Page 2 - SPYDER® BACNET® PROGRAMMABLE CONTROLLERS; ORDERING INFORMATION; General Specifications
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need furth...
Page 3 - BEFORE INSTALLATION; WARNING; Disconnect power supply before beginning wiring or; INSTALLATION; Mount Actuator onto Damper Shaft; IMPORTANT
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 3 63-2689—05 BEFORE INSTALLATION The controller is available in three models (see Table 1). Review the power, input, and output specifications on page 2 before installing the controller. — Hardware driven by Triac outputs must have a minimum current draw, whe...
Page 4 - Before Mounting Actuator onto Damper
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 4 Fig. 2. Damper with 90 degree CW rotation to open. IMPORTANT Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing. Before Mounting Actuator onto Damper Shaft (PVB0000AS, PVB4022AS a...
Page 5 - Mount Controller; NOTE: The controller may be wired before mounting to a; Terminal blocks are used to make all wiring connections to the; dimensions in inches (mm) for PVB0000AS and
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 5 63-2689—05 IMPORTANT Special precautions must be taken for dampers that open in a CCW direction. The actuator is shipped with its rotation direction set to CW to Open, which applies to the damper direction in steps 1 and 2 above. If the damper shaft rotates...
Page 6 - Panel Mounting; NOTE: The controller is designed so that the cover does; Air flow Pickup; Power
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 6 Panel Mounting The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover. NOTE: The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring. ...
Page 7 - Power Budget
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 7 63-2689—05 The application engineer must review the control job requirements. This includes the sequences of operation for the controller, and for the system as a whole. Usually, there are variables that must be passed between the controller and other Spyde...
Page 8 - Wiring
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 8 required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft. (61m) run from the transformer to a controller drawing 37 VA and using two 18 AWG (1.0 sq mm) wires. The formula is: Loss = [len...
Page 9 - Communications
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 9 63-2689—05 on page 6. The earth ground terminal (terminal 3) must be connected to a verified earth ground for each controller in the group (see Fig. 12 on page 9). — All loads on the controller must be powered by the same transformer that powers the control...
Page 10 - Setting the MS/TP MAC address; Termination Resistors; NOTE: The controller does not provide any network bias-; Shield Terminating; DIP
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 10 Cabling should be selected that meets or exceeds the BACnet Standard which specifies the following: An MS/TP EIA-485 network shall use shielded, twisted-pair cable with characteristic impedance between 100 and 130 ohms. Distributed capacitance b...
Page 11 - Wiring Method; Electrical Shock Hazard.; Disconnect power supply before beginning wiring, or; NOTE: When attaching two or more wires to the same; Wiring Details
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 11 63-2689—05 Fig. 13. Termination modules. Wiring Method WARNING Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipme...
Page 12 - Table 7. Description of wiring terminal connections for; MS/TP MAC ADDRESS DIP SWITCHES
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 12 Table 7. Description of wiring terminal connections for PUB6438S, PVB6436AS, and PVB6438NS. IMPORTANT If the controller is not connected to a good earth ground, the controller's internal transient protection circuitry is compromised and the func...
Page 15 - NOTE: Make sure to set the Configuration DIP Switch as
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 15 63-2689—05 Fig. 18. Controller wiring diagram (model PUB6438S shown) for typical PWM reheat and PWM peripheral heat valve actuator. (For note 2, refer to Fig. 14.) NOTE: Make sure to set the Configuration DIP Switch as shown in Fig. 18. Switches 1 through ...
Page 19 - CHECKOUT; Step 1. Check Installation and Wiring; first
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 19 63-2689—05 Fig. 22. Controller wiring diagram (model PUB6438S shown) for RP7517B pneumatic transducer. CHECKOUT Step 1. Check Installation and Wiring Inspect all wiring connections at the controller terminals, and verify compliance with installation wiring...
Page 20 - Step 3. Checkout Completion; CONTROLLER REPLACEMENT; Do not attempt to modify the physical or electrical; Disconnect power supply before beginning controller; Terminal Block Removal
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 63-2689—05 20 Table 8. Status LED States. BACNET STATUS LED: The LED on the front of the controller, between the BACnet MS/TP terminals and MAC Address DIP Switches, provides a visual indication of the BACnet MS/TP communication status. When the controller re...
Page 21 - Controller Replacement (PVB4024NS
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS 21 63-2689—05 2. Once the terminal block is raised 1/4 in. (6.35 mm) from its alignment pins, grasp the terminal block at its center (for long terminal blocks grasp it at each end) and pull it straight up. Controller Replacement (PVB0000AS, PVB4022AS and PVB6...
Page 24 - Automation and Control Solutions; BACnet
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS Automation and Control Solutions Honeywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.com ® U.S. Registered Trademark© 2012 Honeywell International Inc.63-2689—05 M.S. Rev. 01-12 Printed in United States BACnet ® is a ...