THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional que...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 3 68-0311—02 SPECIFICATIONS Thermostat Description: Electrical Ratings for: Equipment Interface Module and the THX9321 Prestige 2.0 Thermostat NOTE: To find what terminals are available on the Equip- ment Interface Module and the Prestige Th...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 4 Fig. 1. Dimensions of THX9421 Prestige IAQ thermostat in in. (mm). Fig. 2. Dimensions of THX9421 Prestige IAQ cover plates in in. (mm). Fig. 3. Dimensions of THX9321 Prestige ® 2.0 thermostat in in. (mm). Fig. 4. Dimensions of T...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 5 68-0311—02 Table 1. Prestige Kits. Kit Part Number Included in Kit Part Number Description Prestige IAQ Kit YTHX9421R5101WW THX9421R5021WW Thermostat - White Front, White Side THM5421R1021 Equipment Interface Module C7089R1013 Wireless Out...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 6 Table 2. Thermostat Replacement Parts and Accessories. Product Part Number Operating Ambient Temperature Operating Relative Humidity Shipping Temperature Physical Dimensions in in. (mm) Color(s) Thermostat THX9421R5021WW 32 to 1...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 8 SYSTEM INSTALLATION When Installing this Product... 1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazard- ous condition. 2. Check the ratings given in the instructions...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 9 68-0311—02 INSTALLATION OPTIONS The THX9321 Prestige ® 2.0 thermostat is wired directly to the equipment. The THX9421 Prestige ® IAQ thermostat is used with the Equipment Interface Module or with a TrueZONE Wireless Adapter. If using the E...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 10 Installing Equipment Interface Module (if used) If no Equipment Interface Module is used, skip to “Selecting Thermostat Location” beginning on page 12. NOTE: If an EIM is mounted inside a metal cabinet, such as a commercial roo...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 11 68-0311—02 Selecting Return Air Temperature Sensor Mounting Location 1. Install the Return Air Temperature Sensor on the return duct in a location where the air is mixed well. Mount the Return Air Temperature Sensor downstream of a Bypass...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 12 Fig. 14. Installing Discharge and Return Air Temperature Sensors Use the following steps to mount the Discharge/Return Air Sensors: 1. Attach plastic cover to the sensor probe. 2. Drill 1/4-inch hole for the sensor probe and mo...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 13 68-0311—02 4. Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until f...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 14 Mount Thermostat on Wallplate Align thermostat to wallplate and snap into place. See Fig. 19. Fig. 21. Mount thermostat (THX9421). POWER OPTIONAL REDLINK™ ACCESSORIES 1. Install batteries or power the optional RedLINK accesso- ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 15 68-0311—02 TrueSTEAM 1. Wire and power TrueSTEAM. 2. Connect the ABCD terminals between TrueSTEAM and the THM4000 Wireless Adapter. 3. Adjust the DIP Switches on TrueSTEAM as follows when using the Wireless Adapter: • DIP3: UP • DIP4: UP ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 16 2. Follow the prompts on the thermostat screen until you reach the Wireless Setup screen. See Fig. 30. Fig. 30. 3. While the Connected light is flashing green on the EIM, press Next on the thermostat. After a short delay, the s...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 17 68-0311—02 Completing Initial Setup 5. Finish the setup by selecting the desired options. Touch Done after you select the last option you want to change. See “Installer Options” beginning on page 21 for a full listing of setup options. Fi...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 18 6. Press and quickly release the CONNECT button on each new RedLINK accessory. NOTE: For locations of CONNECT buttons on RedLINK accessories, see “Locating the Con- nect Buttons on RedLINK Accessories” begin- ning on page 18. F...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 19 68-0311—02 ERROR MESSAGES: E1 29: Incompatible device cannot be connected. E1 34: Low RF signal. Move device to a different location and try again. E1 38: Make sure the thermostat, EIM, or TrueZONE Wireless Adapter is in Wireless Setup mo...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 20 3. Type the sensor name and press Done. The sensor names are used when selecting which sensor to use for temperature, humidification, and dehumidification con- trol. Fig. 51. NOTE: If you link more than 1 wireless indoor sensor...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 21 68-0311—02 Installer Options The following options are available when you access Installer Options. For more information on each, press Help on the thermostat or see Table 3. Fig. 56. Installer Options screen. NOTE: You can use the thermo...