Page 2 - TABLE OF CONTENTS; LIST OF FIGURES
343615-YTG-A-0807 2 Unitary Products Group TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . ....
Page 3 - PRODUCT NOMENCLATURE; -5 Ton Sunline MagnumTM Model Number Nomenclature
343615-YTG-A-0807 Unitary Products Group 3 PRODUCT NOMENCLATURE D Y 048 N04 A 2 A AA 2 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow D = Direct Drive/Motorized Damper B = Direct Drive/Single Input Economizer A = Direct Drive Product Generation 2 = Second Generation C00 = Cooling Only...
Page 4 - FEATURES; Simplicity
343615-YTG-A-0807 4 Unitary Products Group FEATURES All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make th...
Page 5 - FACTORY-INSTALLED OPTIONS
343615-YTG-A-0807 Unitary Products Group 5 FACTORY-INSTALLED OPTIONS • SINGLE INPUT ELECTRONIC ENTHALPY ECONO-MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers....
Page 6 - FIELD-INSTALLED ACCESSORIES
343615-YTG-A-0807 6 Unitary Products Group air temperature. The patented economizer-loading algo-rithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for ...
Page 8 - DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET); Horizontal Ducted Inlet; DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE); Horizontal Ducted Discharge
343615-YTG-A-0807 8 Unitary Products Group TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 80 82 80 82 78 83 81 85 125 76 77 76 77 82 83 81 82 250 56 59 56 6...
Page 9 - DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET); Vertical Ducted Inlet; DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE); Vertical Ducted Discharge
343615-YTG-A-0807 Unitary Products Group 9 TABLE 6: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 78 82 78 82 80 85 80 84 125 70 75 70 74 71 80 71 79 250 55 60 55 60 ...
Page 10 - DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET); DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
343615-YTG-A-0807 10 Unitary Products Group TABLE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 74 97 74 95 77 90 77 90 125 70 86 69 86 73 78 72 77 250 53 58 52 ...
Page 11 - TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
343615-YTG-A-0807 Unitary Products Group 11 TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 76 95 77 93 80 91 79 91 125 68 84 67 82 76 84 73 80 250 54 57 52 5...
Page 12 - TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
343615-YTG-A-0807 12 Unitary Products Group TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODELCONFIGURATION Indoor Blower Speed (RPM)Blower Static Pressure (IWG)Airflow (CFM)Blower Motor BHP 63 77 84 77 84 81 85 79 84 125 71 71 72 73 74 75 71 72 250 57 58 55...
Page 13 - TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
343615-YTG-A-0807 Unitary Products Group 13 TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 77 86 79 88 81 86 83 87 125 69 70 70 72 71 73 72 72 250 56 63 ...
Page 18 - TABLE 21: STATIC RESISTANCES; TABLE 22: ELECTRIC HEATER CFM LIMITATIONS
343615-YTG-A-0807 18 Unitary Products Group 1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.3. The pressure thr...
Page 24 - FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING; TYPICAL POWER WIRING
343615-YTG-A-0807 24 Unitary Products Group FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING REFER TO THE ELECTRICAL DATATABLES TO SIZE THE DISCONNECTSWITCH, OVERCURRENT PROTEC-TION AND WIRING. RC RH Y1 Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT 1 TERMINALS UNIT TER...
Page 26 - FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD; DETAIL “A”; FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD; DETAIL “B”
343615-YTG-A-0807 26 Unitary Products Group FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “A” FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD DETAIL “B”
Page 27 - TABLE 29: MINIMUM CLEARANCES
343615-YTG-A-0807 Unitary Products Group 27 FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 28: UTILITIES ENTRY HOLE OPENING SIZE (DIA.) USED FOR A 7/8” KO 1 1. Opening in the bottom to the unit can be located by the side in the insulation. Control Wiring 2 ...
Page 28 - FIGURE 9 - TYPICAL APPLICATIONS
343615-YTG-A-0807 28 Unitary Products Group FIGURE 9 - TYPICAL APPLICATIONS
Page 29 - FIGURE 10 -FOUR AND SIX POINT LOADING; TABLE 30: DY 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
343615-YTG-A-0807 Unitary Products Group 29 FIGURE 10 -FOUR AND SIX POINT LOADING 44 7 / 8 82 1 / 4 Y X A B C D CONDENSER COILEND OF UNIT FRONT OF UNIT APPROXIMATECENTER OF GRAVITY BACK OF UNIT 44 7 / 8 82 1 / 4 Y X A B C D E F CONDENSER COILEND OF UNIT FRONT OF UNIT APPROXIMATECENTER OF GRAVITY BAC...
Page 30 - FIGURE 11 -ROOF CURB DIMENSIONS
343615-YTG-A-0807 30 Unitary Products Group TABLE 32: OPERATING WEIGHTS (LBS.) MODEL SIZE 3 TON 4 TON 5 TON BASIC UNIT DY (Cooling Only) 575 585 590 DY (Gas/Electric) N04 615 - - N06 - 635 - N08 635 - 650 N10 - 655 660 D06 625 635 640 D10 645 655 660 OPTIONS Economizer 50 Motorized Damper 26 Electri...
Page 31 - GUIDE SPECIFICATIONS; GENERAL; York's Sunline Magnum; DESCRIPTION; UNIT CABINET
343615-YTG-A-0807 Unitary Products Group 31 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline Magnum ™ units are convertible single pack- age units. Although the units are primarily designed for cur...
Page 32 - UNIT CONTROLS
343615-YTG-A-0807 32 Unitary Products Group Coils: a. Evaporator and condenser coils shall have alumi-num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option. b. Evaporator and Condenser c...