Omega LVCN-302 - Manual

Omega LVCN-302

Omega LVCN-302 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
Page: / 7

Table of Contents:

  • Page 2 – Features and Overview; O The pressure transducer is; High Alarm; Sump OFF; Low Alarm; Upper Limit of Display W
  • Page 3 – Security Levels / Selecting and Accessing Data; Programming Mode; Output & Input Terminal Connections; (All terminal connections are plug in Phoenix type); Output; Power Supply; Power Supply; Power Supply
  • Page 4 – Initial Set-Up in Eight Easy Steps; psi water
  • Page 5 – Sensor Input Connections / Schematics; Typical Form-C Relay Connection; External
  • Page 6 – Other Helpful Features of LVCN-302; message is displayed in the Actual Liquid
  • Page 7 – RETURN REQUESTS / INQUIRIES; Servicing North America:; OMEGAnet
Loading the manual

Displaying Your Tank’s Cross-Section

Security Levels / Select and Enter Data

Initial Set-Up / Eight Simple Steps
Sensor Connections / Schematics

Sending a 4-20 mA Signal to Other Devices

LVCN-302

Set-Up Manual for Sump Model

M3760/1201

MADE IN

User’s

Guide

Specifications:

Sensor Input: Isolated input accepts any type of 4-20 mA process signal. Loop power available up to

24VDC for 2 wire device

Input Power: 120VAC/900 mA; 24VDC unregulated/450 mA

Security Levels: 3 levels of access protect data changes with DIP switch on back

Control Circuits: Four Form C relays, 10.0 amp 125VAC (noninductive)

Switching Mode: Selectable, NO or NC states

Output & Input Connections: Terminal Connections are plug in Phoenix type

Programmed Memory: EEPROM - Loss of power will not affect existing programmed data

Mounting Format: Flush mounted anodized steel enclosure with eight (8) 10/32 studs and sealing

gasket; NEMA 4 graphic front panel; steel back pan housing.

Overall Dimensions: Tall: 16.75” (425 mm), Wide: 10.25” (250mm), Deep 2.25” (57mm),

Weight: 4.5 kg (10 lbs.)

LVCN-302 is a solid-state controller with a variety of unique control and display features. It’s designed to
simply present the crucial information, at a glance. It’s built to perform in all types of harsh industrial
environments as well as control alarms, pumps, solenoids, etc.

Topics covered in this manual

omega.com

®

®

®

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Features and Overview; O The pressure transducer is; High Alarm; Sump OFF; Low Alarm; Upper Limit of Display W

LVCN-302 Features and Overview Let's say your tank is 112 inches deep, and the transducer range of the sensor you’vechosen is 0-5 psi of water. 5 psi equals 138 inches H 2 O The pressure transducer is located 11 inches off the bottom of the tank. With 51 inches of water in the tank you arecavitating...

Page 3 - Security Levels / Selecting and Accessing Data; Programming Mode; Output & Input Terminal Connections; (All terminal connections are plug in Phoenix type); Output; Power Supply; Power Supply; Power Supply

Security Levels / Selecting and Accessing Data Operator access to data modifications has three modes of security: View Only, Set PointChanges Allowed and Programming. Each mode is selected from the back of the unit with a DIPswitch setting. ON 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1...

Page 4 - Initial Set-Up in Eight Easy Steps; psi water

1. - Setting the Transducer Range Press the SELECT button on the graphic face - RANG RANG RANG RANG RANG will appear in the display. A few seconds later, the display will convert to R___ . The Transducer Range of the input device needs to be entered, using the INCREASE orDECREASE arrow. The Transduc...

Other Omega Models

All Omega Other