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 68 INSTALLER TESTS Use the installer tests to check out the system: • Equipment Test: Tests the heating, cooling, fan, and IAQ equipment. The test allows you to manually call for each system to ensure the equipment and thermostat ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 69 68-0311—02 Using the Equipment Test 1. Press Equipment Test on the Installer Test screen (see Fig. 61). Turn the equipment on/off as needed and then press Next Test to test the remaining equipment. The time out for the Equipment Test mode...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 70 Mounting Optional Accessories Mounting Outdoor Sensor Mount the sensor where: • it cannot be tampered with. • there is good air circulation. • it can measure true outdoor ambient temperature and humidity. • wire distance betwee...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 71 68-0311—02 Mounting C7189U1005 Wired Indoor Sensor Use the following steps to mount the sensor: 1. Remove the cover from the remote sensor (see Fig. 70). Fig. 70. Remove the cover. 2. Pull wires through wire hole. 3. Position wallplate on...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 72 OPERATION Fig. 73. Quick reference to residential display. Fig. 74. Quick reference to commercial display. HOME. Touch to display Home screen. FAN. Select fan mode. SYSTEM. Select system mode (Heat/Cool). MENU. Touch to display...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 73 68-0311—02 Setting the time/date 1. Touch the current time. The screen displays Set Time/ Set Date. Fig. 75. 2. Touch Set Time or Set Date. Fig. 76. 3. Touch or until the proper time/date is displayed. 4. Touch Done to save or Cancel ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 74 Preset Energy-Saving Schedules This thermostat uses default Energy Saver settings that can reduce your heating/cooling expenses by as much as 33%. * Period 2 is cancelled by default. If you activate it, the values shown above a...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 75 68-0311—02 Overriding schedules: residential use 1. Touch or to adjust the temperature (right side of screen) and the Hold Until time (left side). The schedule will resume when the Hold Until time expires. Fig. 86. 2. Touch Switch to ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 76 3. Touch or to view the status of all the equipment your thermostat is controlling. Depending on how your thermostat was installed, the Equipment Status screen can report data about the following systems: • Heating and cool...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 77 68-0311—02 Setting custom events: commercial use This feature lets you customize temperature settings to be maintained during a specific event. You can set up an event for a specific date or day in a month. The thermostat resumes normal s...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 78 4. Touch or to select the Heat and Cool temperatures. Fig. 105. 5. Review the settings and touch Done to save them. Touch Back, then Cancel to ignore the changes. Setting holiday override: commercial use This feature lets y...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 79 68-0311—02 Depending on how your thermostat was installed, it may delay for up to 30 minutes before switching to REMOTE SETBACK settings. This delay allows the room to stay comfortable if the room is unoccupied for only a short time. Adju...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 80 Adjusting dehumidification settings: commercial use This feature can control a dehumidifier or use your air conditioner to reduce humidity. 1. Touch MENU and select Dehumidification. Fig. 116. 2. Select Auto. 3. Move slider bar...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 82 9. Touch Make Additional Adjustments to continue mak- ing changes, or touch Accept Color Selections when you are satisfied with the selected colors and then touch HOME. Fig. 127. Fig. 128. Setting preferences Preference menu op...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 83 68-0311—02 Adjusting security settings You can adjust security options to prevent unauthorized changes to system settings. 1. Touch MENU and select Security Settings. Fig. 133. 2. Select Change Lock Mode. Fig. 134. 3. Select an option and...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 84 1. Press MENU 2. Scroll to select TEMPORARY SCHEDULE 3. Select option, then follow screen prompts NOTE: See also “Overriding schedules: residential use” beginning on page 75. Utility Scheduling This feature can help reduce fuel...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 85 68-0311—02 Advanced Features ADAPTIVE INTELLIGENT RECOVERY (RESIDENTIAL USE ONLY) Over time, the Prestige® thermostat “learns” how long it takes your system to reach your programmed temperature setting. The thermostat turns on the heating...