Page 2 - continued; Physical Description
51-52-03-27Page 2 Features/Options, continued Auxiliary Output* (Optional)—Thisisolated Auxiliary Output can bescaled from 4-20 mA for 0 to 100%for any range. It can be configured torepresent Input 1, Input 2, PV, activeSetpoint, Local SP1, Deviation, orthe Control Output.. Communications* (Optional...
Page 4 - Keys; F - °Fahrenheit being used; Figure 2—Operator Interface; Operator Interface; Indicator model uses the; Eight keys enable complete configuration and operation; Figure 3—Key Functions
51-52-03-27Page 4 ALM OUT PV F FUNCTION AUTOTUNE MAN-AUTO RESET SET UP RUN HOLD ALM - Alarmconditions exist OUT - ControlRelay1 or 2 on Keys - SeeFigure 3 C R L 1 21 2 SP 2300 2300 DISPLAY M A M or A - Manual/Auto display F - °Fahrenheit being used C - °Centigrade being used R - Remote or Local SP2 ...
Page 5 - Specifications; Design; Inputs sampled six times a second
51-52-03-27 Page 5 Specifications Design CE Conformity (Europe) This product is in conformity with the protection requirements of the followingEuropean Council Directives: 73/23/EEC, the Low Voltage Directive, and89/336/EEC, the EMC Directive. Conformity of this product with any other “CEMark” Direc...
Page 6 - Specifications, continued; Socketed jumper assembly replaces relay.; Controller Output Algorithms; Time Proportional Relay Resolution: 3.3 msec; Input Filter
51-52-03-27Page 6 Specifications, continued Design (continued) Controller Output Types (continued) Electromechanical Relays (One or Two)SPDT contacts. Both Normally Open and Normally Closed contacts are broughtout to the rear terminals. Internally socketedResistive Load: 5 amps @ 120 Vac or 30Vdc, 2...
Page 7 - 0A maximum for 4 ms (under operating conditions); When applying power to more than one UDC 2300, make sure that
51-52-03-27 Page 7 Specifications, continued Design (continued) Auxiliary Linear Output (Optional) (Isolated) 21 mA dc maximum into a negative or positive grounded load or non-groundedload of 0 to 500 ohms.Output range can be set anywhere between 0 to 21 mA, and as direct or reverseaction. It can be...
Page 8 - Environmental and Operating Conditions; Table 1—Input Actuations; Honeywell Radiamatic; Linear
51-52-03-27Page 8 Specifications, continued Environmental and Operating Conditions Parameter Reference Rated Operative Limits Transportation and Storage Ambient Temperature 25 ± 3°C77 ± 5°F 0 to 55°C32 to 131°F 0 to 60°C32 to 140°F –40 to 66°C–40 to 151°F Relative Humidity 10 to 55* 10 to 90* 5 to 9...
Page 9 - = Rear Terminal Cover
51-52-03-27 Page 9 General Reference Data Isolation(Functional) Analog Inputs : are isolated from all other circuits at 850Vdc for 2 seconds, but not from each other.Analog Outputs : are isolated from all other circuits at 850Vdc for 2 seconds.AC Power : is electrically isolated from all other input...
Page 10 - Dimensions; Panel Cutout; rear cover; Figure 5—UDC 2300 Controller Dimensions – not to scale
51-52-03-27Page 10 Dimensions 96 3.780 96 3.780 Panel Cutout 90 =0.0 +0.8 3.5906 +0.03 24 .945 Max PanelThickness 10 .394 Max (2) 4.19 105.4 FUNCTION DISPLAY MAN-AUTO RESET SET UP AUTOTUNE RUN HOLD 1 2 F C MA 1 2 ALM OUT .103 2.62 with optional rear cover 90.73.57 21.0 .826 RL Dimensions: Millimeter...
Page 11 - Wiring Diagram; OP TIO N; Figure 6—External Wiring Diagram; Ordering Information; Pressure Transmitters,; Specifications are subject to change
51-52-03-27 Page 11 Wiring Diagram 8 7 6 5 4 L2/ N L1 IN1 C TL14 -2 0 mA 90- 2 64V ~ ALM2 C TL2 ALM1 OP TIO N IN2 9 10 11 12 13 14 15 16 + - + + + - - - } { { { { R 248 65 Figure 6—External Wiring Diagram Ordering Information For the complete ordering information, request Model Selection Guide 51-51...
Page 12 - Industrial Automation and Control
51-52-03-27Page 12 Distributor : For more information, contact your nearest Honeywell Response Center listed below. Industrial Automation and Control Honeywell Inc. In the U.S.A.: Honeywell Industrial Automation and Control, 16404 North Black Canyon Hwy., Phoenix, AZ 85023, (800) 343-0228 In Europe:...