Page 2 - CAUTION; Disconnect power before beginning installation.
2 Read and save these instructions. Introduction The T6 Pro Z-Wave Programmable Thermostat is a Z-Wave Plus certified thermostat capable of controlling up to three heat and two cool stages of heat pump, (incl. dual fuel heat pump systems) and up to two heat and two cool stages of conventional system...
Page 3 - UWP Mounting System installation; Drill holes at marked positions, and; Optional Decorative Cover Plate installation; Optional Cover Plate
3 UWP Mounting System installation 1. Open package to find the UWP. See Figure 1. 2. Position the UWP on the wall. Level and mark hole positions. See Figure 2. Drill holes at marked positions, and then lightly tap supplied wall anchors into wall using a hammer. ‒ Drill 7/32” holes for drywall. 3. Pu...
Page 4 - Wiring UWP; Gently tug on the wires to verify; Power options
4 Wiring UWP Push down on the tabs to put the wires into the inner holes of their corresponding termi nals on the UWP (one wire per terminal) until they are firmly in place. Gently tug on the wires to verify they are secure. If you need to release the wires again, push down the terminal tabs on the ...
Page 5 - Wiring terminal designations; Setting Slider Tabs; UWP Mounting System
5 Wiring terminal designations S Input for wired indoor or outdoor sensors L /A - A Heat Pump fault input (C wire required) S O/B Changeover valve Y Compressor contactor (stage 1) AUX - W2 Auxiliary heat relay Heat relay (stage 2) Y2 Compressor contactor (stage 2) E Emergency Heat relay G Fan Relay ...
Page 6 - Wiring conventional systems: forced air and hydronics; Heat-only System with Fan
6 Wiring conventional systems: forced air and hydronics NOTES: • Available wiring configurations may differ by product models/product numbers. • Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required. [1] Power supply. Provide disconnect means and overload protectio...
Page 7 - Wiring heat pump systems; NOT
7 1H/1C Heat Pump SystemR Power [1] Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor C 24 VAC common [3] O/B Changeover valve [7] G Fan relay 2H/1C Heat Pump System [8] R Power [1] Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor C 24 VAC common [3] O/B Changeover valve [7] G Fan r...
Page 8 - START SETUP; Edit ISU; View ISU
8 Mounting thermostat 1 Push excess wire back into the wall opening. 2 Close the UWP door. It should remain closed without bulging. 3 Align the UWP with the thermostat, and push gently until the thermostat snaps in place. 4 If needed, gently pull to remove the thermostat from the UWP. 5 Turn the pow...
Page 10 - Z-Wave connection status; ADVANCED; Advanced Z-Wave temperature reporting
10 Z-Wave connection status is located in the upper-right corner of the screen. • Thermostat is included and connected to a Z-Wave network. • Thermostat is excluded from a Z-Wave network. • Thermostat is either included in a Z-Wave network but the Z-Wave signal is lost, or is included but AC power i...
Page 11 - System operation setting
11 1 Press the Mode button to cycle to the next available System mode. 2 Cycle through the modes until the required System mode is displayed and leave it to activate. System modes: • Heat: Controls the heating system. • Cool: Controls the cooling system. • Off: Turns the heating and cooling systems ...
Page 12 - Scheduling options; Common for all days.; See table below with default, adjustable settings:; Thermostat schedule is turned; • Away mode is an Energy saving mode adjustable in the thermostat; AWAY SET TING
12 Scheduling options This thermostat may be configured to be programmable or non programmable. Thermostat schedule is an optional menu item. It will only show up in the thermostat menu if enabled in the Installer setup – advanced menu. It provides setting for local thermostat schedule control.Once ...
Page 13 - thermostat schedule is enabled. This setting is accessed from; INSTALLER; thermostat; INSTALLER SETUP – ADVANCED; Thermostat schedule is; adjustable in thermostat
13 See table below with default 5+2 schedule (Mon-Fri; Sat-Sun), adjustable settings: Thermostat schedule is turned ON , thermostat included in Z-Wave network Period Start Time Heat (Mon-Fri) Cool (Mon-Fri) Heat (Sat-Sun) Cool (Sat-Sun) Away N/A* 62 ° 85 ° 62 ° 85 ° Home 6:00 Am 70 ° 78 ° 70 ° 78 ° ...
Page 14 - Installer setup – advanced menu; Advanced menu options; Key features; of Menu button
14 Installer setup – advanced menu To access the advanced menu, press and hold the Menu button for 5 seconds . Touch or to go through the options in the advanced menu. Advanced menu options Device Setup This is used to access the device ISU setting. Screen Lock The thermostat touch screen can be loc...
Page 15 - Installer setup options (ISU) – advanced menu; ot; ISU options av
15 Installer setup options (ISU) – advanced menu N ot e: ISU options av ail able may v ar y upon the thermos tat model and eq uipment setup. Table 1. # I SU IS U N am e IS U O pt io ns ( de fa ul ts i n b ol d) No te s 120 Sc he du le Ty pe No S ch ed ul e o r O cc up an cy ( wh en i nc lu de d i n ...
Page 20 - Viewing equipment status
20 If your gateway/hub/controller supports configuration function, you may remotely configure or change the default thermostat configuration parameters. For detailed table with all available Z-Wave configuration parameters go to http://customer.resideo.com or search for T6 Pro Z-Wave Thermostat in t...
Page 21 - Number Alert/Reminder Definition; Alerts and reminders
21 Number Alert/Reminder Definition 54 Thermostat Humidity Sensor Error The sensor of the thermostat has encountered an error. Please contact dealer to replace the thermostat. 164 Heat Pump Needs Service Heat pump needs service. Contact dealer to diagnose and service heat pump. 170 Internal Memory E...
Page 22 - Troubleshooting
22 Alerts and reminders Number Alert/Reminder Definition 252 AC Power Lost If batteries used as backup power it would drain batteries quickly so Z-Wave communication needs to be turned off. The working power mode can only be changed when thermostat is NOT included in a Z-Wave network. Either to excl...
Page 23 - Specifications
23 Specifications Model Number: TH6320Z W2003 Model Name: T6 Pro Z-Wave Thermostat Model Description: Programmable Z-Wave thermostat with touchscreen Stages: Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional Power Requirements Batter y power: A A alkaline batter y 3pcs. C-wire input...
Page 24 - Regulatory information; -year limited warranty
Resideo Inc., 1985 Douglas Drive North Golden Valley, MN 55422 www.resideo.com 33-00294—07 M.S. Rev. 04-19 | Printed in United States This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502©2019 Resideo Technologies, Inc. The Honeywell Home trademark is used und...