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 86 Installer options Installer Options require a password and should only be changed by a qualified technician. To prevent unintended changes or damage to your equipment, do not change these options yourself. Fig. 144. Using the t...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 87 68-0311—02 UNIVERSAL INPUTS (S1, S2, S3, S4) S1, S2, S3, and S4 are universal inputs that can be setup to work with a sensor or dry contact device in the Installer Setup. Setup options and compatible sensors are listed below. See wiring d...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 88 7. Delta T Diagnostics is only for non-zoned forced air systems. 8. The thermostat does not provide Heat or Cool Delta T Diagnostics when it is set to control an Economizer module (ISU 2220). 9. The thermostat cannot be setup f...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 89 68-0311—02 5. For Air-to-Air Heat Pumps, press the up/down arrows to set the maximum time duration of a defrost cycle. Default is 10 minutes. Delta T is not monitored during a defrost cycle. Check the heat pump documentation for the defro...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 90 Set Delta T Limits 1. Press Stage 1 to set the limits and run time (see Fig. 158). Use the saved test data located in the upper right corner of the screen to set the Delta T Minimum and Maximum Limits and the Run Time (see Fig....
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 91 68-0311—02 Delta T Alerts are also displayed for performance related issues such as dirty air filter, blocked registers, loss of refrigerant, dirty a-coil, frozen a-coil, cracked heat exchanger, dirty burners, burners need adjustment, etc...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 92 Alerts Log The Alerts Log stores a history of the most recent 25 alerts and records the date and time of each alert. In the Alerts Log, press any of the alerts for more information. You can also press Show Active Alerts to disp...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 93 68-0311—02 User Interactions Log The User Interactions Log can help a service technician save time by determining if the issue is related to a system problem or an accidental user error. The User Interactions Log records the date and time...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 94 Using the Data Logs TO ACCESS THE DATA LOGS 1. From the Home screen, press Menu. 2. Scroll down and press Installer Options. 3. Enter the password (date code) and press Done. 4. Press Data Logs. 5. Press the log you want to vie...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 95 68-0311—02 4. Select the desired time period at the top of the screen (Hourly, Daily, Weekly or Monthly). Use the Up/Down arrows to scroll for Delta T, Discharge Temperature, Return Temperature, Outdoor Temperature/Humidity and Indoor Tem...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 96 When the user presses the alert for more info, the Notification screen is displayed, prompting them to contact their dealer. See Fig. 185 as an example. Fig. 185. The following dry contact alerts are available. Full Drain Pan A...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 97 68-0311—02 1. Wire the dry contact device to S1, S2, S3, or S4 termi- nals at the EIM. 2. Enter Installer Setup (see “Installer Options” beginning on page 21). 3. Dry Contacts are selected at ISU 6000. Select the appro- priate Dry Contact...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 98 Cool Differential The indoor temperature must rise to the selected differential setting before the thermostat turns on the stage of cooling. For example, if stage 2 is set to 2 °F (1.0 °C), the indoor temperature must be 2 °F (...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 99 68-0311—02 2. Default is Comfort. Adjust differentials as needed. Fig. 195. Backup Heat Upstage Timer The Backup Heat Upstage Timer is available for any system with 2 heating types and the Backup Heat Differential is set to 2 °F (1.0 °C) ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 100 HEAT PUMP AND BACKUP HEAT OPERATION Heat pump with outdoor temperature lockouts Outdoor temperature lockouts are optional. See Installer Setup options (ISU 3120). Geothermal Radiant Heat The thermostat can be setup to control ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 101 68-0311—02 Fossil Fuel Backup Heat (Backup Heat NOT Allowed to Run with Heat Pump) HEAT MODE The thermostat turns on Backup Heat only when the indoor temperature drops to the selected Backup Heat Differential setting or the Backup Heat U...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 102 INDOOR AIR QUALITY (IAQ) CONTROL Humidification The thermostat reads the indoor humidity level and allows the user to set a humidification setting with or without window protection. The thermostat can be set up to control a hu...