Page 2 - TABLE OF CONTENTS
2 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product Overview . . . . . . . . . . . . . . . ....
Page 3 - INTRODUCTION; Performance and dependability in a no-nonsense heat pump.; PRODUCT OVERVIEW; Refrigerant
Johnson Controls 3 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) INTRODUCTION Performance and dependability in a no-nonsense heat pump. The R-Series units by YORK are completely self-contained heat pumps. This equipment employs a water-to-refrigerant heat exchanger to extract (heating ...
Page 4 - SPECIFICATIONS
4 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps SPECIFICATIONS GENERAL All R-series models ½ - 6 ton ship as factory-charged packages, complete with R-410A refrigerant. Horizontal (RSH) units are designed for suspended ceiling mount-ing. RSH models are shipped with ‘st...
Page 5 - NOMENCLATURE; WATER SOURCE HEAT PUMP; RS H 018 A 2 E L S A A 0 A
Johnson Controls 5 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) NOMENCLATURE WATER SOURCE HEAT PUMP Product Category RS = Water-Cooled HP R-410A Product Indentifier V = Vertical Arrangement (Upflow)H = Horizontal Arrangment Miscellaneous Options A = None D = Condensate Overflow Switch...
Page 6 - PHYSICAL DATA
6 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps PHYSICAL DATA Model Series 007 009 012 018 024 030 036 042 048 060 070 Nominal Cooling (Ton) 1 0.5 0.75 1.0 1.5 2.0 2.5 3 3.5 4 5 6 Compressor-Type Rotary Reciprocating Scroll Air Coil-Type Enhanced Copper tubes, Enhanced...
Page 7 - ARI/ISO PERFORMANCE DATA
Johnson Controls 7 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) ARI/ISO PERFORMANCE DATA PERFORMANCE DATA - ARI/ISO 13256-1 WATER LOOP CONDITIONS* Unit Model Flow Rate (USGPM) Air Flow (SCFM) Cooling Capacity (Btuh) EER Heating Capacity (Btuh) COP 007 1.8 260 6,800 12.5 8,700 4.5 009 ...
Page 8 - PERFORMANCE DATA
8 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps PERFORMANCE DATA RS*007 — 320 CFM EWT (F) GPM WPD COOLING HEATING PSI FT TC SC kW HR EER HTG kW HE LAT (F) COP 20 1.8 4.8 11.0 4.1 0.44 2.6 80 2.7 30 1.0 2.1 4.9 8.5 6.0 0.30 9.5 28.0 5.0 0.45 3.5 82 3.3 1.4 2.8 6.4 8.7 6...
Page 19 - CORRECTION FACTORS; ANTIFREEZE CORRECTION TABLE; HEATING PERFORMANCE CORRECTION TABLE
Johnson Controls 19 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) CORRECTION FACTORS ANTIFREEZE CORRECTION TABLE Antifreeze Concentration 5% 10% 15% 20% 25% 30% 40% Ethylene Glycol Cooling 0.998 0.995 0.993 0.991 0.989 0.987 0.984 Heating 0.995 0.990 0.985 0.980 0.974 0.969 0.964 PD 1....
Page 20 - BLOWER PERFORMANCE
20 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps BLOWER PERFORMANCE BLOWER PERFORMANCE Unit Size Rated CFM Min. CFM Max. CFM Motor Speed External Static Pressure (in w.g.) 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 007 260 182 299 High - - - - - - - - - Med - - 300 270 235 200 ...
Page 21 - ELECTRICAL DATA; RSH/RSV ELECTRICAL DATA
Johnson Controls 21 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) ELECTRICAL DATA RSH/RSV ELECTRICAL DATA Unit Size SUPPLY VOLTAGE COMPRESSOR BLOWER MIN. CCT. AMPACITY MAX FUSE / CCT. BKR. AMP QTY RLA LRA HP FLA 007 208-230/1/60 1 @ 3.4 22.0 0.10 0.8 5.05 15 009 208-230/1/60 1 @ 4.6 28...
Page 22 - DIMENSIONAL DATA; RSH SERIES
22 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps D A B E C G 1.50" J 2.00" K L 1.63" M 3/4 FPT DRAIN WATER IN WATER OUT SUPPLY AIR AIR RETURN 0.75" TYP 0.75" Ø0.875" 1 2 3 3 - BLOWER SERVICE DOOR 2 - COMPRESSOR AND CONDENSER 1 - ELECTRICAL BOX S...
Page 23 - RSV SERIES
Johnson Controls 23 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) A C K L 2 1" G D G F E G D G F E SERVICE DOORS 1 - ELECTRICAL BOX SERVICE DOOR 2 - COMPRESSOR AND CONDENSER SERVICE DOOR 3 - BLOWER SERVICE DOOR B 2" AIR SUPPLY RETURN AIR 1 3 WATER IN WATER OUT DRAIN 3/4Ø POWER ...
Page 24 - WIRING DIAGRAM; SINGLE PHASE
24 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps WIRING DIAGRAM SINGLE PHASE RS* UNITS: 208-230V/1Ph/60Hz 265V/1PH/60Hz
Page 25 - PHASE
Johnson Controls 25 Water Source Heat Pumps Technical Guide: YK145.00-EG4 (309) WIRING DIAGRAM 3 PHASE RS* UNITS: 208-230V/3Ph/60Hz 460V/3Ph/60Hz 575V/3Ph/60Hz
Page 26 - NOTES
26 Johnson Controls Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps NOTES