode is to be used, initial settings must be made when the unit is installed. Explain Night Quiet Mode, as described below, to the customer, and confirm whether or not the customer wants to use Night Quiet Mode. About Night Q...
Page 15 - Wiring Error Check; All; Wiring correct example
Test Run and Final Check (1) 1) For two rooms, LED 3 and 4 are not displayed, and for three rooms, LED 4 is not displayed. 2) If the outside air temperature is 41 ° F or less , the wiring error check function will not operate. 3) After wiring error check operation is completed, LED indication will c...
Page 16 - ATTENTION; Test Run and Final Check
3P207257-3 M07B061 Test Run and Final Check (2) ● Have the customer actually operate the unit while looking at the manual included with the indoor unit. Instruct the customer how to operate the unit correctly (particularly cleaning of the air filters, operation procedures, and temperature adjustment...