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 104 7. Set the desired lockout option. See Fig. 214. Fig. 214. NOTE: ISU 10140 gives the option to lockout ventila- tion during calls for humidification. This helps maintain the desired humidity level. Control Humidification Level...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 105 68-0311—02 Dehumidification - Residential The thermostat reads the indoor humidity level and allows the user to set a dehumidification setting. The thermostat controls the humidity level using the cooling system or a whole house dehumidi...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 106 5. Select whether the U1, U2, or U3 terminals are Normally Open or Normally Closed. See Fig. 220. • Normally Open – contacts are normally open and will close during a call for dehumidification • Normally Closed – contacts are ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 107 68-0311—02 4. Select the terminals wired to the Whole House Dehumid- ifier. See Fig. 225. Fig. 225. 5. Select the system mode(s) to allow dehumidification. See Fig. 226. NOTE: Heat includes Heat, Emergency Heat and Auto. If the system is...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 108 Set up Dehumidification Away Mode 1. Select Allowed at ISU 9180. See Fig. 231. Fig. 231. 2. Set Fan Control settings. See Fig. 232. • On: Fan is always on. • Automatic: Fan runs only when cooling system is on. • Circulate: Fan...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 109 68-0311—02 Dehumidification - Commercial The thermostat reads the indoor humidity level and allows the user to set a dehumidification setting. The thermostat controls the humidity level using the cooling system or a dehumidifier. If humi...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 110 2. If optional remote wireless indoor sensors are installed, you can choose which sensor you want to use for dehu- midification control. For example, you can use one sen- sor for humidification control, and another for dehumid...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 112 Dehumidification Away Mode Dehumidification Away Mode for a commercial application is identical to Dehumidification Away Mode for a residential application. See “Dehumidification Away Mode” on page 107 and “Set up Dehumidifica...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 113 68-0311—02 Ventilation Fan Control (ISU 10060) • Thermostat Controls Fan The thermostat turns on the ventilator and the fan when ventilation is needed. • Equipment Controls Fan The thermostat turns on the ventilator when ventilation is n...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 114 4. Select the Ventilation Fan Control. See “Ventilation Fan Control (ISU 10060)” on page 113 for more information. See Fig. 251.NOTE: ISU 10060 is only displayed if the Ventilation Type is ERV / HRV. The thermostat controls th...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 115 68-0311—02 8. If Percent On Time was selected for ISU 10050, select the Ventilation Percent on Time. See Fig. 255. Fig. 255. 9. Select the Outdoor Condition Lockouts. See “Ventilation — Outdoor Condition Lockouts (ISU 10130)” on page 113...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 116 4. Press MORE SETTINGS to change maintenance reminders or set outdoor lockouts (if set to Yes, ventila- tion will not run when outdoor conditions exceed values set by the installer). NOTE: If set up for humidification in heat ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 117 68-0311—02 Custom Reminders include: • Service Reminder — Set up for recurring or one time only. • Spring Service Reminder — Provide an alert based on date or outdoor temperature. • Fall Service Reminder — Provide an alert based on date ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 119 68-0311—02 7. The preview of the custom reminder shows you what you’ve selected. Press Done to accept the reminder, or press Back to change it. Fig. 273. 8. The New Custom Reminder will look like this on the Home Screen: Fig. 274. 9. Whe...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 120 Loading Dealer Information Prestige thermostats can display the dealer’s contact information and logo on the screen, making it easy for users to contact them for post-sale support and service. After saving the dealer’s contact...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 121 68-0311—02 COMMERCIAL FEATURES The thermostat can be setup for residential or light commercial applications (ISU 1010). When the thermostat is setup for commercial, the thermostat meets commercial code, Title 24 and provides the followin...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 123 68-0311—02 4. Touch or to select the Heat and Cool temperatures. Fig. 290. 