Page 3 - ONTENTS
1. General Information and Features 2 2. Safety Considerations 3 3. Installation and Removal 4 3.1 Installation Clearance 5 3.2 Mounting on DIN Rail 6 3.3 Removal of Unit 7 4. Input and Output Connections 8 4.1 Block Diagram 8 4.2 Wiring for 115 Vac - Single Phase 9 4.3 Wiring for 230 Vac - Two Phas...
Page 4 - Features; ENERAL
The compact iDRN power supplies are designed tosupply well-regulated 24 volt DC power to sensors,signal conditioners, data acquisition systems andhigh level logic equipment. Significant iDRN features include:• Tested isolation, primary to output • Recessed live parts and connector screws • 35mm DIN ...
Page 7 - NSTALLATION AND
3.1 Installation Clearance Ensure that there is enough room for mounting the power supply unit. There should be a minimum of 1" [25mm] spacingto allow sufficient air circulation for proper cooling. Figure 3.1 — Mounting I NSTALLATION AND R EMOVAL 3 5 DC POWER OUT AC POWER IN DC POWER IN SIGNAL I...
Page 9 - Removal of Unit
3 7 3.3 Removal of Unit 1. Insert flat screw-driver into tab and push downwards.2. Unit will detach from DIN Rail. Figure 3.3 — Removal of Unit I NSTALLATION AND R EMOVAL
Page 10 - Block Diagram of Power Supply; Figure 4.1 — Block Diagram; Do not turn on the ac power to the power supply; NPUT AND
4 8 4.1 Block Diagram of Power Supply Figure 4.1 — Block Diagram 4.2 Wiring Warning: Do not turn on the ac power to the power supply unit until you have completed all output connections. Failureto do so may result in injury! This device must only be installed electrically by a specially trained elec...
Page 11 - 15Vac - Single phase power wiring; Figure 4.2— Wiring for 115Vac - Single Phase; Output Voltage; Input Power
4 9 I NPUT AND O UTPUT C ONNECTIONS 4.2 Wiring (Continued) 115Vac - Single phase power wiring Figure 4.2— Wiring for 115Vac - Single Phase L N + - Output Voltage (for shielded wireconnections, if necessary) Earth FUSE 1 LINE Switch N E U T R A L Earth Switch * * USE A SWITCH TO APPLY +24V POWER TO T...
Page 12 - 30Vac - Two phase power wiring; Figure 4.3— Wiring for 230Vac - Two Phase
4.3 Wiring (Continued) 230Vac - Two phase power wiring Figure 4.3— Wiring for 230Vac - Two Phase I NPUT AND O UTPUT C ONNECTIONS 4 10 L N + - Output Voltage (for shielded wireconnections, if necessary) Earth FUSE 1 L1 Switch L 2 Earth FUSE 2 Switch * * USE A SWITCH TO APPLY +24V POWER TO THE LOAD, I...
Page 13 - PECIFICATIONS; INPUT POWER; Front Panel LED
S PECIFICATIONS 5 11 INPUT POWER Input Voltage: 115 - 240Vac ±10% Frequency: 50/60 Hz Current: 0.400A @ 103Vac 0.190A @ 265Vac Overvoltage Protection: 275 Volt VaristorOvercurrent Protection: Fuse TR-5 800mA Time-lag / IEC 127-3Input Wattage: 26 Watts OUTPUT POWER Output Voltage: 24Vdc ±2% @ 850mA (...
Page 14 - GENERAL; Operating Temperature:; WIRE CONNECTIONS
S PECIFICATIONS 5 12 GENERAL Operating Temperature: 23° to 122°F(-5° to 50°C) Storage Temperature: -40° to 176°F(-40° to 80°C) Mounting: 35mm DIN Rail Size: Height: 3.55" (90mm) Width: 0.99" (25mm) Depth: 4.38" (111mm) Weight: 0.3 lbs. (0.14 kg) Equipment Type: CLASS I Overvoltage: CAT I...
Page 15 - IMENSIONS
Page 16 - Figure 6.2 — Temperature Derating Graph; MAXIMUM POWER OUTPUT; AC INPUT CURRENT @ 100VAC INPUT
I NPUT AC VOLTAGE / POWER OUTPUT 7 14 Example: If ambient is 50ºC, maximum wattage is 21W max. for120-265Vac. If unit is operated at 21W at an input voltage of 100V,the maximum ambient temperature allowed is 40ºC. Figure 6.2 — Temperature Derating Graph MAXIMUM POWER OUTPUT INPUT AC VOLTAGE AMBIENT ...
Page 17 - NOTES
Page 19 - USA
WARRANTY/ DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping ...
Page 20 - TEMPERATURE
M2540/0202 Where Do I Find Ever ything I Need for Process Measurement and Control? OMEGA…Of Course! Shop on line at www.omega.com TEMPERATURE Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies Wire: Thermocouple, RTD & Thermistor Calibrators & Ice Point References...