Page 2 - TABLE OF CONTENTS; LIST OF FIGURES
036-21410-001-A-0502 2 Unitary Products Group TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 FACTORY-INSTALLED OP...
Page 3 - PRODUCT NOMENCLATURE; 5-25T Sunline Magnum Model Number Nomenclature; York Brand
036-21410-001-A-0502 Unitary Products Group 3 PRODUCT NOMENCLATURE 15-25T Sunline Magnum Model Number Nomenclature D J 240 N 24 A 2 A AA 1 A Product Category Product Style D = Air Cond., Single Package A = Style A Product Generation 1 = First Generation Product Identifier J = R-22 Super High Effici...
Page 4 - PRODUCT NOMENCLATURE - Continued; 5-25T Sunline MagnumTM Model Number Nomenclature
036-21410-001-A-0502 4 Unitary Products Group PRODUCT NOMENCLATURE - Continued 15-25T Sunline Magnum™ Model Number Nomenclature Additional Options AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor & Coil Guard AF Phase Monitor & Dirty Filter Switch AG Coil Guard ...
Page 5 - Additional Options
036-21410-001-A-0502 Unitary Products Group 5 EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels ED Johnson UNT Controller, DFS, APS, Phase Monito...
Page 8 - FEATURES; Single enthalpy economizer
036-21410-001-A-0502 8 Unitary Products Group FEATURES All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers,phase monitor, dirty filter switch, and coil guard to make themsuitable for almost every application. All units are self-contained an...
Page 9 - FACTORY-INSTALLED OPTIONS; FIGURE 1: UNIT CUTAWAY
036-21410-001-A-0502 Unitary Products Group 9 • Electric Heat Operation - All electric heat models (fac-tory installed only) are wired for a single power sourceand include a bank of nickel chromium elementsmounted at the discharge of the supply air blower to pro-vide a high velocity and uniform dist...
Page 10 - NOTE: Knobs are shipped separately within the unit to; FIELD-INSTALLED ACCESSORIES; Power exhaust is not available as a field installed option.
036-21410-001-A-0502 10 Unitary Products Group • FILTER OPTIONS - Standard units are shipped with 2”throw-away filters installed. 2” pleated and 4” pleated fil-ters are offered as a factory installed option. • CONVENIENCE OUTLET - This 110 volt outlet can be“powered” by the unit with a stepdown tran...
Page 11 - WOOD SKID - Allows unit to be handled with 90” forks.; levels and automatically
036-21410-001-A-0502 Unitary Products Group 11 • ENTHALPY ACCESSORY CONTROL KIT - This kitcontains the required components to convert a singleenthalpy economizer to dual enthalpy. • BURGLAR BARS - Mount in the supply and returnopenings to prevent entry into the duct work. • FLUE EXHAUST EXTENSION KI...
Page 12 - TABLE 1: SOUND POWER RATING; TABLE 3: GAS HEAT RATIINGS
036-21410-001-A-0502 12 Unitary Products Group NOTE: All gas units are two-stage heating.First stage is 50% of total.S.S.E. = Steady State Efficiency (80%) - output divided by input. TABLE 1: SOUND POWER RATING 1 UNIT SIZE CFM ESP BLOWER SOUND POWER (db 10 -12 Watts) Octave Band Centerline Frequency...
Page 13 - TABLE 4: COOLING CAPACITIES FOR DJ180 AT 85°F
036-21410-001-A-0502 Unitary Products Group 13 TABLE 4: COOLING CAPACITIES FOR DJ180 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 85 CFM WB TEMP °F GROSS CAPACITY 1 (MBH) INPUT POWER 2 (kW) GROSS SENSIBLE CAPACITY 1 (MBH) (RETURN AIR DRY BULB TEMP. - (°F) ) 86 83 80 77 74 71 68 4500 72 210.2...
Page 14 - TABLE 5: COOLING CAPACITIES FOR DJ180 AT 95°F
036-21410-001-A-0502 14 Unitary Products Group TABLE 5: COOLING CAPACITIES FOR DJ180 AT 95°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 95 CFM WB TEMP °F GROSS CAPACITY 1 (MBH) INPUT POWER 2 (kW) GROSS SENSIBLE CAPACITY 1 (MBH) (RETURN AIR DRY BULB TEMP. - (°F) ) 86 83 80 77 74 71 68 4500 72 201.7...
Page 18 - TABLE 9: COOLING CAPACITIES FOR DJ210 AT 85°F
036-21410-001-A-0502 18 Unitary Products Group TABLE 9: COOLING CAPACITIES FOR DJ210 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 85 CFM WB TEMP °F GROSS CAPACITY 1 (MBH) INPUT POWER 2 (kW) GROSS SENSIBLE CAPACITY 1 (MBH) (RETURN AIR DRY BULB TEMP. - (°F) ) 86 83 80 77 74 71 68 6000 72 238.9...
Page 33 - 80 MBH - BOTTOM DUCT CONNECTIONS
036-21410-001-A-0502 Unitary Products Group 33 NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct syste...
Page 34 - 10 MBH - BOTTOM DUCT CONNECTIONS
036-21410-001-A-0502 34 Unitary Products Group NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct syste...
Page 35 - 40 MBH - BOTTOM DUCT CONNECTIONS
036-21410-001-A-0502 Unitary Products Group 35 NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct syste...
Page 39 - 00 MBH - BOTTOM DUCT CONNECTIONS
036-21410-001-A-0502 Unitary Products Group 39 NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return a...
