Page 2 - Features and Overview; O The pressure transducer is; High Alarm; Sump OFF; Low Alarm; Upper Limit of Display W

LVCN-302 Features and Overview Let's say your tank is 112 inches deep, and the transducer range of the sensor you’vechosen is 0-5 psi of water. 5 psi equals 138 inches H 2 O The pressure transducer is located 11 inches off the bottom of the tank. With 51 inches of water in the tank you arecavitating...

Page 3 - Security Levels / Selecting and Accessing Data; Programming Mode; Output & Input Terminal Connections; (All terminal connections are plug in Phoenix type); Output; Power Supply; Power Supply; Power Supply

Security Levels / Selecting and Accessing Data Operator access to data modifications has three modes of security: View Only, Set PointChanges Allowed and Programming. Each mode is selected from the back of the unit with a DIPswitch setting. ON 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1...

Page 4 - Initial Set-Up in Eight Easy Steps; psi water

1. - Setting the Transducer Range Press the SELECT button on the graphic face - RANG RANG RANG RANG RANG will appear in the display. A few seconds later, the display will convert to R___ . The Transducer Range of the input device needs to be entered, using the INCREASE orDECREASE arrow. The Transduc...