Page 2 - Do not connect the secondary side of the transformer to
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK EN1B-0203GE51 R0507C 2 WIRING Screwless type, spring loaded terminals are provided on the controllers for panel and field wiring. These terminals are suitable for solid conductors as well as tinned or with multicore cable end, strand...
Page 3 - CONFIGURATION AND CONTROL PARAMETERS
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK 3 EN1B-0203GE51 R0507C CONFIGURATION AND CONTROL PARAMETERS The controllers R7426A,B,C include two groups of settings *) (I and II) for control and configuration parameters that are automatically selected during programming. For para...
Page 5 - Parameter Settings and Adjustment.
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK 5 EN1B-0203GE51 R0507C control par. setting I / setting II R7426 no. name description low high def. reso- lution unit A B C actual value P.01 W1 Main setpoint for input T1 0 50 / 130 21 / 70 0.5 ° C x x x P.02 Wlim Limit setpoint (lo...
Page 6 - CONFIGURATION SETTINGS; Direct - Reverse Action; How; Control Point / Setpoint Adjustment CPATYP; remote setpoint unit type; Output Control Range Selection
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK EN1B-0203GE51 R0507C 6 CONFIGURATION SETTINGS The controllers R7426A,B are supplied with unconfigured outputs to avoid damage of installed final control devices by supply of not applicable output signals if the controller power suppl...
Page 7 - Supply of Temperature Signal T2
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK 7 EN1B-0203GE51 R0507C Output Signal Mode YMode (C.11) Sequence Operation The controllers R7426B,C are supplied from the factory configured for sequence operation of heating, mixed air, and cooling control. The sequence operation can...
Page 8 - def
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK EN1B-0203GE51 R0507C 8 Summer / Winter Time Change AddHour / SubHour (C.16 / C.17) These configuration parameters are only available on controllers with RTC. The configuration parameter AddHour or SubHour are required to adjust the m...
Page 9 - Setting Guidelines for Proportional Band of P and
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK 9 EN1B-0203GE51 R0507C limit or cascade sensor (T2) to operate the output device from full open (100%) to full closed (0%) or vice versa. Xp1 is the throttling range for the main control loop, Xp2 is used if limitation or cascade con...
Page 10 - Setting Guidelines for Reset Time of P+I Control; start
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK EN1B-0203GE51 R0507C 10 Setting Guidelines for Reset Time of P+I Control The reset time tr should be adjusted to 2...3 times of the response time T u , which is the time interval between the beginning of a sustained disturbance (e.g....
Page 11 - Calibration of Temperature Sensors; OPERATING OVERVIEW; Display and Operation Elements; DISPLAY
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK 11 EN1B-0203GE51 R0507C Y (%) 100 T ( ) ° C SOFFS SOFFS CTRPH CTRPC Xph Xpc OCCUPIED UNOCCUPIED Fig. 5. Night cycle NightLow and NightHigh The night cycle program automatically cycles between the user selected upper and lower limits ...
Page 12 - Changing Operating Modes
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK EN1B-0203GE51 R0507C 12 Changing Operating Modes Fig. 7 shows the six operating modes. After power-up the controller version is displayed and the controller enters the standard display mode. In this mode, selected input or output val...
Page 13 - Time Out; by the
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK 13 EN1B-0203GE51 R0507C Time Out After approximately 10 min of inactivity (no button has been pressed: time out), each mode returns automatically to standard display mode. Inputs that have not been confirmed by the SET button are ign...
Page 18 - Interpreting Error Messages
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK EN1B-0203GE51 R0507C 18 Programming Holiday Schedule (with RTC, only) The holiday schedule programming is used to program each day of the year (01.01 ... 31.12.) as a holiday (day type = H1, H2 or H3) or as a normal day (day type = H...
Page 20 - Table 17. Weekly schedule and holiday types
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell...