Page 2 - COMPATIBILITY; TIPS AND THINGS YOU NEED TO KNOW
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 2 COMPATIBILITY Honeywell TB7600 Series thermostat compatiblity information is provided in Table 1. Table 1. TB7600 Thermostat Compatibility Information * 128 total devices supported. One node used by controller and one for a repeate...
Page 3 - WIRING GUIDELINES; Overview
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 3 63-4523—02 WIRING GUIDELINES Overview Honeywell uses EIA-485 as the physical layer between their devices and supervisory controllers For clarity we will use the term “Device” to represent any product with an active EIA-485 network connection,...
Page 4 - NETWORK CONFIGURATION; Maximum Number of Devices
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 4 NETWORK CONFIGURATION EIA-485 networks use a daisy chain configuration. A daisy chain means that there is only one main cable and every network device is connected directly along its path. Fig. 1 illustrates two improper network co...
Page 5 - Maximum Cable Length
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 5 63-4523—02 Maximum Cable Length The maximum length of a chain is related to its transmission speed. The longer the chain, the slower the speed. Using proper cable, the maximum length of an EIA-485 daisy chain is 4000-ft (1200 m). This will on...
Page 6 - NETWORK ADAPTER
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 6 End Of Line (EOL) Resistors MS/TP network must be properly terminated. For daisy chain configurations, you must install an EOL resistor at each end of the daisy chain. Depending on your MS/TP network configuration, the resistance v...
Page 7 - Network Adapter Status LED
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 7 63-4523—02 Network Adapter Status LED Table 3 shows the different possibilities with the Status LED behavior of the BACnet module. Table 3. Status LED condition and possible solutions Condition of the Status LED Possible Cause Solution 1 shor...
Page 8 - INTEGRATION; Global Commands
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 8 INTEGRATION This section provides compatibility and programming information useful when setting up TB7600 Series thermostats on a WEBs- AX building automation system. Global Commands The following figure shows which objects from th...
Page 9 - Typical Graphical User Interface (GUI) Objects
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 9 63-4523—02 Typical Graphical User Interface (GUI) Objects The following objects should be typically used in a GUI: • Room Temperature (AV7); • Occupied and Unoccupied Heat Setpoints (AV 42 and AV44); • Occupied and Unoccupied Cool Setpoints (...
Page 10 - Recommended Configuration Objects; Graphical interfaces
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 10 Recommended Configuration Objects The following objects and group objects should be typically used for configuration purposes. If your BAS allows you to remove objects from your database, Honeywell recommends removing all configur...
Page 11 - Free programmed object or loops; Retries and Timeouts
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 11 63-4523—02 Free programmed object or loops As for the application program, you might want to read and write any MS/TP data on an “If Once” basis or a “Do Every” loop basis instead of reading or writing to a 3 rd party device’s object directl...
Page 12 - TROUBLESHOOTING
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 12 TROUBLESHOOTING Error / Trouble Condition Possible Cause Solution Thermostat does not come online Two or more controllers have the same MAC address. Modify each duplicate address to a unique number. The MS/TP network has too many ...
Page 13 - APPENDIX A: BACNET OBJECTS; Product Description
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 13 63-4523—02 APPENDIX A: BACNET OBJECTS TB7600 SERIES PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS) Vendor Name: Honeywell Vendor ID: 140 Product Name: TB7600 Thermostat Series Product Model Number: TB7600A5x14B, TB7614B5x 14B, TB7605B5...
Page 14 - BACNET OBJECTS SUPPORTED; Device Objects
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 14 BACNET OBJECTS SUPPORTED Device Objects Table 4. Device Objects Object Name Type and Instance Object Property Thermostat Parameter TB76xxX5x14B Device Object_Identifier Property 75 (R,W) Unique ID number of a device on a network O...
Page 15 - Objects Table
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 15 63-4523—02 Objects Table Table 5. Objects Object Name Type and Instance Object Property T B 7600A5x 14B T B 7652A5x 14B T B 7600B5x 14B T B 7652B5x 14B T B 7605B5x 14B T B 7656B5x 14B T B 7607B5x 14B T B 7657B5x 14B T B 7600H5x 14B T B 7652H...
Page 18 - Standard Object Types Supported
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 18 Standard Object Types Supported Table 6. Standard Object Types Supported a The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value if written is not derived from the applicatio...
Page 19 - Property Value Range Restrictions for AI and AV objects
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 19 63-4523—02 Property Value Range Restrictions for AI and AV objects Table 8. Property Value Range Restrictions for AI and AV objects Object name Object Type and instance Under range value Over range value Default value Room Temperature AV 7 -...
Page 20 - List of Property Enumeration Sets for BI and BV objects
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 63-4523—02 20 List of Property Enumeration Sets for BI and BV objects Table 9. List of Property Enumeration Sets for BI and BV objects Object Name Object Type and instance Inactive_Text Active_Text Default value Room Temp Override BV 8 Normal O...
Page 21 - Property Enumeration Sets for MV Objects
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 21 63-4523—02 Property Enumeration Sets for MV Objects Table 10. Property Enumeration Sets for MV Objects Object Name Object Type and instance BACnet Index Text Default value Occupancy Command MV12 1 Local Occupancy Local Occupancy 2 Occupied 3...