5. Review the settings and touch Done to save them. Touch Back, then Cancel to ignore the changes. Setting holiday override: commercial use This feature lets ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 124 automatically adjust the ramp rate based on outdoor conditions. This allows the thermostat to save energy by starting recovery at the optimum time as outdoor conditions change. NOTE: The thermostat uses an adjustable ramp rate...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 126 Economizer and Time of Day (TOD) Operation Economizer The thermostat controls an economizer module to provide ventilation during occupied periods and free cooling when outdoor conditions are favorable. In some climates the coo...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 127 68-0311—02 Battery Replacement Wireless Indoor Sensor Replace batteries in your indoor sensor when a warning appears on the thermostat screen, about two months before batteries are depleted. When the sensor status light begins flashing r...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 128 OPTIONAL ACCESSORIES PORTABLE COMFORT CONTROL If you have only one thermostat, you move this remote control from room to room (like a portable thermostat), to make sure the temperature is comfortable in the room you’re using. ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 129 68-0311—02 PORTABLE COMFORT CONTROL The Portable Comfort Control communicates wirelessly with the thermostat, and can control up to 16 thermostats, though each thermostat can only be connected to 1 Portable Comfort Control. If you have o...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 130 REMOTE INDOOR SENSORS For installation, see “Mounting C7189R1004 Wireless Indoor Sensor” on page 70, and “Mounting C7189U1005 Wired Indoor Sensor” on page 71. For wiring, see “Wiring guide — Wired Indoor Sensors” on page 154. ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 131 68-0311—02 Temperature Display The temperature reading displayed on the home screen is from the sensor or sensors that are being used for temperature control. In Fig. 313, the temperature reading is the average of the thermostat internal...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 133 68-0311—02 Calibration - Outdoor Sensor The C7089U1006 Outdoor Sensor is calibrated at the factory and cannot be recalibrated in the field. Calibration - Indoor Sensor The C7189U1005 Wall Mount Temperature Sensor is calibrated at the fac...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 134 BACKUP CONTROL This section explains when backup control is used. For example, if batteries in the wireless indoor sensors are depleted. If the Thermostat is Part of the Temperature Average 1. The thermostat controls the syste...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 135 68-0311—02 WIRING See Table 13 for Equipment Interface Module terminal descriptions and Table 14 for thermostat terminal descriptions. * Remove jumpers when separate transformers are used. † See “Wiring IAQ Equipment or a Heat/Cool Stage...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 138 EIM Wiring Diagrams Typical wiring of a conventional system with up to 3-stage heat and 2-stage cool with one transformer. Fig. 319. EIM wiring guide — conventional systems. 1 See guides on following pages for thermostat wirin...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 141 68-0311—02 THX9321 Thermostat Wiring Diagrams Typical wiring of a 3-heat / 2-cool heat pump system with one transformer. Fig. 322. Prestige THX9321 and heat pump system with one transformer. Typical wiring of a 2-heat / 2-cool convention...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 143 68-0311—02 Fig. 328. 2-Wire Zone Valve with end switch. Fig. 329. Series 20 hot water heat. Fig. 330. AQ2000 series panels or other hot water relay panels. Fig. 331. Heat pump with oil forced air backup. TRANSFORMER THERMOSTAT/EIM R IS J...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 145 68-0311—02 Fig. 333. Wood stove-fired hot water fan coil with forced air furnace backup heat. Fig. 334. Hot water radiant heat with backup heat (single zone application). W W2 W3 W Y G R C CONFIGURE THE THERMOSTAT TO ENERGIZE THE FAN WIT...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 147 68-0311—02 Fig. 336. Hot water radiant heat with backup forced air heat. Zoned with forced air zone panel and hot water panel. Fig. 337. Hot water fan coil with forced air furnace backup heat. M31485 HOT WATER RELAY PANEL RH W W W2 W3 W ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 148 Fig. 338. Wood stove with heat pump and backup electric strips. (For applications in which the thermostat only needs to run the blower fan when stove is hot). 1 Select Geothermal Radiant Heat at ISU 2010. Connect Fan to U1, U2...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 149 68-0311—02 Wiring IAQ Equipment or a Heat/Cool Stage to the Universal Terminals To Equipment Interface Module “U” terminals can be used for humidification, dehumidification or ventilation. Fig. 339. Wiring a powered humidifier. Fig. 340....
