Honeywell VISTA-15P - Manuals
Honeywell VISTA-15P – Manual in PDF format online.
Manuals:
Manual Honeywell VISTA-15P
Summary
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscr...
Table Of Contents Features and Installation Highlights............................................................................................................1-1 Capabilities and Functions...............................................................................................................
Table Of Contents (continued) Data Field Programming .................................................................................................................................4-1 About Data Field Programming ........................................................................................
S E C T I O N 1 Features and Installation Highlights This manual applies to the following Honeywell security systems: ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred...
Compatible Devices Device VISTA-20P VISTA-15P Notes Addressable Keypads 8 8 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V Fixed-Word Display Voice Keypad, 6160V Alpha Display Voice Keypad, 6150RF Keypad/Transceiver Touch Screen (AUI) Devices 2 2 Touch Screen (AUI) devices are in addition to the 8...
S E C T I O N 2 Mounting and Wiring the Control Installing the Control Cabinet and PC Board Cabinet and Lock 1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet moun...
ANTENNA MOUNT (2 PLACES) ANTENNA (2) SCREW (2) BLACK MOUNTING CLIP RED MOUNTING CLIP WHITE MOUNTING CLIP GROUNDING LUG (2) NOTE A COMBINATION OF THESE MOUNTING CLIPS HAS BEENINCLUDED IN YOUR INSTALLATION KIT.USE THE APPROPRIATE CLIPS FOR MOUNTING. IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USINGE...
AC Power, Battery, and Ground Connections 1321 Transformer TO TERMINALS 1 AND 2 1321X10-001-V0 1 2 Connect the 1321 Transformer (1321CN in Canada) to terminals 1 and 2 on the control board. See Wire Run Chart for wire size to use. • Use caution when wiring the transformer to the control to guard aga...
Sounder (Bell) Connections Basic Connections spkr_conn-001-V0 ALARM OUTPUT 10.5 - 13.5 VDC 2A MAX. 3 4 Make sounder connections to alarm output terminals 3 (+) and 4 (–). • The 12VDC sounder output activates when an alarm occurs. • Total current drawn from this output cannot exceed 2 amps (going bey...
Keypad Notes ARMED READY 1 OF F 4 MA X 7 INST ANT REA DY 2 AW AY 5 TES T 8 CO DE 0 3 STA Y 6 BYP ASS 9 CH IME # Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Devices Addresses . See Keypad Programming Fields (fields *190-*196...
Hardwire Zones and Zone Expansion Hardwire Zones zones-001-V0 HI LO Normally Open Zones/ N.O. EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming m...
Smoke Detector Notes •••• Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control wil...
BRN GRN BLK (–) GROUND RED (+) 12VDC YEL 432 1 ZONES A B C D F G H DIP SWITCH FOR SETTING ADDRESSAND ZONE "A" RESPONSE TAMPER JUMPER POSITION 4229 IN CABINET(NOT TAMPER) 4229 REMOTE(TAMPER PROTECTED) TB1 4 2 2 9 TB2 WHT GR Y VIO BLK YEL ORG NO NC C GND NO NC C RLY 1 RLY 2 RELAYS OFF RELAY CO...
Installing a 5800TM Module • Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., 5883). • The 5800TM must be set to address 28 (cut red-W1 jumper). • The 5800TM can be used in par...
Installing a Keyswitch Keyswitch Connections GREEN RED 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone. 2. Using a standard keypad cable as shown: Connect the yellow and white keyswitch...
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers 4204/4229 Relay Modules UL For UL installation requirements, refer to the Installation Instructions for the 4204. 1. Mount either remotely or in the control panel. 2. Connect each module to the control’s keypad terminals and set...
On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. • If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1 cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section fo...
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections Phone Line Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors represent the colors of the cable to...
Audio Alarm Verification Connections (AAV, “listen-In”) • Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used. • Connections use one of the on-board triggers. • Set field *91 for AAV a...
