Page 2 - TABLE OF CONTENTS; LIST OF FIGURES
262260-YTG-E-1008 2 Johnson Controls Unitary Products TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTION...
Page 3 - PRODUCT NOMENCLATURE; 5-25 Ton Sunline UltraTM Model Number Nomenclature
262260-YTG-E-1008 Johnson Controls Unitary Products 3 PRODUCT NOMENCLATURE D H 180 N24 A 2 A AA 1 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow 1 = First Generation Product Generation 2 = Second Generation C00 = Cooling Only. No field installed electric heat Heat Type and Nominal Hea...
Page 4 - FEATURES; Simplicity
262260-YTG-E-1008 4 Johnson Controls Unitary Products FEATURES All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application. All units are self-co...
Page 5 - All models are CSA approved.; Gas Heat Operation; - All gas heat units are built with; Electric Heat Operation; - York’s SunlineTM series units offer factory; Comfort; FACTORY-INSTALLED OPTIONS; FIGURE 1 - UNIT CUTAWAY; UNIT SHOWN
262260-YTG-E-1008 Johnson Controls Unitary Products 5 All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. All models are CSA approved. • Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors...
Page 8 - FIELD-INSTALLED ACCESSORIES
262260-YTG-E-1008 8 Johnson Controls Unitary Products • HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR, FILTER AND ELECTRIC ACCESS PANELS - This option allows for complete hinged and tool free access to the unit's blower, blower motor, filters and electrical panel sections. FIELD-INSTALLED ACCESSOR...
Page 9 - TABLE 1: INDOOR SOUND POWER RATING; TABLE 3: GAS HEAT RATINGS
262260-YTG-E-1008 Johnson Controls Unitary Products 9 SSE = Steady State Efficiency (80%) - Output divided by Input TABLE 1: INDOOR SOUND POWER RATING 1 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA val- ues provide...
Page 18 - Example 1; tion is given so 70°F is assumed.; TABLE 8: ALTITUDE CORRECTION FACTORS
262260-YTG-E-1008 18 Johnson Controls Unitary Products CFM, STATIC PRESSURE, AND POWER - ALTI-TUDE AND TEMPERATURE CORRECTIONS The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed...
Page 19 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
262260-YTG-E-1008 Johnson Controls Unitary Products 19 FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
Page 20 - 80 MBH - BOTTOM DUCT CONNECTIONS
262260-YTG-E-1008 20 Johnson Controls Unitary Products NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.2. Refer to Table 11 for additional static resistances. ESP = External Static Pressure available for the supply and return air du...
Page 21 - 10 MBH - BOTTOM DUCT CONNECTIONS
262260-YTG-E-1008 Johnson Controls Unitary Products 21 NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duc...
Page 22 - 40 MBH - BOTTOM DUCT CONNECTIONS
262260-YTG-E-1008 22 Johnson Controls Unitary Products NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.2. Refer to Table 11 for additional static resistances. ESP = External Static Pressure available for the supply and return air du...
Page 26 - 00 MBH - BOTTOM DUCT CONNECTIONS
262260-YTG-E-1008 26 Johnson Controls Unitary Products NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and ...
Page 27 - TABLE 16: BLOWER MOTOR AND DRIVE DATA; TABLE 18: POWER EXHAUST PERFORMANCE
262260-YTG-E-1008 Johnson Controls Unitary Products 27 TABLE 16: BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLOWER RANGE (RPM) MOTOR 1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT (NOTCHED) HP FRAME EFF. (%) DESIG- NATION OUTSIDE DIA.(IN.) PITCH DIA.(IN.) BORE (IN.) DESIG- NATION OUTSIDE DIA. ...
Page 32 - TABLE 25: DH VOLTAGE LIMITATIONS; POWER SUPPLY; TABLE 26: ELECTRIC HEAT CORRECTION; NOMINAL VOLTAGE; TYPICAL DH FIELD WIRING DIAGRAM; CONTROL WIRING
262260-YTG-E-1008 32 Johnson Controls Unitary Products TABLE 25: DH VOLTAGE LIMITATIONS 1 1. Utilization Range “A” in accordance with ARI Standard 110. POWER SUPPLY VOLTAGE MIN. MAX. 208/230-3-60 187 253 460-3-60 414 506 575-3-60 518 506 TABLE 26: ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOL...