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 151 68-0311—02 Economizer Module Wiring Diagrams Typical wiring of a W7220 Economizer Module for a heat pump system, using a Prestige THX9321 thermostat or Equipment Interface Module. Fig. 346. Wiring a W7220 Economizer Module for a heat pum...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 153 68-0311—02 Wiring C7089U1006 Outdoor Sensor CAUTION Electrical Interference (Noise) Hazard. Can cause erratic system operation. Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballast...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 154 Wiring guide — Wired Indoor Sensors Use the S1, S2, S3, or S4 terminals for wired sensors. CAUTION Electrical Interference (Noise) Hazard. Can cause erratic system operation. Keep wiring at least one foot away from large induc...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 155 68-0311—02 ZONING The following diagrams show the wiring for zoning with different IAQ equipment. Fig. 355. Prestige IAQ thermostats with an HZ432 zone panel and no IAQ control. C R C R C R C R RHRC W1/E W2W3 Y1Y2 GO B DS/BK MCR34669 TRA...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 156 Zoning and Humidification Fig. 356. Prestige IAQ controlling one zone with an HZ432 zone panel and a TrueSTEAM humidifier. Setting up Humidification Control on Prestige or Prestige IAQ Select the terminals wired to the humidif...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 157 68-0311—02 Zoning and Ventilation Fig. 357. Ventilation with zoning. Setting up Ventilation Control on Prestige or Prestige IAQ Select the terminals wired to the ventilator at ISU 10020 (U1, U2, U3). In Fig. 357, the ventilator is wired ...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 68-0311—02 158 Zoning FAQs Q: How does the Prestige or Prestige IAQ thermostat control a humidifier in zoned systems? A: If ISU 8070 Humidification Control is set to Humidify on Demand: Thermostat Controls Fan, then the zone panel will close...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM 159 68-0311—02 TROUBLESHOOTING REGULATORY INFORMATION FCC Compliance Statement (Part 15.19) (USA only) This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause har...
THX9321 PRESTIGE ® 2.0 AND THX9421 PRESTIGE ® IAQ WITH EIM Automation and Control Solutions Honeywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.com ® U.S. Registered Trademark© 2013 Honeywell International Inc.68-0311—02 M.S. Rev. 04-13Printed in United Stat...
Honeywell Manuals
-
Honeywell DT8050A
Installation Manual
-
Honeywell DT8050A
Manual
-
Honeywell DT8050A
User Manual
-
Honeywell DT8050
Manual
-
Honeywell DT8050
User Manual
-
Honeywell TPFIT25WK
User Manual
-
Honeywell TPFIT25AWK
User Manual
-
Honeywell TPFIT32WK
User Manual
-
Honeywell TPFIT32AWK
User Manual
-
Honeywell 24DX47
User Manual
-
Honeywell 24DX47
Manual
-
Honeywell TPFIT50PWK
User Manual
-
Honeywell TPFIT50WK
User Manual
-
Honeywell TPFIT50AWK
User Manual
-
Honeywell TPFIT50APWK
User Manual
-
Honeywell 00010
User Manual
-
Honeywell ADVBLEWIFI
Manual
-
Honeywell ADVBLEWIFI
User Manual
-
Honeywell ADVBLE
Manual
-
Honeywell ADVBLE
User Manual