Page 2 - Johnson Controls Unitary Products; TABLE OF CONTENTS; LIST OF FIGURES; TYPICAL SIMPLICITY; LIST OF TABLES; 9 DJ ELECTRICAL DATA WITHOUT POWERED
261660-YTG-D-0708 2 Johnson Controls Unitary Products TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTION...
Page 3 - PRODUCT NOMENCLATURE; 5-25 Ton MagnumTM Model Number Nomenclature
261660-YTG-D-0708 Johnson Controls Unitary Products 3 PRODUCT NOMENCLATURE D J 180 N24 A 2 A AA 1 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category A = Std. Drive Airflow B = Std. Drive/Single Input Econo.C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only) D = Std. Drive/Motorized D...
Page 4 - FEATURES; Simplicity
261660-YTG-D-0708 4 Johnson Controls Unitary Products FEATURES All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application. All units are self-co...
Page 5 - Electric Heat Operation; - York’s MagnumTM series units offer fac-; Comfort; FACTORY-INSTALLED OPTIONS; POWER EXHAUST; - Our single economizer options are; FIGURE 1 - UNIT CUTAWAY
261660-YTG-D-0708 Johnson Controls Unitary Products 5 with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. The gas supply piping c...
Page 8 - FIELD-INSTALLED ACCESSORIES
261660-YTG-D-0708 8 Johnson Controls Unitary Products FIELD-INSTALLED ACCESSORIES • SINGLE INPUT ELECTRONIC ENTHALPY ECONO-MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage ...
Page 9 - TABLE 1: SOUND POWER RATING; TABLE 3: GAS HEAT RATIINGS
261660-YTG-D-0708 Johnson Controls Unitary Products 9 NOTE: All gas units are two-stage heating.First stage is 50% of total.S.S.E. = Steady State Efficiency (80%) - output divided by input. TABLE 1: SOUND POWER RATING 1 UNIT SIZE CFM ESP BLOWER SOUND POWER (db 10 -12 Watts) Octave Band Centerline Fr...
Page 10 - TABLE 4: COOLING CAPACITIES FOR DJ180
261660-YTG-D-0708 10 Johnson Controls Unitary Products TABLE 4: COOLING CAPACITIES FOR DJ180 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Se...
Page 11 - TABLE 5: COOLING CAPACITIES FOR DJ210
261660-YTG-D-0708 Johnson Controls Unitary Products 11 TABLE 5: COOLING CAPACITIES FOR DJ210 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Se...
Page 12 - TABLE 6: COOLING CAPACITIES FOR DJ240
261660-YTG-D-0708 12 Johnson Controls Unitary Products TABLE 6: COOLING CAPACITIES FOR DJ240 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Se...
Page 13 - TABLE 7: COOLING CAPACITIES FOR DJ300
261660-YTG-D-0708 Johnson Controls Unitary Products 13 TABLE 7: COOLING CAPACITIES FOR DJ300 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Se...
Page 14 - Example 1; tion is given so 70°F is assumed.; TABLE 8: ALTITUDE CORRECTION FACTORS
261660-YTG-D-0708 14 Johnson Controls Unitary Products CFM, STATIC PRESSURE, AND POWER - ALTI-TUDE AND TEMPERATURE CORRECTIONS The information below should be used to assist in applicationof product when being applied at altitudes at or exceeding1000 feet above sea level. The air flow rates listed i...
Page 15 - FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
261660-YTG-D-0708 Johnson Controls Unitary Products 15 FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
Page 16 - 80 MBH - BOTTOM DUCT CONNECTIONS
261660-YTG-D-0708 16 Johnson Controls Unitary Products NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duc...
Page 17 - 10 MBH - BOTTOM DUCT CONNECTIONS
261660-YTG-D-0708 Johnson Controls Unitary Products 17 NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duc...
Page 18 - 40 MBH - BOTTOM DUCT CONNECTIONS
261660-YTG-D-0708 18 Johnson Controls Unitary Products NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duc...
Page 22 - 00 MBH - BOTTOM DUCT CONNECTIONS
261660-YTG-D-0708 22 Johnson Controls Unitary Products NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and r...
Page 23 - TABLE 16: BLOWER MOTOR AND DRIVE DATA
261660-YTG-D-0708 Johnson Controls Unitary Products 23 TABLE 16: BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLOWER RANGE (RPM) MOTOR 1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT (NOTCHED) HP FRAME EFF. (%) DESIG- NATION OUTSIDE DIA.(IN.) PITCH DIA.(IN.) BORE (IN.) DESIG- NATION OUTSIDE DIA.(...
Page 24 - TABLE 19: DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
261660-YTG-D-0708 24 Johnson Controls Unitary Products NOTE 1: HACR Type per NEC. TABLE 19: DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET MODEL (TON- NAGE) VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN. CIRCUIT AMPACITY (AMPS) MAX. FUSE/ BR...