S E C T I O N 3 Programming Overview About Programming • You can program the system at any time, even at the installer's premises prior to the actual installation. • Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass down...
Interactive Mode Programming ( ∗∗∗∗ 56, *57, ∗∗∗∗ 58, ∗∗∗∗ 79, ∗∗∗∗ 80, ∗∗∗∗ 81, ∗∗∗∗ 82) Entering Interactive Mode Press [ ∗ ] + [Interactive Mode No.] (for example, ∗ 56) while in Program Mode. The Alpha display keypad will display the first of a series of prompts. After making the appropriate ent...
S E C T I O N 4 Data Field Programming About Data Field Programming The following pages list this control’s data fields in numerical order. Valid entries for each field are shown in italics. Explanations and special notes are presented below the entries. Use the separate Programming Guide to record ...
*32 Fire Alarm Sounder Timeout 0 = yes; sounder timeout after time selected in field ∗ 33 1 = no timeout; sounds until manually turned off This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of th...
System Status Report Codes Zone report codes are programmed using interactive ✱ 56 or ✱ 58 Zone Programming modes, while system status (non-alarm) codes and restore codes are entered in data fields *59 - *68, *70 - *76, *89. The actual report code digits that you enter depend upon the particular ins...
*69 Recent Closing Report V20PSIA/V15PSIA only Always enabled. Field does not apply to other controls. Similar to the Exit Error condition described in field *59, but occurs if an entry/exit door or interior zone is faulted within two minutes after the initial exit delay expires. Disarming the syste...
*87 Misc. Fault Delay Time 0 = 15 secs 4 = 90 secs 8 = 4 min #+12 = 8 min 1 = 30 secs 5 = 2 min 9 = 5 min #+13 = 10 min 2 = 45 secs 6 = 2-1/2 min #+10 = 6 min #+14 = 12 min 3 = 60 secs 7 = 3 min #+11 = 7 min #+15 = 15 min Used with zones assigned to a configurable zone type with fault delay on (conf...
*93 No. of Reports In Armed Period per Zone (Swinger Suppression) 0 = unlimited number of reports 1 = 1 report pair per zone per armed period 2 = 2 report pairs per zone per armed period Selection limits the number of alarm/alarm restore message pairs per zone sent to the CS in an armed period. SIA ...
Configurable Zone Type Fields • The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90, 91]), based on the options described at right. • All configurable zone types can be programmed via the downloader. • Configurable zone types 90 and 9...
Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL RF zone normal Open RF zone N/A Shorted RF zn off-normal Auto Restore Vent Zone 0 = normal 1 = alarm 2 = trouble 3 = fault 0 = normal 4 = alarm 8 = trouble 12 = fault see note 5 0 = normal 1 = alarm 2...
Touch Screen Keypad (AUI) Enable The system supports up to two touch screen style keypads (e.g., Symphony Advanced User Interface (AUI), and 6270 Touch Screen keypad. NOTE: Use of touch screen devices does not affect the number of standard keypads supported. *189 AUI Device 1 and 2 Enable VISTA-20P:...
S E C T I O N 5 Menu Mode Programming Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or ✱ 58 Expert Programming Mode. The VISTA-20P system can control two independent areas of protection (known as partitions) for use by indepe...
Enter Zn Num. (00 = Quit) 10 Zone Number VISTA-20P: wired 01-08 (and 09-48†); wireless 09-48; RF button zones 49-64 VISTA-15P: wired 01-06 (and 07-22†); wireless 09-34; RF button zones 49-56 Both Controls: 91 = addr. device report enable; 92 = duress report enable 95, 96, 99 =emerg. zones [ ∗ ] to c...
10 INPUT TYPE RF TRANS 3 Input Device type (In) 2 = AW (Aux wired zone) 3 = RF (supervised RF transmitter 4 = UR (unsupervised RF transmitter) 5 = Button type RF transmitter (unsupervised). [ ∗ ] to continue This prompt is skipped for zones 2-8, or 2-16 if zone-doubling was enabled at “Hardwire Type...
