Page 2 - Installation Guide; TablE Of CONTENTs; Read and save these instructions.; For assistance with this product please visit
Installation Guide 69-2200—0 TablE Of CONTENTs Read and save these instructions. Need Help? For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Zoning Hotline toll-free at 1-800-828-8367 ® U.S. Registered Trademark. Patents pending. Copyright © 2008 Honeywel...
Page 3 - spECifiCaTiONs aNd aCCEssOriEs
HZ22 TrueZONE 69-2200—0 spECifiCaTiONs aNd aCCEssOriEs Input Ratings: Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more. Current Draw: Zone Panel: 6.25 VA max.All VA specifications at 24 VAC. Wiring: 18–20-gauge solid (not stranded) wire. Humidity Ratings: 5% to 90% RH non-condensing. Tempera...
Page 4 - iNsTallaTiON
Installation Guide 69-2200—0 2 69-2200—0 iNsTallaTiON Mount the HZ221 TrueZONE panel near the HVAC equip-ment; locate it on a wall, stud, roof truss, or cold-air return. NOTE: The HZ221 TrueZONE panel can be mounted in any orientation; level it for appearance only. 1 DATS M28164 SUPPLY DUCT RETURN D...
Page 5 - WiriNg; Multiple dampers can be wired in; Connect DATS as shown.
69-2200—0 2 HZ22 TrueZONE 69-2200—0 WiriNg Install thermostats using instructions provided with thermostats.Connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To release wire, press the button on top of the terminal....
Page 6 - Connect transformer as shown.
Installation Guide 69-2200—0 69-2200—0 The DS/BK terminal is used with a variable-speed fan. Connect to the DS, BK, or ODD terminal on the furnace equipment. When only one zone calls for heat, cool, or fan, the DS/BK terminal operates the fan at low speed to reduce airflow. 7 Connect transformer as ...
Page 7 - OpEraTiON; LED; Rh
69-2200—0 HZ22 TrueZONE 69-2200—0 The HZ221 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information. OpEraTiON HZ221 HEAT COOL FAN PURGE ZONE 1 ZONE 2 EM HEAT M28239A LED display. Table 5. LED Operation. LED Description HEAT Solid ...
Page 8 - Automation and Control Solutions; WarraNTy
Honeywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.com Automation and Control Solutions Honeywell Limited-Honeywell Limitée35 Dynamic DriveToronto, Ontario M1V 4Z9 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. ® U.S...