Page 2 - SPECIFICATIONS; General Specifications; BEFORE INSTALLATION; WARNING; INSTALLATION; Mount Actuator onto Damper Shaft
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 62-0287—03 2 SPECIFICATIONS General Specifications Rated Voltage: 20–30 Vac; 50/60 Hz Power Consumption: 100 VA for controller and all connected loads (including the actuator on models PVL0000AS, PVL4022AS, and PVL6436AS) Controller Only Load: 20 VA ...
Page 4 - Mount Controller; Fig. 4. Panel mounting — controller and actuator
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 62-0287—03 4 Mount Controller NOTE: The controller may be wired before mounting to a panel or DIN rail. Terminal blocks are used to make all wiring connections to the controller. Attach all wiring to the appropriate terminal blocks (see “Wiring” on p...
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 5 62-0287—03 Panel Mounting The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover. NOTE: The controller is designed so that the cover does not need to be removed from the base plate for either mounting or...
Page 6 - Fig. 10. Power wiring details for one controller
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 62-0287—03 6 NOTES: — For multiple controllers operating from a single transformer, the same side of the transformer sec- ondary must be connected to the same power input terminal in each controller. Controller config- urations will not necessarily b...
Page 7 - Wiring Method
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 7 62-0287—03 Fig. 12. Power wiring details for two or more controllers per transformer. Wiring Method WARNING Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wirin...
Page 8 - Automation and Control Solutions; Controller Replacement (PVL4024NS and
Page 2 - SPECIFICATIONS; General Specifications; BEFORE INSTALLATION; WARNING; INSTALLATION; Mount Actuator onto Damper Shaft
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 62-0287—03 2 SPECIFICATIONS General Specifications Rated Voltage: 20–30 Vac; 50/60 Hz Power Consumption: 100 VA for controller and all connected loads (including the actuator on models PVL0000AS, PVL4022AS, and PVL6436AS) Controller Only Load: 20 VA ...
Page 4 - Mount Controller; Fig. 4. Panel mounting — controller and actuator
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 62-0287—03 4 Mount Controller NOTE: The controller may be wired before mounting to a panel or DIN rail. Terminal blocks are used to make all wiring connections to the controller. Attach all wiring to the appropriate terminal blocks (see “Wiring” on p...
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 5 62-0287—03 Panel Mounting The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover. NOTE: The controller is designed so that the cover does not need to be removed from the base plate for either mounting or...
Page 6 - Fig. 10. Power wiring details for one controller
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 62-0287—03 6 NOTES: — For multiple controllers operating from a single transformer, the same side of the transformer sec- ondary must be connected to the same power input terminal in each controller. Controller config- urations will not necessarily b...
Page 7 - Wiring Method
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS 7 62-0287—03 Fig. 12. Power wiring details for two or more controllers per transformer. Wiring Method WARNING Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wirin...
Page 8 - Automation and Control Solutions; Controller Replacement (PVL4024NS and