Page 41 - TABLE 34: DJ ELECTRICAL DATA
036-21410-001-A-0502 Unitary Products Group 41 TABLE 34: DJ ELECTRICAL DATA ~ 72.9 90 13.5 72.9 90 27.0 112.9 125 40.6 160.1 175 54.1 169.1 200 ~ 71.9 90 18.0 72.1 90 36.0 126.3 150 54.0 147.9 175 72.0 191.2 225 ~ 36.4 45 18.0 36.4 45 36.0 63.1 70 54.0 74 90 72.0 95.6 110 ~ 31.1 40 18.0 31.1 40 36.0...
Page 42 - TABLE 35: DJ VOLTAGE LIMITATIONS; TABLE 36: PHYSICAL DATA; MODELS
036-21410-001-A-0502 42 Unitary Products Group TABLE 35: DJ VOLTAGE LIMITATIONS 1 VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE MIN. MAX. VOLTAGE LIMITATIONS 208/230-3-60 187 253 460-3-60 414 506 575-3-60 518 630 1. Utilization Range “A” in accordance with ARI Standard 110. TABLE 36: PHYSICAL DATA N24N32...
Page 43 - TABLE 37: ELECTRIC HEAT CORRECTION FACTORS; NOMINAL VOLTAGE; FIGURE 2: DJ FIELD WIRING DIAGRAM; CONTROL WIRING
036-21410-001-A-0502 Unitary Products Group 43 TABLE 37: ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER 208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92 FIGURE 2: DJ FIELD WIRING DIAGRAM 67 68 9: 9; <: <; = 6 67 9: 9; <:<; = > ?@A: ?@A; 8BC D: D; E E F ...
Page 44 - TABLE 38: MINIMUM CLEARANCES; TABLE 39: UTILITIES ENTRY
036-21410-001-A-0502 44 Unitary Products Group NOTE: A 1” clearance must be provided between any com- bustible material and the supply air ductwork for a distance of3 feet from the unit. NOTE: The products of combustion must not be allowed to accumulate within a confined space and recirculate. NOTE:...
Page 45 - Units are shipped with the bottom duct openings ocov-; FIGURE 5: UNIT CENTER OF GRAVITY
036-21410-001-A-0502 Unitary Products Group 45 NOTE: Units are shipped with the bottom duct openings ocov- ered. An accessory flange kit is available for connecting sideducts. For bottom duct applications: 1. Remove the side panels from the supply and return aircompartments to gain access to the bot...
Page 46 - R E A R V I E W; FIGURE 7: TYPICAL UNIT APPLICATIONS
036-21410-001-A-0502 46 Unitary Products Group FIGURE 6: UNIT DIMENSIONS DJ180, 210, 240 & 300 (RAINHOOD) S U P P L Y A I R C O M P A R T M E N T P O W E R E X H A U S T R A I N H O O D ( o n R e t u r n A i r C o m p a r t m e n t ) E C O N O M I Z E R M O T O R I Z E D D A M P E R R A I N H O ...
Page 47 - FIGURE 8: FOUR AND SIX POINT LOADS
036-21410-001-A-0502 Unitary Products Group 47 FIGURE 8: FOUR AND SIX POINT LOADS A D C E B F A D B C TABLE 40: FOUR AND SIX POINT LOADS 180 Gas 2540 474 768 802 495 210 Gas 2928 510 954 954 510 240 Gas 2960 516 964 964 516 300 Gas 3046 531 992 992 531 180 Elec 2340 437 708 739 456 210 Elec 2728 476...
Page 48 - Ducts can be installed into the curb from the roof. All; FIGURE 9: UNIT ROOF CURB DIMENSIONS
036-21410-001-A-0502 48 Unitary Products Group 1. The 2” space between the ducts allows for “jumping” anexisting roof joist. 2. The 58-1/2” overall dimension of the ducts allows duct-work penetration between roof joists that are spaced on72” centers. NOTE: Ducts can be installed into the curb from t...
Page 49 - FIGURE 12: SIMPLICITY CONTROL WIRING DIAGRAM; SD
036-21410-001-A-0502 Unitary Products Group 49 FIGURE 12: SIMPLICITY CONTROL WIRING DIAGRAM W1 W2 Y1 G OCC P P1 Y2 X R SD C C SD SD R OCC C RC G Y2 Y1 W2 W1 Jumper Smoke Detector 24 VAC Class 2 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2...
Page 50 - GUIDE SPECIFICATIONS; GENERAL; UNIT CABINET
036-21410-001-A-0502 50 Unitary Products Group GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International UnitaryProducts Group in an ISO 9001 certified facility. York's Sunline Magnum™ units are convertible single pack-age units. All models have dual independent refrigerant cir-...
Page 51 - REFRIGERANT COMPONENTS
036-21410-001-A-0502 Unitary Products Group 51 bearings, internally protected against overload conditions andstaged independently. REFRIGERANT COMPONENTS Compressors: a. Shall be Scroll compressors internally protected withinternal high-pressure relief and over temperatureprotection. b. Shall have i...
Page 52 - Compressor 5 Years
036-21410-001-A-0502 52 Unitary Products Group UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125° Foutdoor temperature, exceeding maximum load criteria ofARI Standard 210/240. The compressor, with standardcontrols, shall be capable of operation down to 25° F outdoor...
Page 56 - by Unitary Products 2002. All rights reserved.
Subject to change without notice. Printed in U.S.A.Copyright © by Unitary Products 2002. All rights reserved. Supersedes: Nothing 036-21410-001-A-0502 Unitary 5005 Norman Products York OK Group Drive 73069