E n t d A 0 2 2 - 4 0 6 3 1 R c v d A 0 2 2 - 4 0 6 4 1 If Serial or Loop Numbers do not match after activating the transmitter [ ∗ ] to continue If the serial number transmitted does not match the serial number entered, a display similar to the one shown appears. If the loop number does not match, ...
Zn ZT P RC HW: RT 01 09 1 10 EL 1 Zn ZT P RC IN: L 10 00 1 10 :RF – Summary Screen 01-64 = zone number; [ ∗ ] to continue; 00 = quit OR [D] to go to prompts for wireless key programming templates A summary screen appears, showing zone 1’s currently programmed values. Enter the zone number being prog...
Entd A022-4063 Rcvd A022-4064 If Serial or Loop Numbers do not match after activating the transmitter [ ∗ ] to continue I f the serial/loop number combination transmitted does not match the serial and loop number entered, a display similar to the one below will appear. If the loop number does not ma...
XMIT TO CONFIRM PRESS ✱ TO SKIP Confirm [ ∗ ] to continue • If “Yes” was entered at the SET TO CONFIRM? prompt previously (see first prompt following entry into the ∗ 58 Expert Programming Mode), the display on the left will appear. Confirm serial and loop numbers by activating the wireless key. IMP...
About Output Device Programming (*79/*80 Menu Mode) Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mo...
Start Output Device Mapping by pressing *79 while in Data Programming Mode. ∗∗∗∗ 79 Menu Mode ENTER OUTPUT NO. 00 = QUIT xx Device Output Number 01-18 = VISTA-20P relays/X-10; 01-08, 17, 18 = VISTA-15P relays/X-10 [ ∗ ] to continue; 00 to quit This is the logical (or reference) relay number as used ...
*80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an o...
“ A ” 01 Zn List 1 Zone List (prompt appears if zone list was selected) 01-08 = zone list; [ ∗ ] to continue Enter the desired zone list number associated with this output number. NOTE: Do not use pager zone lists 09-12 in output definitions. Enter the zone list event that will activate this output....
Enter Output No. R02 02 Output Number 01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = on-board triggers Enter the device output number (programmed in *79 Menu Mode) you want associated with this output. Press [ ✱ ] to continue. 02 A E P TRIG R02 1 1 3 ZL=00 Summary Screen A summa...
About Function Keys (*57 Menu Mode) The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions (listed below) i...
About Descriptor Programming (*82 Menu Mode) The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memory (see a follo...
✱ Z N 0 1 B A C K Accept First Word 6 = save word and go to next word in this descriptor; 8 = save word and go to next zone Press [6] to accept the selected word and continue to the next word, or press [8] if this is the only word you are using for the descriptor. ✱ Z N 0 1 B A C K D O O R Second 3-...
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 (Word Space) – A – • 001 AIR • 002 ALARM ∗∗∗∗ 004 ALLEY 005 AMBUSH • 006 AREA • 007 APARTMENT • 009 ATTIC ∗∗∗∗ 010 AUDIO – B – • 012 BABY ∗∗∗∗ • 013 BACK ∗∗∗∗ • 014 BAR • 016 BASEMENT ∗∗∗∗ • 017 BATHROOM ∗∗∗∗ • 018 BED • 019 BEDROOM ∗∗∗∗ 020 ...
Programming Installer and User Schedules The system provides schedules, which can be used to automatically control 11 types of system events at pre-defined times. Some events are reserved for the installer only. VISTA-20P: Provides up to 32 schedules: 16 schedules for use by the end-user, 16 for use...
S T O P S M T W T F S H H M M A M 0 0 1 0 0 0 0 Stop Time (For events 01-relay on/off; 02-user access; 03-latch key report) 01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; Days = place “1” under days Press [ ∗ ] to continue. Enter the event’s stop time and days of the week to occur. To select days, po...
S E C T I O N 6 System Communication and Operation Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between ...