Page 26 - TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
261660-YTG-D-0708 26 Johnson Controls Unitary Products NOTE 1: HACR Type per NEC. TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET MODEL (TON- NAGE) VOLTAGE COMPRESSORS OD FAN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEATER OPTION MIN. CIRCUIT AMPACITY (AMPS) MAX. FUSE/ BRKR ...
Page 28 - TABLE 21: DJ VOLTAGE LIMITATIONS; MODELS
261660-YTG-D-0708 28 Johnson Controls Unitary Products TABLE 21: DJ VOLTAGE LIMITATIONS 1 1. Utilization Range “A” in accordance with ARI Standard 110. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE MIN. MAX. VOLTAGE LIMITATIONS 208/230-3-60 187 253 460-3-60 414 506 575-3-60 518 630 TABLE 22: PHYSICAL DAT...
Page 29 - SUPPLY FAN MOTOR; TABLE 24: ELECTRIC HEAT CORRECTION; NOMINAL VOLTAGE; FIGURE 3 - TYPICAL DJ FIELD WIRING DIAGRAM; CONTROL WIRING
261660-YTG-D-0708 Johnson Controls Unitary Products 29 TABLE 23: SUPPLY FAN VFD WEIGHTS, IN LBS. SUPPLY FAN MOTOR 230V 460V 575V W/O MANUAL BYPASS 5.0 hp 25 25 30 7.5 hp 30 30 30 10.0 hp 30 30 35 15.0 hp 30 30 40 W/MANUAL BYPASS 5.0 hp 30 30 35 7.5 hp 35 35 35 10.0 hp 35 35 40 15.0 hp 40 35 45 TABLE...
Page 30 - FIGURE 4 - FRONT VIEW DIMENSIONS; HOLE
261660-YTG-D-0708 30 Johnson Controls Unitary Products FIGURE 4 - FRONT VIEW DIMENSIONS TABLE 25: UTILITIES ENTRY DATA HOLE OPENING SIZE (DIA.) USED FOR A 1-1/8” KO Control Wiring Side 3/4” NPS (Fem.) Bottom B 3-5/8” KO Power Wiring Side 3” NPS (Fem.) Bottom C 2-3/8” KO Gas Piping (Front) 1 1. One-i...
Page 31 - FIGURE 5 - REAR VIEW DIMENSIONS; For bottom duct applications:; Connect ductwork to the flanges on those panels.
261660-YTG-D-0708 Johnson Controls Unitary Products 31 FIGURE 5 - REAR VIEW DIMENSIONS NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1. Remove the side panels from the supply and return air...
Page 32 - TABLE 26: MINIMUM CLEARANCES; REAR VIEW
261660-YTG-D-0708 32 Johnson Controls Unitary Products NOTE: ELEC / ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters. GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air duct...
Page 33 - FIGURE 7 - UNIT CENTER OF GRAVITY
261660-YTG-D-0708 Johnson Controls Unitary Products 33 FIGURE 7 - UNIT CENTER OF GRAVITY FIGURE 8 - TYPICAL UNIT APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION
Page 34 - FIGURE 9 - FOUR AND SIX POINT LOADS
261660-YTG-D-0708 34 Johnson Controls Unitary Products FIGURE 9 - FOUR AND SIX POINT LOADS A D C E B F A D B C TABLE 27: FOUR AND SIX POINT LOADS 180 Gas 2660 454 847 885 474 210 Gas 2928 510 954 954 510 240 Gas 2960 516 964 964 516 300 Gas 3046 531 992 992 531 180 Elec 2460 419 784 819 438 210 Elec...
Page 35 - FIGURE 10 - UNIT ROOF CURB DIMENSIONS
261660-YTG-D-0708 Johnson Controls Unitary Products 35 1. The 2” space between the ducts allows for “jumping” an existing roof joist. 2. The 58-1/2” overall dimension of the ducts allows duct-work penetration between roof joists that are spaced on 72” centers. Note: Ducts can be installed into the c...
Page 36 - FIGURE 13 - TYPICAL SIMPLICITY; SD
261660-YTG-D-0708 36 Johnson Controls Unitary Products FIGURE 13 - TYPICAL SIMPLICITY ® WIRING DIAGRAM W1 W2 Y1 G OCC P P1 Y2 X R SD C C SD SD R OCC C RC G Y2 Y1 W2 W1 Jumper Smoke Detector 24 VAC Class 2 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 ...
Page 37 - GUIDE SPECIFICATIONS; GENERAL; UNIT CABINET
261660-YTG-D-0708 Johnson Controls Unitary Products 37 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline Magnum™ units are convertible single pack-age units. All models have dual independent refrige...
Page 38 - REFRIGERANT COMPONENTS; All models shall have two independent circuits.; UNIT CONTROLS; Induced draft motor speed sensor.
261660-YTG-D-0708 38 Johnson Controls Unitary Products OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor-rosion resistant steel spider brackets and shall be dynami-cally balanced for smooth op...