Page 2 - INSTALLATION; When Installing this Product...; WARNING; Heat; Mounting Auxiliary Controls
69-1174 2 S8701/S8702 DIRECT SPARK IGNITION CONTROLS a Valve used must be designed for DSI application. b Separate spark igniter and flame sensor mounted on a common bracket. INSTALLATION When Installing this Product… 1. Read these instructions carefully. Failure to follow them could damage the prod...
Page 3 - Wiring; General Precautions
69-1174 3 S8701/S8702 DIRECT SPARK IGNITION CONTROLS RMS Temperature Rating Cable Type Voltage Rating ° F ° C UL Style 3257 10,000 482 250 Table 4. Transformer Ratings for S8701/S8702 and Dual Valve Combination Gas Controls. Wiring the S8701/S8702 Control 1. Connect system components to the S8701/S8...
Page 4 - STARTUP AND CHECKOUT; Gas Leak Test; START SYSTEM
69-1174 4 S8701/S8702 DIRECT SPARK IGNITION CONTROLS Fig. 3. S8702 Wiring Diagram. Grounding the S8701/S8702 Spark Igniter andMain Burner For the system to operate properly, spark igniter, flamesensor bracket, the burner (GND) terminal on the 24V(GND) terminal, and the S8701/S8702 control must share...
Page 5 - Check Trial for Ignition; CHECKOUT; Sequence of Operation
69-1174 5 S8701/S8702 DIRECT SPARK IGNITION CONTROLS NOTE: If the gas control has been replaced or serviced,lightoff may not be satisfactory until air has beenpurged from the gas line or the gas input andcombustion air have been adjusted (seemanufacturer’s instructions). Table 6. Trial for Ignition ...
Page 7 - SERVICE; Preliminary Check; START
69-1174 7 S8701/S8702 DIRECT SPARK IGNITION CONTROLS Fig. 5. S8701/S8702 Sequence of Operation for Retry Models (E, F, L and M Models). SERVICE IMPORTANT 1. Only persons trained and experienced in DSI systems should service this equipment. 2. If a condition exists that causes the S8701 or S8702 cont...
Page 8 - Spark Ignition Circuit; Ignition Cable
69-1174 8 S8701/S8702 DIRECT SPARK IGNITION CONTROLS 6. Check the flame sensor and its mounting bracket. Correct the position if bent out of shape. 7. Review the S8701/S8702 normal sequence of operation. See START SYSTEM section. S8701/S8702 COMPONENT CHECKS Spark Ignition Circuit The step-up transf...
Page 9 - Low or Unsteady Flame Current; Burner Flame; Checkout After Service; TROUBLESHOOTING GUIDE
69-1174 9 S8701/S8702 DIRECT SPARK IGNITION CONTROLS CHECK BURNER FLAME CONDITION NOISY LIFTING FLAME BURNER WAVING FLAME SMALL BLUE FLAME LAZY YELLOW FLAME GOOD RECTIFYING FLAME 1 IN. (25.4 MM) 1/4 TO 1/2 IN. (6.4 TO 12.7 MM) M18055 CHECK FOR:• HIGH GAS PRESSURE• EXCESS PRIMARY AIR OR DRAFT CHECK F...
Page 2 - INSTALLATION; When Installing this Product...; WARNING; Heat; Mounting Auxiliary Controls
69-1174 2 S8701/S8702 DIRECT SPARK IGNITION CONTROLS a Valve used must be designed for DSI application. b Separate spark igniter and flame sensor mounted on a common bracket. INSTALLATION When Installing this Product… 1. Read these instructions carefully. Failure to follow them could damage the prod...
Page 3 - Wiring; General Precautions
69-1174 3 S8701/S8702 DIRECT SPARK IGNITION CONTROLS RMS Temperature Rating Cable Type Voltage Rating ° F ° C UL Style 3257 10,000 482 250 Table 4. Transformer Ratings for S8701/S8702 and Dual Valve Combination Gas Controls. Wiring the S8701/S8702 Control 1. Connect system components to the S8701/S8...
Page 4 - STARTUP AND CHECKOUT; Gas Leak Test; START SYSTEM
69-1174 4 S8701/S8702 DIRECT SPARK IGNITION CONTROLS Fig. 3. S8702 Wiring Diagram. Grounding the S8701/S8702 Spark Igniter andMain Burner For the system to operate properly, spark igniter, flamesensor bracket, the burner (GND) terminal on the 24V(GND) terminal, and the S8701/S8702 control must share...
Page 5 - Check Trial for Ignition; CHECKOUT; Sequence of Operation
69-1174 5 S8701/S8702 DIRECT SPARK IGNITION CONTROLS NOTE: If the gas control has been replaced or serviced,lightoff may not be satisfactory until air has beenpurged from the gas line or the gas input andcombustion air have been adjusted (seemanufacturer’s instructions). Table 6. Trial for Ignition ...
Page 7 - SERVICE; Preliminary Check; START
69-1174 7 S8701/S8702 DIRECT SPARK IGNITION CONTROLS Fig. 5. S8701/S8702 Sequence of Operation for Retry Models (E, F, L and M Models). SERVICE IMPORTANT 1. Only persons trained and experienced in DSI systems should service this equipment. 2. If a condition exists that causes the S8701 or S8702 cont...
Page 8 - Spark Ignition Circuit; Ignition Cable
69-1174 8 S8701/S8702 DIRECT SPARK IGNITION CONTROLS 6. Check the flame sensor and its mounting bracket. Correct the position if bent out of shape. 7. Review the S8701/S8702 normal sequence of operation. See START SYSTEM section. S8701/S8702 COMPONENT CHECKS Spark Ignition Circuit The step-up transf...
Page 9 - Low or Unsteady Flame Current; Burner Flame; Checkout After Service; TROUBLESHOOTING GUIDE
69-1174 9 S8701/S8702 DIRECT SPARK IGNITION CONTROLS CHECK BURNER FLAME CONDITION NOISY LIFTING FLAME BURNER WAVING FLAME SMALL BLUE FLAME LAZY YELLOW FLAME GOOD RECTIFYING FLAME 1 IN. (25.4 MM) 1/4 TO 1/2 IN. (6.4 TO 12.7 MM) M18055 CHECK FOR:• HIGH GAS PRESSURE• EXCESS PRIMARY AIR OR DRAFT CHECK F...