Page 2 - SPECIFICATIONS • ORDERING INFORMATION; Ordering Information; Specifications; IMPORTANT: The specifications given in this publica-
68-0148—1 2 T8131A,B,C; T8132A,B,C SPECIFICATIONS • ORDERING INFORMATION Ordering Information When purchasing replacement and modernization products form your TRADELINE ® wholesaler or your distributor, refer to the TRADELINE Catalog or price sheets for complete ordering information, or specify— 1. ...
Page 3 - SPECIFICATIONS • INSTALLATION; Installation; WHEN INSTALLING THIS PRODUCT...; Heat pumps/Multistage Equipment; WARNING; LOCATION
3 68-0148—1 T8131A,B,C; T8132A,B,C SPECIFICATIONS • INSTALLATION Fig. 2—T8131 LED. CYCLES PER HOUR ADJUSTMENT: Heating: Field adjustable to 3, 6, or 9 cph ±10 percent.Cooling: Factory-set at 3 cph ±10 percent (not field adjustable). CALIBRATION: Thermostat and thermometer self-cali- brating to ±1.25...
Page 4 - Fig. 3—Mounting thermostat mounting plate.; INSTALLATION; WIRING
68-0148—1 4 Fig. 3—Mounting thermostat mounting plate. T8131A,B,C; T8132A,B,C INSTALLATION WALL WIRES THROUGHWALL OPENING WALLANCHORS (2) MOUNTINGPLATE MOUNTINGSCREWS (2) M1718 WIRING All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow instructionsprovide...
Page 6 - INSTALL BATTERIES; IMPORTANT: All T8132 models require batteries for
68-0148—1 6 ADJUST FAN OPERATION SWITCH, ASREQUIRED The thermostat fan operation switch, labeled FUEL SWITCH (see Fig. 12) is factory-set in the “F” position.This is the correct setting for most systems. If this system is an electric heat system, set the switch to “E.” The “E”setting will allow the ...
Page 7 - Fig. 14—Installing position for batteries.; MOUNTING THE THERMOSTAT; To mount the thermostat on the subbase, engage the tabs; Fig. 15—Mounting the thermostat on the subbase.; IMPORTANT: Although the thermostat has a low battery
7 68-0148—1 T8131A,B,C; T8132A,B,C INSTALLATION M1719C REMOVINGBATTERYDOOR Fig. 14—Installing position for batteries. MOUNTING THE THERMOSTAT To mount the thermostat on the subbase, engage the tabs at the top of the thermostat and mounting plate (see Fig. 14)and then press the lower edge of the case...
Page 8 - PROGRAMMING THE THERMOSTAT; Programming the Thermostat
68-0148—1 8 T8131A,B,C; T8132A,B,C PROGRAMMING THE THERMOSTAT Programming the Thermostat T8131A AND T8132A MODELSSet Current Time/Day To set time, press and release Set Clock/Day once, then press Ahead or Back until the current time displays. To setday, press and release Set Clock/Day again, and the...
Page 10 - CHECKOUT AND SETTINGS; Checkout and Settings; CHECKOUT
68-0148—1 10 T8131A,B,C; T8132A,B,C CHECKOUT AND SETTINGS Checkout and Settings CHECKOUT After the thermostat is mounted on the subbase, check operation as follows: Model Heating A,C B For T8131 models only, first check that the green power LED is lit, indicating thethermostat is powered properly. D...
Page 11 - CHECKOUT AND SETTINGS • TROUBLESHOOTING; Troubleshooting; IF...; Display will not come on.
11 68-0148—1 T8131A,B,C; T8132A,B,C CHECKOUT AND SETTINGS • TROUBLESHOOTING SETTINGS AND ADJUSTMENTSSet the Fan and System SwitchesFirst set the fan switch FAN AUTO: Normal setting for most homes. A single-speed fan will turn on automatically with the air conditioner orfurnace. A two-speed fan will ...
Page 12 - TROUBLESHOOTING • CROSS REFERENCE; Cross Reference
68-0148—1 12 Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, OntarioM1P 2V9 Printed in U.S.A. QUALITY IS KEY Cooling will not come on...