Page 2 - TABLE OF CONTENTS; LIST OF FIGURES
343615-YTG-B-0308 2 Johnson Controls Unitary Products TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTI...
Page 3 - Johnson Controls Unitary Products; PRODUCT NOMENCLATURE; -5 Ton Sunline MagnumTM Model Number Nomenclature
343615-YTG-B-0308 Johnson Controls Unitary Products 3 PRODUCT NOMENCLATURE D Y 048 N04 A 2 A AA 2 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow D = Direct Drive/Motorized Damper B = Direct Drive/Single Input Economizer A = Direct Drive Product Generation 2 = Second Generation C00 = C...
Page 4 - FEATURES; Simplicity
343615-YTG-B-0308 4 Johnson Controls Unitary Products FEATURES All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard...
Page 5 - Electric/Electric and Heat Pump
343615-YTG-B-0308 Johnson Controls Unitary Products 5 Gas/Electric Electric/Electric and Heat Pump FIGURE 1 - UNIT CUTAWAY 3/4 " PVC female condensate drain Knockoutfor sidecontrol entry GFCI convenience outlet Smoke detector Slide-in economizer Economizer hood HACR breaker 20 Gauge aluminized s...
Page 6 - FACTORY-INSTALLED OPTIONS
343615-YTG-B-0308 6 Johnson Controls Unitary Products FACTORY-INSTALLED OPTIONS • SINGLE INPUT ELECTRONIC ENTHALPY ECONO-MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage ty...
Page 7 - FIELD-INSTALLED ACCESSORIES
343615-YTG-B-0308 Johnson Controls Unitary Products 7 • STAINLESS STEEL HEAT EXCHANGER - For applica- tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly. • STAINLESS STEEL DRAIN PAN - An optional rust- proof stainless steel drain pan is available to ...
Page 9 - DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET); Horizontal Ducted Inlet; DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE); Horizontal Ducted Discharge
343615-YTG-B-0308 Johnson Controls Unitary Products 9 TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 80 82 80 82 78 83 81 85 125 76 77 76 77 82 83 81 82 250...
Page 10 - DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET); Vertical Ducted Inlet; DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE); Vertical Ducted Discharge
343615-YTG-B-0308 10 Johnson Controls Unitary Products TABLE 6: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 78 82 78 82 80 85 80 84 125 70 75 70 74 71 80 71 79 250 ...
Page 11 - DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET); DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
343615-YTG-B-0308 Johnson Controls Unitary Products 11 TABLE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 74 97 74 95 77 90 77 90 125 70 86 69 86 73 78 72 77 25...
Page 12 - TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
343615-YTG-B-0308 12 Johnson Controls Unitary Products TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 76 95 77 93 80 91 79 91 125 68 84 67 82 76 84 73 80 250...
Page 13 - TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
343615-YTG-B-0308 Johnson Controls Unitary Products 13 TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 77 84 77 84 81 85 79 84 125 71 71 72 73 74 75 71 72 2...
Page 14 - TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
343615-YTG-B-0308 14 Johnson Controls Unitary Products TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 77 86 79 88 81 86 83 87 125 69 70 70 72 71 73 72 72...
Page 19 - TABLE 21: STATIC RESISTANCES; TABLE 22: ELECTRIC HEAT CFM LIMITATIONS; Size
343615-YTG-B-0308 Johnson Controls Unitary Products 19 1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.3. The p...
Page 24 - TABLE 25: DY PHYSICAL DATA
343615-YTG-B-0308 24 Johnson Controls Unitary Products TABLE 25: DY PHYSICAL DATA MODELS DY 036 048 060 EVAPORATOR BLOWER Centrifugal Blower (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 Fan Motor HP (Direct Drive) 3/4 1 1 EVAPORATOR COIL Rows Deep 3 4 4 Fins Per Inch 13 13 13 Face Area (Ft. 2 ) 5.1 5.1 ...
Page 25 - FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING; TYPICAL POWER WIRING
343615-YTG-B-0308 Johnson Controls Unitary Products 25 FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING REFER TO THE ELECTRICAL DATATABLES TO SIZE THE DISCONNECTSWITCH, OVERCURRENT PROTEC-TION AND WIRING. RC RH Y1 Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT 1 TERMINA...
Page 27 - FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD; DETAIL “A”; FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD; DETAIL “B”
343615-YTG-B-0308 Johnson Controls Unitary Products 27 FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “A” FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD DETAIL “B”
Page 28 - FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION
343615-YTG-B-0308 28 Johnson Controls Unitary Products FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 28: UTILITIES ENTRY HOLE OPENING SIZE (DIA.) USED FOR A 7/8” KO 1 1. Opening in the bottom to the unit can be located by the side in the insulation. Contro...
Page 29 - FIGURE 9 - TYPICAL APPLICATIONS
343615-YTG-B-0308 Johnson Controls Unitary Products 29 FIGURE 9 - TYPICAL APPLICATIONS
Page 30 - FIGURE 10 -FOUR AND SIX POINT LOADING
343615-YTG-B-0308 30 Johnson Controls Unitary Products FIGURE 10 -FOUR AND SIX POINT LOADING 44 7 / 8 82 1 / 4 Y X A B C D CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT 44 7 / 8 82 1 / 4 Y X A B C D E F CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER...
Page 31 - MODEL SIZE; FIGURE 11 -ROOF CURB DIMENSIONS
343615-YTG-B-0308 Johnson Controls Unitary Products 31 TABLE 32: OPERATING WEIGHTS (LBS.) MODEL SIZE 3 TON 4 TON 5 TON BASIC UNIT DY (Cooling Only) 575 585 590 DY (Gas/Electric) N04 615 - - N06 - 635 - N08 635 - 650 N10 - 655 660 D06 625 635 640 D10 645 655 660 OPTIONS Economizer 50 Motorized Damper...
Page 32 - GUIDE SPECIFICATIONS; GENERAL; York's Sunline Magnum; UNIT CABINET
343615-YTG-B-0308 32 Johnson Controls Unitary Products GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline Magnum ™ units are convertible single pack- age units. Although the units are primarily desig...
Page 36 - Copyright
Subject to change without notice. Printed in U.S.A. 343615-YTG-B-0308 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 343615-YTG-A-0807 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069