Ademco Contact ID ® The Ademco Contact ID ® Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected). 1-digit event qualifier (“new” or “restore”). 3-digit event code. 2-digit Partition No. 3-digit zone number, user number, or system status numbe...
System Security Codes The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of the system. These codes can each be assigned one of 5 authority levels, which determine the functions each code can perform as listed in the table below. ...
Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI) User’s Guide. Voice Keypads The 6150V/6160V Voice Keypads provide ...
SUMMARY OF ARMING MODES Features for Each Arming Mode Arming Mode Exit Delay Entry Delay Perimeter Armed Interior Armed AWAY Yes Yes Yes Yes STAY Yes Yes Yes No NIGHT-STAY Yes Yes Yes only those zones listed in Night- Stay zone list INSTANT Yes No Yes No MAXIMUM Yes No Yes Yes Panic Keys There are t...
Various System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED CA will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time. The alarm sounder and ke...
S E C T I O N 7 Testing the System About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system responds to faults. Dialer Test: Checks that the phone connection to the central station...
NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared from the display. This also applies to 5816 and 5817 transmitters, which have multiple lo...
S E C T I O N 8 Specifications & Accessories Security Control 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Vo...
2-Wire Smoke Detector: Detector Type System Sensor Model No. Photoelectric w/heat sensor, direct wire 2300TB Photoelectric, direct wire 2400 Photoelectric w/heat sensor, direct wire 2400TH Photoelectric 2451 w/B401B base Photoelectric w/heat sensor 2451TH w/B401B base Ionization, direct wire 1400 Io...
5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). 5802MN ENROLL AS "UR&...
Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description 5817 Multi-Point Universal Transmitter RF Has three unique input (loop) codes: one for a “Primary” contact loop with programmable options; the others for two “auxiliary” closed circuit contact loops. 5818 Rece...
S E C T I O N 9 Regulatory Agency Statements RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device mus...
UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ✱ 35, ✱ 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds. 2. F...
S E C T I O N 1 0 Limitations and Warranty WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compr...
– INDEX – 1-9 1321 AC Transformer ...... 1-2, 2-3, 2-11 1361X10 ................. 2-3, 2-11, 2-12, 8-2 24-Hour Audible Alarm .................... 3-3 24-Hour Auxiliary Alarm ................... 3-3 24-Hour Silent Alarm ....................... 3-3 3+1 and 4+1 Standard Formats ..... 6-1 42041-2, 2-2, ...
CLASS 2 PLUG-IN TRANSFORMER 16.5V A C , 25V A (e .g. ADEMCO No . 1321). (USE No . 1321CN IN CANAD A) T O 110V A C UNSWITCHED OUTLET (24HR) + THIS EQ UIPMENT SHOULD BE INST ALLED IN A CCORD ANCE WITH THE NA TIONAL FIRE PR O TECTION ASSOCIA T ION'S ST AND ARD 72, CHAPTER 2 (NA T IONAL FIRE PR O T EC...
LIMITED WARRANTY Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and wor...
Honeywell Manuals
-
Honeywell DT8050A
Installation Manual
-
Honeywell DT8050A
Manual
-
Honeywell DT8050A
User Manual
-
Honeywell DT8050
Manual
-
Honeywell DT8050
User Manual
-
Honeywell TPFIT25WK
User Manual
-
Honeywell TPFIT25AWK
User Manual
-
Honeywell TPFIT32WK
User Manual
-
Honeywell TPFIT32AWK
User Manual
-
Honeywell 24DX47
User Manual
-
Honeywell 24DX47
Manual
-
Honeywell TPFIT50PWK
User Manual
-
Honeywell TPFIT50WK
User Manual
-
Honeywell TPFIT50AWK
User Manual
-
Honeywell TPFIT50APWK
User Manual
-
Honeywell 00010
User Manual
-
Honeywell ADVBLEWIFI
Manual
-
Honeywell ADVBLEWIFI
User Manual
-
Honeywell ADVBLE
Manual
-
Honeywell ADVBLE
User Manual