Page 33 - TABLE 27: PHYSICAL DATA
262260-YTG-E-1008 Johnson Controls Unitary Products 33 TABLE 27: PHYSICAL DATA MODELS DH 180 210 240 300 EVAPORATOR BLOWER Centrifugal Blower (Dia. x Wd. in.) 15 x 15 18 x 15 18 x 15 18 x 15 Fan Motor HP Standard/Hi Static 5 7.5 7.5 10/15 EVAPORATOR COIL Rows Deep 4 4 4 4 Fins Per Inch 13.5 13.5 13....
Page 34 - TABLE 30: UTILITIES ENTRY DATA; HOLE
262260-YTG-E-1008 34 Johnson Controls Unitary Products FIGURE 4 - UNIT DIMENSIONS DH180, 210, 240 & 300 (FRONT VIEW) TABLE 30: UTILITIES ENTRY DATA HOLE OPENING SIZE (DIA.) USED FOR A 1-1/8” KO Control Wiring Side 3/4” NPS (Fem.) Bottom B 3-5/8” KO Power Wiring Side 3” NPS (Fem.) Bottom C 2-3/8”...
Page 35 - REAR VIEW DIMENSIONS; For bottom duct applications:; Connect ductwork to the flanges on those panels.
262260-YTG-E-1008 Johnson Controls Unitary Products 35 FIGURE 5 - REAR VIEW DIMENSIONS NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1. Remove the side panels from the supply and return air...
Page 36 - Locate unit so that the vent air outlet hood is at least:; TABLE 31: MINIMUM CLEARANCES; REAR VIEW
262260-YTG-E-1008 36 Johnson Controls Unitary Products NOTE: ELEC / ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters. GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air duct...
Page 37 - UNIT CENTER OF GRAVITY
262260-YTG-E-1008 Johnson Controls Unitary Products 37 FIGURE 7 - UNIT CENTER OF GRAVITY (17.5, 20 & 25 Ton) FIGURE 8 - TYPICAL UNIT APPLICATIONS
Page 38 - UNIT 4 POINT LOAD; FIGURE 10 - UNIT 6 POINT LOAD
262260-YTG-E-1008 38 Johnson Controls Unitary Products FIGURE 9 - UNIT 4 POINT LOAD A C D F R O N T B FIGURE 10 - UNIT 6 POINT LOAD A E D B F C F R O N T TABLE 32: DH 180, 210, 240 & 300 4 POINT LOAD WEIGHT DISTRIBUTION UNIT MODEL OPERATING WEIGHT (lb) A B C D DH180C00 1900 445 484 506 465 DH180...
Page 39 - FIGURE 11 - UNIT ROOF CURB DIMENSIONS
262260-YTG-E-1008 Johnson Controls Unitary Products 39 1. The 2” space between the ducts allows for “jumping” an existing roof joist. 2. The 58-1/2” overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 72” centers. NOTE: Ducts can be installed into the cu...
Page 40 - FIGURE 14 - TYPICAL ROOFTOP INSTALLATION; SIMPLICITY; CONTROL WIRING DIAGRAM
262260-YTG-E-1008 40 Johnson Controls Unitary Products FIGURE 14 - TYPICAL ROOFTOP INSTALLATION FIGURE 15 - TYPICAL SIMPLICITY ® CONTROL WIRING DIAGRAM W1 W2 Y1 G OCC P P1 Y2 X R SD C C SD SD R OCC C RC G Y2 Y1 W2 W1 Jumper Smoke Detector 24 VAC Class 2 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOC...
Page 41 - GUIDE SPECIFICATIONS; GENERAL; UNIT CABINET
262260-YTG-E-1008 Johnson Controls Unitary Products 41 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by Unitary Products in an ISO 9001 certified facility. York's Sunline Ultra™ units are convertible single package units. All models have dual independent refrigerant circuits for efficient...
Page 42 - REFRIGERANT COMPONENTS; All models shall have two independent circuits.; UNIT CONTROLS; Primary and auxiliary high-temperature limit switches.; UNIT OPERATING CHARACTERISTICS
262260-YTG-E-1008 42 Johnson Controls Unitary Products OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor-rosion resistant steel spider brackets and shall be dynami-cally balanced for smooth op...